Bryant 355CAV installation instructions Vent Termination Kit Direct Vent/2-Pipe System Only

Page 38

355CAV

Vent Termination Kit (Direct Vent/2-Pipe System Only)

NOTE: Always refer to the instructions in termination kit for the latest version.

Combustion air and vent pipes MUST terminate outside structure. A factory accessory termination kit must be installed as shown in Table 8. There are four options of vent/combustion air termination kits available as shown in Table 8.

NOTE: Combustion air pipe must have the same diameter as vent pipe.

Concentric Vent / Combustion Air Termination Kit (Direct Vent / 2-Pipe System Only

Determine an appropriate location for termination kit using the guidelines provided in section “Vent Termination: General” in this instruction.

1.Cut one 4-in. diameter hole for 2-in. kit, or one 5-in. diameter hole for 3-in. kit.

2.Loosely assemble concentric vent/combustion air termination components together using instructions in kit.

3.Slide assembled kit with rain shield REMOVED through hole.

NOTE: Do not allow insulation or other materials to accumulate inside of pipe assembly when installing it through hole.

Roof terminations-Locate assembly through roof to appropriate height as shown in Fig. 36 or Fig. 37.

Sidewall terminations-Locate assembly through sidewall with rain shield positioned no more than 1-in (25.4mm). from wall as shown in Fig. 36 and Fig. 37.

4.Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.

5.Check required dimensions as shown.

Two-Pipe Termination Kit (Direct Vent/2-Pipe System Only)

Determine an appropriate location for termination kit using the guidelines provided in section “Vent Termination: General” in this instruction.

1.Cut 2 holes, 1 for each pipe, of appropriate size for pipe size being used.

2.Loosely install elbow in bracket and place assembly on combustion-air pipe.

Roof terminations-Loosely install pipe coupling on properly cut vent pipe. Coupling must be positioned so bracket will mount as shown in Fig. 38.

For applications using combustion-air pipe option, indicated by dashed lines in Fig. 36, install 90_ street elbow into 90_ elbow, making a U-fitting. A 180_ U-fitting may be used.

Sidewall terminations-Install bracket as shown in Fig. 36.

For applications using vent pipe option indicated by dashed lines in Fig. 36, rotate vent elbow 90_ from position shown in Fig. 36

.

3.Disassemble loose pipe fittings. Clean and cement using same procedures as used for system piping.

4.Check required dimensions as shown in Fig. 36.

(Direct Vent/2-Pipe System ONLY)-When 2 or more 355CAV furnaces are vented near each other, 2 vent terminations may be installed as shown in Fig. 36, but next vent termination must be at least 36 in. (914.4mm) away from first 2 terminations. It is important that vent terminations be made as shown in Fig. 36 to avoid recirculation of flue gases.

38

Image 38
Contents Installation Instructions Table of ContentsRequired Notice for Massachusetts Installations Safety Considerations CUT HazardDimensions In. / mm Dimensional DrawingInstallation Codes and Standards Applications Electrostatic Discharge ESD PrecautionsIntroduction Upflow ApplicationCondensate Trap Tubing Alternate Upflow Orientation Condensate Trap Alternate Upflow OrientationCarbon Monoxide Poisoning Hazard Condensate Trap Freeze Protection Upper Inducer Housing Drain ConnectionCondensate Trap Field Drain Attachment Downflow Applications Condensate Trap LocationHorizontal Left Tube Configuration Horizontal Left SUPPLY-AIR Discharge ApplicationsProperty Damage Manual Shutoff GAS Valve Sediment Trapcondensate TrapUnit Operation Hazard Horizontal Right SUPPLY-AIR Discharge ApplicationsConstruct a Working Platform Location Condenste Trap Field Drain AttachmentProhibit Installation on Back Fire or Death HazardUnit MAY not Operate Hazard InstallationFIRE, EXPLOSION, Injury or Death Hazard Furnace, Plenum, and Coil Assembly or Coil Box Locations Reqd PER ROD AIR Ducts Unit MAY not Operate Fire HazardFIRE, Carbon Monoxide and Poisoning Hazard Fire or Explosion Hazard Bottom Closure PanelGas Piping Removing Bottom Closure Panel Electrical Shock Hazard WiringMaximum Capacity of Pipe Disconnect Switch and Furnace Electrical Shock and Fire HazardFire or Electrical Shock Hazard Factory Installed J-Box LocationAccessories AIR for Combustion and Ventilation Fire and Explosion HazardDescription AstmMaterial Pipe Fittings CementFurnace Control Direct Vent Termination Clearance Ventilated Combustion Air Vent Termination Clearance Vent Pipe Termination for Ventilated Combustion Air System Combustion AIR Pipe Unit Corrosion HazardAttachment of Combustion Air Intake Housing Plug Fitting Combustion Air Termination Ventilated Combustion Air OptionCarbon Monoxide Poisoning Property Damage Hazard Vent PipeCombustion Air Termination-Direct Vent / 2-Pipe System Attachment of Vent Pipe304.8mm minimum 76.2mm minimum Vent Termination Extended Exposed Sidewall PipesVent Termination Kit Direct Vent/2-Pipe System Only Two-Pipe Termination Kit Direct Vent/2-Pipe System Only042060 Maximum Allowable Pipe Length Ft / M BtuhUnit Size Condensate Drain Personal Injury HazardContinuous Fan CF Setup Switches START-UP, Adjustment and Safety CheckAir Conditioning A/C Setup Switches Additional Setup Switches SW4Example of Setup Switch in Off Position Prime Condensate Trap with WaterWiring Diagram Inducer Housing Drain Tube Furnace Setup Switch DescriptionSequence of Operation Purge Gas LinesTwo-Stage Thermostat and Two-Stage Low / High Heating Thermidistat Mode See -55 for thermostat connectionsContinuous Blower Speed Selection from Thermostat Super Dehumidify ModeContinuous Blower Mode Heat PumpStep-Modulating Furnace with Single-Speed Air Conditioning Pump Furnace and Two-Speed Air Conditioner Furnace and Two-Speed Heat PumpSet Gas Input Rate Redundant Automatic Gas ValveBurner Orifice A07253 A07254 Altitude Derate Multiplier for U.S.A Burner FlameSet Thermostat Heat Anticipator Set Temperature RiseGas Rate cu Ft/Hr Check Pressure Switches ChecklistCheck Safety Controls Check Primary Limit ControlChecklist Installation Combustion and Vent Piping
Related manuals
Manual 14 pages 23.93 Kb Manual 62 pages 7.79 Kb

355CAV specifications

The Bryant 355CAV is a state-of-the-art automated vertical machining center designed to enhance precision and efficiency in the manufacturing sector. Renowned for its robust construction, this machine is engineered to handle a broad spectrum of machining tasks, making it suitable for both small and large-scale production environments.

One of the standout features of the Bryant 355CAV is its advanced CNC control system, which provides users with exceptional ease of use. The intuitive user interface allows operators to program complex machining operations with minimal effort, significantly reducing setup times. The machine's high-speed spindle achieves impressive rotational speeds, which allows for quick material removal, ultimately optimizing productivity and throughput.

The Bryant 355CAV exhibits superior rigidity and stability due to its solid cast iron frame and carefully designed structural components. This construction minimizes vibrations during machining, ensuring that even the most intricate parts are produced with high accuracy. The machine's precision ground linear guideways further enhance its performance by providing smooth motion and high load capacity.

Equipped with a large work envelope, the Bryant 355CAV enables manufacturers to accommodate various part sizes and geometries. Additionally, its automatic tool changers can hold a variety of tools, thus facilitating quick transitions between different machining operations without requiring manual intervention. This flexibility is essential for meeting the diverse needs of modern manufacturing.

Another notable characteristic of the Bryant 355CAV is its energy-efficient design. It integrates modern technologies aimed at reducing power consumption while maintaining optimum performance. This environmentally conscious approach not only cuts operational costs but also aligns with the growing demand for sustainable manufacturing practices.

Moreover, the Bryant 355CAV features advanced monitoring capabilities, allowing operators to track machine performance in real time. Data analytics from these systems can be utilized to improve operational efficiency, reduce downtime, and enhance predictive maintenance protocols.

In summary, the Bryant 355CAV is a versatile, high-performance machining center that showcases cutting-edge features and technologies. Its combination of user-friendly controls, sturdy construction, energy efficiency, and advanced monitoring positions it as a vital asset for manufacturers aiming to elevate their productivity and precision in an increasingly competitive landscape.