Bryant 355MAV instruction manual Electrical Data, Accessories

Page 26

Table 4—Electrical Data

UNIT

VOLTS—

OPERATING

MAX

UNIT

MIN

MAX WIRE

MAX FUSE

HERTZ—

VOLTAGE RANGE

UNIT

WIRE

LENGTH

OR CKT BKR

SIZE

AMPACITY†

PHASE

Max*

Min*

AMPS

SIZE

(FT)‡

AMPS**

 

 

042040

115-60-1

127

104

8.9

12.0

14

31

15

042060

115-60-1

127

104

8.9

12.0

14

31

15

042080

115-60-1

127

104

8.9

12.0

14

31

15

060080

115-60-1

127

104

13.8

17.9

12

32

20

060100

115-60-1

127

104

13.8

18.1

12

32

20

060120

115-60-1

127

104

11.6

15.3

12

37

20

 

 

 

 

 

 

 

 

 

* Permissible limits of voltage range at which unit will operate satisfactorily.

Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load amps.

‡ Length shown is a measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time-delay type is recommended.

ELECTRIC

DISCONNECT

SWITCH

COPPER

WIRE ONLY

ALUMINUM

WIRE

A93033

Fig. 28—Disconnect Switch and Furnace

CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. (See Fig. 28.)

WARNING: The furnace casing MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2002 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in electrical shock, fire, or death.

J-BOX RELOCATION

1.Remove 2 screws holding auxiliary J-box. (See Fig. 29.)

2.Rotate J-box 180° and attach box to left side, using holes provided.

CAUTION: If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.

B. 24-V Wiring

Make field 24-v thermostat connections at 24-v terminal block on control center. Y wire from thermostat MUST be connected to Y terminal on control center, as shown in Fig. 27, for proper cooling operation. The 24-v terminal board is marked for easy connection of field wiring. (See Fig. 30.) The 24-v circuit contains a 3-amp, automotive-type fuse located on control center. (See Fig. 31.) Any electrical shorts of 24-v wiring during installation, service, or maintenance may cause fuse to blow. If fuse replacement is required, use only a fuse of identical size (3 amp).

NOTE: Use AWG No. 18 color-coded copper thermostat wire for lengths up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire.

NOTE: For 2-speed applications, refer to Sequence of Operation section.

C.Accessories

1.Electronic Air Cleaner (EAC)

The control center EAC terminals are energized with 115v (1.5-amp maximum) during blower operation.

a.Two extension leads are connected to the control center EAC terminals to assist field installation of an EAC. (See Fig. 31.) To use these leads, proceed with the following:

(1.) Strip EAC power lead insulation approximately 1/4 in.

(2.) Insert stripped end into factory-supplied black lead’s butt connector and crimp to secure.

(3.) Strip EAC neutral lead insulation approximately 1/4 in.

(4.) Insert stripped end into factory-supplied white leads’s butt connector and crimp to secure.

—26—

Image 26
Contents Installation, Start-up, and Operating Instructions Table of ContentsLocation Codes and Standards Safety ConsiderationsIntroduction Dimensions Unit SizeInstaller Packet Includes Clearances to CombustiblesElectrostatic Discharge ESD Precaution Procedure Applications Procedure 1-GENERALCondensate Trap Tubing Factory-Shipped Orientation Procedure 2-UPFLOW ApplicationsCondensate Trap Location Factory-Shipped Orientation Condensate Trap Location Alternate Upflow Orientation Condensate Trap Tubing Alternate Upflow OrientationCondensate Trap Field Drain Attachment Pressure Switch TubingProcedure 3-DOWNFLOW Applications Condensate Trap Freeze ProtectionDownflow Tube Configuration Right-Hand Trap Installation Condensate Trap TubingCondensate Trap Field Drain Attachment Condensate Trap Field Drain Attachments Construct a Working PlatformAttic Location and Working Platform Horizontal Right Tube Configuration Location Procedure 1-GENERAL Furnace Location for Proper Condensate DrainageProhibit Installation on Back Procedure 2-LOW-FIRE only InstallationInstallation Procedure 1-LEVELING Legs if Desired Procedure 3-FURNACE Location Relative to CoolingequipmentProcedure 4-HAZARDOUS Locations Opening Dimensions Furnace Plenum Opening Floor OpeningFloor and Plenum Opening Dimensions Procedure 3-INSTALLATION in Horizontal ApplicationsProcedure 4-AIR Ducts General RequirementsReturn Air Connections Ductwork Acoustical TreatmentSupply Air Connections Procedure 7-GAS Piping Procedure 5-FILTER ArrangementProcedure 6-BOTTOM Closure Panel Filter InformationBottom Filter Arrangement Internal Pipe Diameter Size Maximum Capacity of PipeNominal Length of Pipe FT Procedure 8-ELECTRICAL Connections WiringAccessories Electrical DataProcedure 9-DIRECT Venting Removal of Existing Furnaces from Common Vent SystemsUnit Wiring Diagram Control Center Combustion-Air and Vent Piping355MAV Variable Speed Furnace Control Location Clearance FT OpeningCombustion-Air and Vent Pipe Connections Short Vent 5 to 8 ft System Maximum Allowable Pipe Length ft Altitude FT4001 to 5000‡ Intake Housing Plug Fitting Drain Roof Termination Preferred Concentric Vent and Combustion-Air RoofTermination Preferred Sidewall Termination of Less than 12 General Procedure 10-CONDENSATE DrainMultiventing and Vent Terminations Condensation Drain Protection ″ 25 mm Maximum TYP Example of Field Drain Attachment Sequence of OperationProcedure 3-HEATING MODE-TWO Stage Procedure 1-SELF-TEST ModeProcedure 2-HEATING Mode Procedure 4-EMERGENCY Heat ModeSingle-Speed Applications Procedure 5-COOLING ModeProcedure 6-HEAT Pump Mode Two-Speed ApplicationsProcedure 7-CONTINUOUS FAN Mode Procedure 8-COMPONENT TestProcedure 9-BYPASS Humidifier Mode Procedure 10-DEHUMIDIFICATION ModeProcedure 2-SELECT Setup Switch Positions Procedure 11-ZONE ModeSTART-UP Procedures Procedure 1-GENERAL AIR Setup Allowable Furnace Model Setup Air Conditioning A/C Airflow Switch PositionSetup Switches SW Switch Position TonsProcedure 5-ADJUSTMENTS Procedure 3-PRIME Condensate Trap with WaterProcedure 4-PURGE GAS Lines Filling Condensate Trap Altitude Altitude AVG GAS Specific Gravity of Natural GASHeat Value United States Canada Set Temperature Rise Redundant Automatic Gas ValveExample Altitude Derate Multiplier for U.S.ASet Thermostat Heat Anticipator Altitude Percent Derate MultiplierGas Rate Cu Ft/Hr Procedure 6-CHECK Safety ControlsCheck Pressure Switches Check Primary Limit ControlProcedure 7-CHECKLIST Amp Draw Check with AmmeterCHECKLIST-INSTALLATION Combustion and Vent Piping CHECKLIST-START-UPBook/Tab 1/6 Catalog No
Related manuals
Manual 12 pages 42.74 Kb

355MAV specifications

The Bryant 355MAV is a remarkable model that stands out in the HVAC (heating, ventilation, and air conditioning) industry for its efficiency, reliability, and advanced technology. This unit is specifically designed to provide homeowners with excellent comfort while maintaining energy efficiency, making it an ideal choice for residential applications.

One of the standout features of the Bryant 355MAV is its variable speed compressor. This technology allows the system to adjust its cooling output based on the current temperature needs of the home. By operating at multiple speed levels, the compressor can maintain a more consistent indoor climate while using significantly less energy than traditional single-speed systems. This capability translates to lower energy bills and enhanced comfort.

Additionally, the Bryant 355MAV integrates an advanced control system that offers precise temperature regulation. Homeowners can easily set their desired indoor conditions, and the thermostat will communicate with the system to ensure optimal performance. This smart technology not only enhances comfort but also extends the lifespan of the unit by preventing unnecessary strain during operation.

The 355MAV also features significant advancements in sound reduction technology. Designed with noise-absorbing materials and a quiet operation mode, this unit ensures that indoor comfort is maintained without the disruption of loud operational sounds. This makes it a perfect choice for residential settings, particularly in areas where noise sensitivity is a concern.

Energy efficiency is another key characteristic of the Bryant 355MAV. The unit is certified with a high Seasonal Energy Efficiency Ratio (SEER) rating, which means it meets strict energy consumption standards. This not only reflects its eco-friendliness but also contributes to significant savings on utility bills over time.

Moreover, the Bryant 355MAV uses environmentally friendly refrigerants that comply with EPA regulations, further solidifying its commitment to sustainability. This, combined with durable construction and a reliable warranty, ensures that homeowners can expect lasting performance from the system.

In conclusion, the Bryant 355MAV offers an impressive array of features, including a variable speed compressor, advanced control systems, sound reduction technology, and high energy efficiency. These characteristics make it an exceptional option for those seeking a reliable and efficient HVAC solution in their homes. With its commitment to comfort, savings, and sustainability, the Bryant 355MAV continues to be a popular choice among homeowners looking to enhance their indoor environments.