CAUTION: Combustion air must not be taken from inside structure because inside air is frequently contaminated by halogens, which include fluorides, chlorides, bromides, and iodides. These elements are found in aerosols, detergents, bleaches, cleaning solvents, salts, air fresheners, adhesives, paint, and other household products. Locate combustion-air inlet as far as possible from swimming pool and swimming pool pump house. Excessive exposure to contaminated combustion air will result in safety and performance related problems

WARNING: Solvent cements are combustible. Keep away from heat, sparks, and open flame. Use only in well ventilated areas. Avoid breathing in vapor or allowing contact with skin or eyes. Failure to follow this warning could result in fire, property damage, personal injury, or death.

WARNING: All combustion-air and vent pipes must be airtight and watertight. Pipes must also terminate exactly as shown in Fig. 39, 40, 41, 42, or 43. Failure to follow this warning could result in property damage, personal injury, or death.

NOTE: The minimum combustion-air and vent pipe length (each) for these furnaces is 5 ft. Short pipe lengths (5-8 ft) may discharge water droplets. These droplets may be undesirable, and a 12-in. minimum offset pipe section is recommended, as shown in Fig. 37, to reduce excessive droplets from exiting vent pipe outlet.

VENT PIPE

 

12MIN

12MIN

(305mm)

 

(305mm)

 

 

VENT PIPE

COMBUSTION-AIR PIPE

COMBUSTION-AIR PIPE

HORIZONTAL TO ROOF

HORIZONTAL TO SIDEWALL

 

COMBUSTION-AIR PIPE

 

VENT PIPE

COMBUSTION-AIR PIPE

 

 

12MIN

 

(304.8mm)

12MIN

VENT PIPE

(304.8mm)

 

VERTICAL TO ROOF

VERTICAL TO SIDEWALL

NOTE: A 12-in. (304.8mm) minimum offset pipe section is recommended with short (5 to 8 ft / 1.5 to 2.5M) vent systems. This recommendation is to reduce excessive condensate droplets.

A96230

Fig. 37—Short Vent (5 to 8 ft) System

COMBUSTION-AIR AND VENT PIPE DIAMETER

Determine combustion-air and vent pipe diameter.

1.Using Table 7, individually determine the smallest combustion-air and vent pipe diameters allowed for each pipe. Pick the larger of these 2 pipe diameters and use this diameter for both combustion-air and vent pipes.

2.When installing vent systems of short pipe length, use the smallest allowable pipe diameter. Do not use pipe size greater than required or incomplete combustion, flame disturbance, or flame sense lockout may occur.

—33—

Image 33
Contents Table of Contents Installation, Start-up, and Operating InstructionsLocation Safety Considerations IntroductionCodes and Standards Unit Size DimensionsClearances to Combustibles Installer Packet IncludesApplications Procedure 1-GENERAL Electrostatic Discharge ESD Precaution ProcedureProcedure 2-UPFLOW Applications Condensate Trap Location Factory-Shipped OrientationCondensate Trap Tubing Factory-Shipped Orientation Condensate Trap Tubing Alternate Upflow Orientation Condensate Trap Location Alternate Upflow OrientationProcedure 3-DOWNFLOW Applications Pressure Switch TubingCondensate Trap Field Drain Attachment Condensate Trap Freeze ProtectionCondensate Trap Tubing Downflow Tube Configuration Right-Hand Trap InstallationCondensate Trap Field Drain Attachment Construct a Working Platform Condensate Trap Field Drain AttachmentsAttic Location and Working Platform Horizontal Right Tube Configuration Furnace Location for Proper Condensate Drainage Location Procedure 1-GENERALProcedure 2-LOW-FIRE only Installation Prohibit Installation on BackProcedure 3-FURNACE Location Relative to Coolingequipment Procedure 4-HAZARDOUS LocationsInstallation Procedure 1-LEVELING Legs if Desired Furnace Plenum Opening Floor Opening Opening DimensionsProcedure 3-INSTALLATION in Horizontal Applications Floor and Plenum Opening DimensionsGeneral Requirements Procedure 4-AIR DuctsDuctwork Acoustical Treatment Supply Air ConnectionsReturn Air Connections Procedure 6-BOTTOM Closure Panel Procedure 5-FILTER ArrangementProcedure 7-GAS Piping Filter InformationBottom Filter Arrangement Maximum Capacity of Pipe Nominal Length of Pipe FTInternal Pipe Diameter Size Wiring Procedure 8-ELECTRICAL ConnectionsElectrical Data AccessoriesRemoval of Existing Furnaces from Common Vent Systems Procedure 9-DIRECT VentingUnit Wiring Diagram Combustion-Air and Vent Piping Control Center355MAV Variable Speed Furnace Control Opening Location Clearance FTCombustion-Air and Vent Pipe Connections Short Vent 5 to 8 ft System Altitude FT Maximum Allowable Pipe Length ft4001 to 5000‡ Intake Housing Plug Fitting Drain Roof Termination Preferred Concentric Vent and Combustion-Air RoofTermination Preferred Sidewall Termination of Less than 12 Procedure 10-CONDENSATE Drain Multiventing and Vent TerminationsGeneral Condensation Drain Protection ″ 25 mm Maximum TYP Sequence of Operation Example of Field Drain AttachmentProcedure 2-HEATING Mode Procedure 1-SELF-TEST ModeProcedure 3-HEATING MODE-TWO Stage Procedure 4-EMERGENCY Heat ModeProcedure 6-HEAT Pump Mode Procedure 5-COOLING ModeSingle-Speed Applications Two-Speed ApplicationsProcedure 8-COMPONENT Test Procedure 7-CONTINUOUS FAN ModeProcedure 10-DEHUMIDIFICATION Mode Procedure 9-BYPASS Humidifier ModeProcedure 11-ZONE Mode START-UP Procedures Procedure 1-GENERALProcedure 2-SELECT Setup Switch Positions Setup Switches SW Air Conditioning A/C Airflow Switch PositionAIR Setup Allowable Furnace Model Setup Switch Position TonsProcedure 3-PRIME Condensate Trap with Water Procedure 4-PURGE GAS LinesProcedure 5-ADJUSTMENTS Filling Condensate Trap Altitude AVG GAS Specific Gravity of Natural GAS Heat ValueAltitude United States Canada Redundant Automatic Gas Valve Set Temperature RiseSet Thermostat Heat Anticipator Altitude Derate Multiplier for U.S.AExample Altitude Percent Derate MultiplierCheck Pressure Switches Procedure 6-CHECK Safety ControlsGas Rate Cu Ft/Hr Check Primary Limit ControlAmp Draw Check with Ammeter Procedure 7-CHECKLISTCombustion and Vent Piping CHECKLIST-START-UP CHECKLIST-INSTALLATIONBook/Tab 1/6 Catalog No
Related manuals
Manual 12 pages 42.74 Kb

355MAV specifications

The Bryant 355MAV is a remarkable model that stands out in the HVAC (heating, ventilation, and air conditioning) industry for its efficiency, reliability, and advanced technology. This unit is specifically designed to provide homeowners with excellent comfort while maintaining energy efficiency, making it an ideal choice for residential applications.

One of the standout features of the Bryant 355MAV is its variable speed compressor. This technology allows the system to adjust its cooling output based on the current temperature needs of the home. By operating at multiple speed levels, the compressor can maintain a more consistent indoor climate while using significantly less energy than traditional single-speed systems. This capability translates to lower energy bills and enhanced comfort.

Additionally, the Bryant 355MAV integrates an advanced control system that offers precise temperature regulation. Homeowners can easily set their desired indoor conditions, and the thermostat will communicate with the system to ensure optimal performance. This smart technology not only enhances comfort but also extends the lifespan of the unit by preventing unnecessary strain during operation.

The 355MAV also features significant advancements in sound reduction technology. Designed with noise-absorbing materials and a quiet operation mode, this unit ensures that indoor comfort is maintained without the disruption of loud operational sounds. This makes it a perfect choice for residential settings, particularly in areas where noise sensitivity is a concern.

Energy efficiency is another key characteristic of the Bryant 355MAV. The unit is certified with a high Seasonal Energy Efficiency Ratio (SEER) rating, which means it meets strict energy consumption standards. This not only reflects its eco-friendliness but also contributes to significant savings on utility bills over time.

Moreover, the Bryant 355MAV uses environmentally friendly refrigerants that comply with EPA regulations, further solidifying its commitment to sustainability. This, combined with durable construction and a reliable warranty, ensures that homeowners can expect lasting performance from the system.

In conclusion, the Bryant 355MAV offers an impressive array of features, including a variable speed compressor, advanced control systems, sound reduction technology, and high energy efficiency. These characteristics make it an exceptional option for those seeking a reliable and efficient HVAC solution in their homes. With its commitment to comfort, savings, and sustainability, the Bryant 355MAV continues to be a popular choice among homeowners looking to enhance their indoor environments.