Bryant instruction manual 355MAV Variable Speed Furnace Control

Page 30

 

 

 

HUM

 

 

 

G

 

 

 

R

 

 

 

Y/Y2

 

 

 

W/W1

 

 

 

Com 24V

 

 

 

W2

 

 

DE

 

SEC-2

SEC-1

DEHUM

DE CONNECTION

 

DE CONNECTION

LOCATION

A99098

Fig. 33—355MAV Variable Speed Furnace Control

VARIABLE-SPEED￿

THERMIDISTATCONDENSING￿

FURNACE

24 VAC HOT

 

R

DEHUMIDIFY

 

DHUM

 

 

 

 

24 VAC COMM C

R

DEHUM

DE￿

NOTE 1

Com

NOTE 1 - Remove DE Connection￿ To Enable DEHUM Input

A98295

Fig. 34—Thermidistat Connection

NOTE: Furnace combustion-air and vent pipe connections are sized for 2-in. pipe. Any pipe size change should be made outside furnace casing in vertical pipe. (See Fig. 35.) This allows proper drainage of vent condensate.

Combustion-air and vent pipes must terminate together in same atmosphere pressure zone, either through roof or sidewall (roof termination preferred), using accessory termination kit. See Table 5 for required clearances.

Furnace combustion-air and vent pipe connections must be attached as shown in Fig. 37. Combustion-air intake plug fitting and inducer housing alternate vent cap may need to be relocated in some applications.

NOTE: Slope combustion-air and vent pipes a minimum of 1/4 in. per linear ft with no sags between hangers.

CAUTION: When combustion-air pipe is installed above a suspended ceiling, pipe must be insulated with 3/8-in. thick Armaflex-type insulation. Combustion-air pipe should also be insulated when it passes through warm, humid space.

An abandoned masonry chimney may be used as a raceway for properly insulated and supported combustion-air and vent pipes. Each furnace must have its own set of combustion-air and vent pipes and be terminated individually, as shown in Fig. 39, 40, 44 and 45.

—30—

Image 30
Contents Installation, Start-up, and Operating Instructions Table of ContentsLocation Safety Considerations IntroductionCodes and Standards Dimensions Unit SizeInstaller Packet Includes Clearances to CombustiblesElectrostatic Discharge ESD Precaution Procedure Applications Procedure 1-GENERALProcedure 2-UPFLOW Applications Condensate Trap Location Factory-Shipped OrientationCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Location Alternate Upflow Orientation Condensate Trap Tubing Alternate Upflow OrientationCondensate Trap Field Drain Attachment Pressure Switch TubingProcedure 3-DOWNFLOW Applications Condensate Trap Freeze ProtectionDownflow Tube Configuration Right-Hand Trap Installation Condensate Trap TubingCondensate Trap Field Drain Attachment Condensate Trap Field Drain Attachments Construct a Working PlatformAttic Location and Working Platform Horizontal Right Tube Configuration Location Procedure 1-GENERAL Furnace Location for Proper Condensate DrainageProhibit Installation on Back Procedure 2-LOW-FIRE only InstallationProcedure 3-FURNACE Location Relative to Coolingequipment Procedure 4-HAZARDOUS LocationsInstallation Procedure 1-LEVELING Legs if Desired Opening Dimensions Furnace Plenum Opening Floor OpeningFloor and Plenum Opening Dimensions Procedure 3-INSTALLATION in Horizontal ApplicationsProcedure 4-AIR Ducts General RequirementsDuctwork Acoustical Treatment Supply Air ConnectionsReturn Air Connections Procedure 7-GAS Piping Procedure 5-FILTER ArrangementProcedure 6-BOTTOM Closure Panel Filter InformationBottom Filter Arrangement Maximum Capacity of Pipe Nominal Length of Pipe FTInternal Pipe Diameter Size Procedure 8-ELECTRICAL Connections WiringAccessories Electrical DataProcedure 9-DIRECT Venting Removal of Existing Furnaces from Common Vent SystemsUnit Wiring Diagram Control Center Combustion-Air and Vent Piping355MAV Variable Speed Furnace Control Location Clearance FT OpeningCombustion-Air and Vent Pipe Connections Short Vent 5 to 8 ft System Maximum Allowable Pipe Length ft Altitude FT4001 to 5000‡ Intake Housing Plug Fitting Drain Roof Termination Preferred Concentric Vent and Combustion-Air RoofTermination Preferred Sidewall Termination of Less than 12 Procedure 10-CONDENSATE Drain Multiventing and Vent TerminationsGeneral Condensation Drain Protection ″ 25 mm Maximum TYP Example of Field Drain Attachment Sequence of OperationProcedure 3-HEATING MODE-TWO Stage Procedure 1-SELF-TEST ModeProcedure 2-HEATING Mode Procedure 4-EMERGENCY Heat ModeSingle-Speed Applications Procedure 5-COOLING ModeProcedure 6-HEAT Pump Mode Two-Speed ApplicationsProcedure 7-CONTINUOUS FAN Mode Procedure 8-COMPONENT TestProcedure 9-BYPASS Humidifier Mode Procedure 10-DEHUMIDIFICATION ModeProcedure 11-ZONE Mode START-UP Procedures Procedure 1-GENERALProcedure 2-SELECT Setup Switch Positions AIR Setup Allowable Furnace Model Setup Air Conditioning A/C Airflow Switch PositionSetup Switches SW Switch Position TonsProcedure 3-PRIME Condensate Trap with Water Procedure 4-PURGE GAS LinesProcedure 5-ADJUSTMENTS Filling Condensate Trap Altitude AVG GAS Specific Gravity of Natural GAS Heat ValueAltitude United States Canada Set Temperature Rise Redundant Automatic Gas ValveExample Altitude Derate Multiplier for U.S.ASet Thermostat Heat Anticipator Altitude Percent Derate MultiplierGas Rate Cu Ft/Hr Procedure 6-CHECK Safety ControlsCheck Pressure Switches Check Primary Limit ControlProcedure 7-CHECKLIST Amp Draw Check with AmmeterCHECKLIST-INSTALLATION Combustion and Vent Piping CHECKLIST-START-UPBook/Tab 1/6 Catalog No
Related manuals
Manual 12 pages 42.74 Kb

355MAV specifications

The Bryant 355MAV is a remarkable model that stands out in the HVAC (heating, ventilation, and air conditioning) industry for its efficiency, reliability, and advanced technology. This unit is specifically designed to provide homeowners with excellent comfort while maintaining energy efficiency, making it an ideal choice for residential applications.

One of the standout features of the Bryant 355MAV is its variable speed compressor. This technology allows the system to adjust its cooling output based on the current temperature needs of the home. By operating at multiple speed levels, the compressor can maintain a more consistent indoor climate while using significantly less energy than traditional single-speed systems. This capability translates to lower energy bills and enhanced comfort.

Additionally, the Bryant 355MAV integrates an advanced control system that offers precise temperature regulation. Homeowners can easily set their desired indoor conditions, and the thermostat will communicate with the system to ensure optimal performance. This smart technology not only enhances comfort but also extends the lifespan of the unit by preventing unnecessary strain during operation.

The 355MAV also features significant advancements in sound reduction technology. Designed with noise-absorbing materials and a quiet operation mode, this unit ensures that indoor comfort is maintained without the disruption of loud operational sounds. This makes it a perfect choice for residential settings, particularly in areas where noise sensitivity is a concern.

Energy efficiency is another key characteristic of the Bryant 355MAV. The unit is certified with a high Seasonal Energy Efficiency Ratio (SEER) rating, which means it meets strict energy consumption standards. This not only reflects its eco-friendliness but also contributes to significant savings on utility bills over time.

Moreover, the Bryant 355MAV uses environmentally friendly refrigerants that comply with EPA regulations, further solidifying its commitment to sustainability. This, combined with durable construction and a reliable warranty, ensures that homeowners can expect lasting performance from the system.

In conclusion, the Bryant 355MAV offers an impressive array of features, including a variable speed compressor, advanced control systems, sound reduction technology, and high energy efficiency. These characteristics make it an exceptional option for those seeking a reliable and efficient HVAC solution in their homes. With its commitment to comfort, savings, and sustainability, the Bryant 355MAV continues to be a popular choice among homeowners looking to enhance their indoor environments.