NOT IN HORIZONTAL SECTION

FURNACE

PIPE DIAMETER

TRANSITION IN

VERTICAL SECTION

A93034

Fig. 35—Combustion-Air and Vent Pipe Diameter Transition Location and Elbow Configuration

Table 5—Combustion-Air and Vent Pipe Termination Clearances

LOCATION

 

CLEARANCE (FT)

U.S.A.

 

Canada

 

 

Above grade level or aboveanticipated snow depth

1

 

1†

Dryer/Water heater ventt

3

 

3

From plumbing vent stack

3

 

3

From any mechanical fresh air intake

See note 4

 

6

For furnaces with an input capacity of100,000 Btuh or less—from any non-

 

 

 

mechanical air supply (windows or doorswhich can be opened) or combustion-air

1

 

1

opening

 

 

 

For furnaces with an input capacity greaterthan 100,000 Btuh or less—from any non-

 

 

 

mechanical air supply (windows or doorswhich can be opened) or combustion-air

1

 

3

opening

 

 

 

From service regulator vent, electric and gas meters and relief equipment

4*

 

6‡

Above grade when adjacent to public walkway

Note 3

 

Note 3

* Horizontal distance.

18 in. above roof surface in Canada.

‡ 36 in. to electric meter in Canada only.

NOTES:

1.If installing 2 adjacent 355MAV furnaces, refer to Multiventing and Vent Terminations section for proper vent configurations.

2.When locating combustion-air and vent terminations, consideration must begiven to prevailing winds, location, and other conditions which may cause recirculation of the appliance’s own flue products or the flue products of adjacent vents. Recirculation can cause poor combustion, inlet condensate problems, and accelerated corrosion of heat exchangers.

3.Vent termination can not terminate less than 2 ft horizontal and 7 ft above public walkway or where condensate vapor or droplets may be a hazard.

4.Vent termination must be at least 3 feet above any forced draft inlets within 10 feet horizontal. Vent termination must be at least 3 feet horizontal from other direct vent appliances intake unless otherwise specified by manufacturer.

Other gas appliances with their own venting system may also use the abandoned chimney as a raceway providing it is permitted by local code, the current edition of the National Fuel Gas Code and the vent or liner manufacturer’s installation instructions. Care must be taken to prevent the exhaust gases from one appliance from contaminating the combustion air of other gas appliances.

CAUTION: When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a raceway, pipe must be insulated as shown in Table 8 with Armaflex-type insulation.

—31—

Image 31
Contents Table of Contents Installation, Start-up, and Operating InstructionsLocation Introduction Safety ConsiderationsCodes and Standards Unit Size DimensionsClearances to Combustibles Installer Packet IncludesApplications Procedure 1-GENERAL Electrostatic Discharge ESD Precaution ProcedureCondensate Trap Location Factory-Shipped Orientation Procedure 2-UPFLOW ApplicationsCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Tubing Alternate Upflow Orientation Condensate Trap Location Alternate Upflow OrientationCondensate Trap Freeze Protection Pressure Switch TubingProcedure 3-DOWNFLOW Applications Condensate Trap Field Drain AttachmentCondensate Trap Tubing Downflow Tube Configuration Right-Hand Trap InstallationCondensate Trap Field Drain Attachment Construct a Working Platform Condensate Trap Field Drain AttachmentsAttic Location and Working Platform Horizontal Right Tube Configuration Furnace Location for Proper Condensate Drainage Location Procedure 1-GENERALProcedure 2-LOW-FIRE only Installation Prohibit Installation on BackProcedure 4-HAZARDOUS Locations Procedure 3-FURNACE Location Relative to CoolingequipmentInstallation Procedure 1-LEVELING Legs if Desired Furnace Plenum Opening Floor Opening Opening DimensionsProcedure 3-INSTALLATION in Horizontal Applications Floor and Plenum Opening DimensionsGeneral Requirements Procedure 4-AIR DuctsSupply Air Connections Ductwork Acoustical TreatmentReturn Air Connections Filter Information Procedure 5-FILTER ArrangementProcedure 6-BOTTOM Closure Panel Procedure 7-GAS PipingBottom Filter Arrangement Nominal Length of Pipe FT Maximum Capacity of PipeInternal Pipe Diameter Size Wiring Procedure 8-ELECTRICAL ConnectionsElectrical Data AccessoriesRemoval of Existing Furnaces from Common Vent Systems Procedure 9-DIRECT VentingUnit Wiring Diagram Combustion-Air and Vent Piping Control Center355MAV Variable Speed Furnace Control Opening Location Clearance FTCombustion-Air and Vent Pipe Connections Short Vent 5 to 8 ft System Altitude FT Maximum Allowable Pipe Length ft4001 to 5000‡ Intake Housing Plug Fitting Drain Roof Termination Preferred Concentric Vent and Combustion-Air RoofTermination Preferred Sidewall Termination of Less than 12 Multiventing and Vent Terminations Procedure 10-CONDENSATE DrainGeneral Condensation Drain Protection ″ 25 mm Maximum TYP Sequence of Operation Example of Field Drain AttachmentProcedure 4-EMERGENCY Heat Mode Procedure 1-SELF-TEST ModeProcedure 2-HEATING Mode Procedure 3-HEATING MODE-TWO StageTwo-Speed Applications Procedure 5-COOLING ModeProcedure 6-HEAT Pump Mode Single-Speed ApplicationsProcedure 8-COMPONENT Test Procedure 7-CONTINUOUS FAN ModeProcedure 10-DEHUMIDIFICATION Mode Procedure 9-BYPASS Humidifier ModeSTART-UP Procedures Procedure 1-GENERAL Procedure 11-ZONE ModeProcedure 2-SELECT Setup Switch Positions Switch Position Tons Air Conditioning A/C Airflow Switch PositionSetup Switches SW AIR Setup Allowable Furnace Model SetupProcedure 4-PURGE GAS Lines Procedure 3-PRIME Condensate Trap with WaterProcedure 5-ADJUSTMENTS Filling Condensate Trap Heat Value Altitude AVG GAS Specific Gravity of Natural GASAltitude United States Canada Redundant Automatic Gas Valve Set Temperature RiseAltitude Percent Derate Multiplier Altitude Derate Multiplier for U.S.ASet Thermostat Heat Anticipator ExampleCheck Primary Limit Control Procedure 6-CHECK Safety ControlsCheck Pressure Switches Gas Rate Cu Ft/HrAmp Draw Check with Ammeter Procedure 7-CHECKLISTCombustion and Vent Piping CHECKLIST-START-UP CHECKLIST-INSTALLATIONBook/Tab 1/6 Catalog No
Related manuals
Manual 12 pages 42.74 Kb

355MAV specifications

The Bryant 355MAV is a remarkable model that stands out in the HVAC (heating, ventilation, and air conditioning) industry for its efficiency, reliability, and advanced technology. This unit is specifically designed to provide homeowners with excellent comfort while maintaining energy efficiency, making it an ideal choice for residential applications.

One of the standout features of the Bryant 355MAV is its variable speed compressor. This technology allows the system to adjust its cooling output based on the current temperature needs of the home. By operating at multiple speed levels, the compressor can maintain a more consistent indoor climate while using significantly less energy than traditional single-speed systems. This capability translates to lower energy bills and enhanced comfort.

Additionally, the Bryant 355MAV integrates an advanced control system that offers precise temperature regulation. Homeowners can easily set their desired indoor conditions, and the thermostat will communicate with the system to ensure optimal performance. This smart technology not only enhances comfort but also extends the lifespan of the unit by preventing unnecessary strain during operation.

The 355MAV also features significant advancements in sound reduction technology. Designed with noise-absorbing materials and a quiet operation mode, this unit ensures that indoor comfort is maintained without the disruption of loud operational sounds. This makes it a perfect choice for residential settings, particularly in areas where noise sensitivity is a concern.

Energy efficiency is another key characteristic of the Bryant 355MAV. The unit is certified with a high Seasonal Energy Efficiency Ratio (SEER) rating, which means it meets strict energy consumption standards. This not only reflects its eco-friendliness but also contributes to significant savings on utility bills over time.

Moreover, the Bryant 355MAV uses environmentally friendly refrigerants that comply with EPA regulations, further solidifying its commitment to sustainability. This, combined with durable construction and a reliable warranty, ensures that homeowners can expect lasting performance from the system.

In conclusion, the Bryant 355MAV offers an impressive array of features, including a variable speed compressor, advanced control systems, sound reduction technology, and high energy efficiency. These characteristics make it an exceptional option for those seeking a reliable and efficient HVAC solution in their homes. With its commitment to comfort, savings, and sustainability, the Bryant 355MAV continues to be a popular choice among homeowners looking to enhance their indoor environments.