Bryant 355MAV Procedure 5-FILTER Arrangement, Filter Information, Procedure 7-GAS Piping

Page 22

PROCEDURE 5—FILTER ARRANGEMENT

WARNING: Never operate unit without a filter or with filter access door removed. Failure to follow this warning can cause fire, personal injury, or death.

The air filter arrangement will vary due to application, furnace orientation, and filter type. The filter may be installed in an external Filter/Media cabinet (if provided) or the furnace blower compartment. Factory supplied washable filters are shipped in the blower compartment.

If a factory-supplied external Filter/Media cabinet is provided, instructions for its application, assembly, and installation are packaged with the cabinet. The Filter/Media cabinet can be used with the factory-supplied washable filter or a factory-specified high-efficiency disposable filter (see cabinet instructions).

If installing the filter in the furnace blower compartment, determine location for filter and relocate filter retaining wire if necessary. See Table 2 to determine correct filter size for desired filter location. Table 2 indicates filter size, location, and quantity shipped with this furnace. See Fig. 2 for location and size of bottom and side return-air openings.

Table 2—Filter Information

AIR FILTER LOCATED IN BLOWER COMPARTMENT

FURNACE

FILTER SIZE (IN.)*

 

FILTER

CASING

 

 

 

Side Return

 

Bottom Return

TYPE

WIDTH (IN.)

 

 

 

17-1/2

(1) 16 X 25 X 1†

 

(1) 16 X 25 X 1†

Cleanable

21

(1) 16 X 25 X 1

 

(1) 20 X 25 X 1†

Cleanable

24-1/2

(1 or 2) 16 X 25 X 1

 

(1) 24 X 25 X 1†

Cleanable

 

 

 

 

 

*Filters may be field modified by cutting filter material and support rods (3) in filters. Alternate sizes and additional filters may be ordered from your dealer.

Factory-provided with furnace.

CAUTION: Use care when cutting support rods in filters to protect against flying pieces and sharp rod ends. Wear safety glasses, gloves, and appropriate protective clothing. Failure to follow this caution could result in personal injury.

CAUTION: For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.

NOTE: Side return-air openings can ONLY be used in UPFLOW configurations. Install filter(s) as shown in Fig. 23. For bottom return-air applications, filter may need to be cut to fit some furnace widths. Install filter as shown in Fig. 24. NOTE: Remove and discard bottom closure panel when bottom inlet is used.

WASHABLE

FILTER

FILTER

RETAINER

A93045

Fig. 23—Filter Installed for Side Inlet

PROCEDURE 6—BOTTOM CLOSURE PANEL

These furnaces are shipped with bottom enclosure panel installed in bottom return-air opening. This panel MUST be in place when side return air is used.

To remove bottom closure panel, perform the following:

1.Tilt or raise furnace and remove 2 screws holding front filler panel. (See Fig. 25.)

2.Rotate front filler panel downward to release holding tabs.

3.Remove bottom closure panel.

4.Reinstall front filler panel and screws.

PROCEDURE 7—GAS PIPING

Gas piping must be installed in accordance with national and local codes. Refer to current edition of NFGC in the United States. Canadian installations must be made in accordance with NSCNGPIC and all authorities having jurisdiction.

Gas supply line should be a separate line running directly from meter to furnace, if possible. Refer to Table 3 for recommended gas pipe sizing.

—22—

Image 22
Contents Installation, Start-up, and Operating Instructions Table of ContentsLocation Introduction Safety ConsiderationsCodes and Standards Dimensions Unit SizeInstaller Packet Includes Clearances to CombustiblesElectrostatic Discharge ESD Precaution Procedure Applications Procedure 1-GENERALCondensate Trap Location Factory-Shipped Orientation Procedure 2-UPFLOW ApplicationsCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Location Alternate Upflow Orientation Condensate Trap Tubing Alternate Upflow OrientationCondensate Trap Field Drain Attachment Pressure Switch TubingProcedure 3-DOWNFLOW Applications Condensate Trap Freeze ProtectionDownflow Tube Configuration Right-Hand Trap Installation Condensate Trap TubingCondensate Trap Field Drain Attachment Condensate Trap Field Drain Attachments Construct a Working PlatformAttic Location and Working Platform Horizontal Right Tube Configuration Location Procedure 1-GENERAL Furnace Location for Proper Condensate DrainageProhibit Installation on Back Procedure 2-LOW-FIRE only InstallationProcedure 4-HAZARDOUS Locations Procedure 3-FURNACE Location Relative to CoolingequipmentInstallation Procedure 1-LEVELING Legs if Desired Opening Dimensions Furnace Plenum Opening Floor OpeningFloor and Plenum Opening Dimensions Procedure 3-INSTALLATION in Horizontal ApplicationsProcedure 4-AIR Ducts General RequirementsSupply Air Connections Ductwork Acoustical TreatmentReturn Air Connections Procedure 7-GAS Piping Procedure 5-FILTER ArrangementProcedure 6-BOTTOM Closure Panel Filter InformationBottom Filter Arrangement Nominal Length of Pipe FT Maximum Capacity of PipeInternal Pipe Diameter Size Procedure 8-ELECTRICAL Connections WiringAccessories Electrical DataProcedure 9-DIRECT Venting Removal of Existing Furnaces from Common Vent SystemsUnit Wiring Diagram Control Center Combustion-Air and Vent Piping355MAV Variable Speed Furnace Control Location Clearance FT OpeningCombustion-Air and Vent Pipe Connections Short Vent 5 to 8 ft System Maximum Allowable Pipe Length ft Altitude FT4001 to 5000‡ Intake Housing Plug Fitting Drain Roof Termination Preferred Concentric Vent and Combustion-Air RoofTermination Preferred Sidewall Termination of Less than 12 Multiventing and Vent Terminations Procedure 10-CONDENSATE DrainGeneral Condensation Drain Protection ″ 25 mm Maximum TYP Example of Field Drain Attachment Sequence of OperationProcedure 3-HEATING MODE-TWO Stage Procedure 1-SELF-TEST ModeProcedure 2-HEATING Mode Procedure 4-EMERGENCY Heat ModeSingle-Speed Applications Procedure 5-COOLING ModeProcedure 6-HEAT Pump Mode Two-Speed ApplicationsProcedure 7-CONTINUOUS FAN Mode Procedure 8-COMPONENT TestProcedure 9-BYPASS Humidifier Mode Procedure 10-DEHUMIDIFICATION ModeSTART-UP Procedures Procedure 1-GENERAL Procedure 11-ZONE ModeProcedure 2-SELECT Setup Switch Positions AIR Setup Allowable Furnace Model Setup Air Conditioning A/C Airflow Switch PositionSetup Switches SW Switch Position TonsProcedure 4-PURGE GAS Lines Procedure 3-PRIME Condensate Trap with WaterProcedure 5-ADJUSTMENTS Filling Condensate Trap Heat Value Altitude AVG GAS Specific Gravity of Natural GASAltitude United States Canada Set Temperature Rise Redundant Automatic Gas ValveExample Altitude Derate Multiplier for U.S.ASet Thermostat Heat Anticipator Altitude Percent Derate MultiplierGas Rate Cu Ft/Hr Procedure 6-CHECK Safety ControlsCheck Pressure Switches Check Primary Limit ControlProcedure 7-CHECKLIST Amp Draw Check with AmmeterCHECKLIST-INSTALLATION Combustion and Vent Piping CHECKLIST-START-UPBook/Tab 1/6 Catalog No
Related manuals
Manual 12 pages 42.74 Kb

355MAV specifications

The Bryant 355MAV is a remarkable model that stands out in the HVAC (heating, ventilation, and air conditioning) industry for its efficiency, reliability, and advanced technology. This unit is specifically designed to provide homeowners with excellent comfort while maintaining energy efficiency, making it an ideal choice for residential applications.

One of the standout features of the Bryant 355MAV is its variable speed compressor. This technology allows the system to adjust its cooling output based on the current temperature needs of the home. By operating at multiple speed levels, the compressor can maintain a more consistent indoor climate while using significantly less energy than traditional single-speed systems. This capability translates to lower energy bills and enhanced comfort.

Additionally, the Bryant 355MAV integrates an advanced control system that offers precise temperature regulation. Homeowners can easily set their desired indoor conditions, and the thermostat will communicate with the system to ensure optimal performance. This smart technology not only enhances comfort but also extends the lifespan of the unit by preventing unnecessary strain during operation.

The 355MAV also features significant advancements in sound reduction technology. Designed with noise-absorbing materials and a quiet operation mode, this unit ensures that indoor comfort is maintained without the disruption of loud operational sounds. This makes it a perfect choice for residential settings, particularly in areas where noise sensitivity is a concern.

Energy efficiency is another key characteristic of the Bryant 355MAV. The unit is certified with a high Seasonal Energy Efficiency Ratio (SEER) rating, which means it meets strict energy consumption standards. This not only reflects its eco-friendliness but also contributes to significant savings on utility bills over time.

Moreover, the Bryant 355MAV uses environmentally friendly refrigerants that comply with EPA regulations, further solidifying its commitment to sustainability. This, combined with durable construction and a reliable warranty, ensures that homeowners can expect lasting performance from the system.

In conclusion, the Bryant 355MAV offers an impressive array of features, including a variable speed compressor, advanced control systems, sound reduction technology, and high energy efficiency. These characteristics make it an exceptional option for those seeking a reliable and efficient HVAC solution in their homes. With its commitment to comfort, savings, and sustainability, the Bryant 355MAV continues to be a popular choice among homeowners looking to enhance their indoor environments.