Bryant 355MAV Procedure 9-DIRECT Venting, Removal of Existing Furnaces from Common Vent Systems

Page 27

ALTERNATE FIELD LOCATION

FACTORY

INSTALLED

LOCATION

A00212

Fig. 29—Relocating J-Box

NOTE: If desired, cut butt connectors off factory leads and strip insulation approximately 1/4 in and use field-supplied wire nuts to connect.

b.An alternate method to attach EAC lead to control center is the following procedure: (1.) Remove 2 screws securing the control box to furnace blower shelf.

(2.) Remove and discard 2 factory-supplied leads from control center EAC terminals.

(3.) Strip EAC power leads insulation approximately 1/8 in.

NOTE: The control center EAC terminals are sized for 12 gage maximum, solid or stranded wire. (4.) Route EAC leads through right-hand wire grommet.

(5.) Insert EAC stripped leads into control center EAC terminals by depressing terminal’s arm with a screwdriver or finger. (See Fig. 32.)

(6.) Reinstall control box to furnace blower shelf using 2 screws removed earlier.

2.Humidifier (HUM)

Screw terminals (HUM and COM) are provided for 24-v humidifier connection. (See Fig. 30.) The HUM terminal is energized with 24-v (0.5-amp maximum) after inducer motor prepurge period.

NOTE: A field-supplied, 115–v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation.

3.Dehumidification (DEHUM)

A dehumidification input is provided via a 1/4-in. male quick-connect labeled DEHUM located next to the transformer secondary connections. When there is a dehumidify demand, the DEHUM input is activated, which means 24 vac signal is removed from the DEHUM input terminal. In other words, the DEHUM input logic is reversed. the DEHUM input is turned ON when no dehumidify demand exists and is turned OFF when demand exists. This logic reversal has come about from historical use of a standard humidistat to do dehumidification since the contacts open on high humidity, thus removing the 24-v signal to initiate dehumidification.

The DEHUM output on the thermidistat control or the humidistat output is connected directly to the DEHUM terminal on the furnace control. In addition, the DE jumper located next to the DEHUM terminal must be removed to enable the DEHUM input. (See Fig. 33 and 34.) When a dehumidify demand exists, the furnace control reduces the blower airflow by 21 percent to 315 CFM per ton during continuous fan or cooling operation.

PROCEDURE 9—DIRECT VENTING

The 355MAV furnaces require a dedicated (one 355MAV furnace only) direct-vent system. In a direct-vent system, all air for combustion is taken directly from outside atmosphere, and all flue products are discharged to outside atmosphere.

A. Removal of Existing Furnaces from Common Vent Systems

If furnace being replaced was connected to a common vent system with other appliances, the following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:

1.Seal any unused openings in the venting system.

2.Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code, ANSI Z223.1 or 24 the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion, and other deficiencies which could cause an unsafe condition.

3.If practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

—27—

Image 27
Contents Table of Contents Installation, Start-up, and Operating InstructionsLocation Safety Considerations IntroductionCodes and Standards Unit Size DimensionsClearances to Combustibles Installer Packet IncludesApplications Procedure 1-GENERAL Electrostatic Discharge ESD Precaution ProcedureProcedure 2-UPFLOW Applications Condensate Trap Location Factory-Shipped OrientationCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Tubing Alternate Upflow Orientation Condensate Trap Location Alternate Upflow OrientationCondensate Trap Freeze Protection Pressure Switch TubingProcedure 3-DOWNFLOW Applications Condensate Trap Field Drain AttachmentCondensate Trap Tubing Downflow Tube Configuration Right-Hand Trap InstallationCondensate Trap Field Drain Attachment Construct a Working Platform Condensate Trap Field Drain AttachmentsAttic Location and Working Platform Horizontal Right Tube Configuration Furnace Location for Proper Condensate Drainage Location Procedure 1-GENERALProcedure 2-LOW-FIRE only Installation Prohibit Installation on BackProcedure 3-FURNACE Location Relative to Coolingequipment Procedure 4-HAZARDOUS LocationsInstallation Procedure 1-LEVELING Legs if Desired Furnace Plenum Opening Floor Opening Opening DimensionsProcedure 3-INSTALLATION in Horizontal Applications Floor and Plenum Opening DimensionsGeneral Requirements Procedure 4-AIR DuctsDuctwork Acoustical Treatment Supply Air ConnectionsReturn Air Connections Filter Information Procedure 5-FILTER ArrangementProcedure 6-BOTTOM Closure Panel Procedure 7-GAS PipingBottom Filter Arrangement Maximum Capacity of Pipe Nominal Length of Pipe FTInternal Pipe Diameter Size Wiring Procedure 8-ELECTRICAL ConnectionsElectrical Data AccessoriesRemoval of Existing Furnaces from Common Vent Systems Procedure 9-DIRECT VentingUnit Wiring Diagram Combustion-Air and Vent Piping Control Center355MAV Variable Speed Furnace Control Opening Location Clearance FTCombustion-Air and Vent Pipe Connections Short Vent 5 to 8 ft System Altitude FT Maximum Allowable Pipe Length ft4001 to 5000‡ Intake Housing Plug Fitting Drain Roof Termination Preferred Concentric Vent and Combustion-Air RoofTermination Preferred Sidewall Termination of Less than 12 Procedure 10-CONDENSATE Drain Multiventing and Vent TerminationsGeneral Condensation Drain Protection ″ 25 mm Maximum TYP Sequence of Operation Example of Field Drain AttachmentProcedure 4-EMERGENCY Heat Mode Procedure 1-SELF-TEST ModeProcedure 2-HEATING Mode Procedure 3-HEATING MODE-TWO StageTwo-Speed Applications Procedure 5-COOLING ModeProcedure 6-HEAT Pump Mode Single-Speed ApplicationsProcedure 8-COMPONENT Test Procedure 7-CONTINUOUS FAN ModeProcedure 10-DEHUMIDIFICATION Mode Procedure 9-BYPASS Humidifier ModeProcedure 11-ZONE Mode START-UP Procedures Procedure 1-GENERALProcedure 2-SELECT Setup Switch Positions Switch Position Tons Air Conditioning A/C Airflow Switch PositionSetup Switches SW AIR Setup Allowable Furnace Model SetupProcedure 3-PRIME Condensate Trap with Water Procedure 4-PURGE GAS LinesProcedure 5-ADJUSTMENTS Filling Condensate Trap Altitude AVG GAS Specific Gravity of Natural GAS Heat ValueAltitude United States Canada Redundant Automatic Gas Valve Set Temperature RiseAltitude Percent Derate Multiplier Altitude Derate Multiplier for U.S.ASet Thermostat Heat Anticipator ExampleCheck Primary Limit Control Procedure 6-CHECK Safety ControlsCheck Pressure Switches Gas Rate Cu Ft/HrAmp Draw Check with Ammeter Procedure 7-CHECKLISTCombustion and Vent Piping CHECKLIST-START-UP CHECKLIST-INSTALLATIONBook/Tab 1/6 Catalog No
Related manuals
Manual 12 pages 42.74 Kb

355MAV specifications

The Bryant 355MAV is a remarkable model that stands out in the HVAC (heating, ventilation, and air conditioning) industry for its efficiency, reliability, and advanced technology. This unit is specifically designed to provide homeowners with excellent comfort while maintaining energy efficiency, making it an ideal choice for residential applications.

One of the standout features of the Bryant 355MAV is its variable speed compressor. This technology allows the system to adjust its cooling output based on the current temperature needs of the home. By operating at multiple speed levels, the compressor can maintain a more consistent indoor climate while using significantly less energy than traditional single-speed systems. This capability translates to lower energy bills and enhanced comfort.

Additionally, the Bryant 355MAV integrates an advanced control system that offers precise temperature regulation. Homeowners can easily set their desired indoor conditions, and the thermostat will communicate with the system to ensure optimal performance. This smart technology not only enhances comfort but also extends the lifespan of the unit by preventing unnecessary strain during operation.

The 355MAV also features significant advancements in sound reduction technology. Designed with noise-absorbing materials and a quiet operation mode, this unit ensures that indoor comfort is maintained without the disruption of loud operational sounds. This makes it a perfect choice for residential settings, particularly in areas where noise sensitivity is a concern.

Energy efficiency is another key characteristic of the Bryant 355MAV. The unit is certified with a high Seasonal Energy Efficiency Ratio (SEER) rating, which means it meets strict energy consumption standards. This not only reflects its eco-friendliness but also contributes to significant savings on utility bills over time.

Moreover, the Bryant 355MAV uses environmentally friendly refrigerants that comply with EPA regulations, further solidifying its commitment to sustainability. This, combined with durable construction and a reliable warranty, ensures that homeowners can expect lasting performance from the system.

In conclusion, the Bryant 355MAV offers an impressive array of features, including a variable speed compressor, advanced control systems, sound reduction technology, and high energy efficiency. These characteristics make it an exceptional option for those seeking a reliable and efficient HVAC solution in their homes. With its commitment to comfort, savings, and sustainability, the Bryant 355MAV continues to be a popular choice among homeowners looking to enhance their indoor environments.