Bryant 355MAV Procedure 3-PRIME Condensate Trap with Water, Procedure 4-PURGE GAS Lines

Page 50

2.Locate setup switches on control center. (See Fig. 31.)

3.See Table 11 for setup switch description. (See Fig. 30.)

4.Replace main furnace door and blower access panel.

Table 11—Setup Switch Description

SETUP

NORMAL

DESCRIPTION

SWITCH NO.

POSITION

OF USE

SW-1

OFF

Turn switch to ON for fault history display. No thermostat signal

(FLT)

can be present for fault history display.

 

SW-2

 

Turn switch to ON to lock furnace in low-heat mode only or

OFF

when using a 2-stage thermostat with a R-W/W1 and R-W2 sig-

(LOW)

 

nals.

 

 

SW-3

 

Turn switch to ON when a bypass humidifier is used. This com-

OFF

pensates for higher return-air temperature and provides 15 per-

(BPH)

 

cent more airflow in low-heat mode only.

 

 

SW-4

 

Turn switch to ON to bypass microprocessor control. Furnace

OFF

will operate at high heat only with main blower and inducer mo-

(EMER HEAT)

 

tor operating at maximum RPM. NO safeties are bypassed.

 

 

SW-5

 

Turn switch to ON when modulating dampers are used. In this

OFF

mode, main blower speed is recalculated once every minute

(MZ)

 

while furnace is in low-heat or continuous fan mode.

 

 

 

 

Turn switch to ON to initiate component test. Furnace will oper-

SW-6

 

ate inducer motor for 20 sec at low speed, operate inducer motor

OFF

for 20 sec at high speed, energize HSI for 15 sec, operate blower

(COMP TEST)

for 20 sec at low speed, and operate blower for 20 sec at high

 

 

 

speed. SW-1 must be in OFF position. No thermostat signal can

 

 

be present for component test to be initiated.

SW-7 and SW-8

See Table 12

Adjust switches to provide desired heating mode blower off de-

(Blower Off Delay)

lay time. 90, 135, 180, or 225 sec.

 

Table 12—Blower Off Delay Setup Switch Position

DESIRED HEATING

SETUP SWITCH (SW-7 AND SW-8) POSITION

MODE BLOWER

 

 

SW-7

SW-8

OFF DELAY (SEC)

90

OFF

OFF

135

ON

OFF

180

OFF

ON

225

ON

ON

NOTE: If a bypass humidifier is used, setup switch SW-3 (BPH) should be in ON position. This prevents nuisance limit trips caused by the increased temperature in return air resulting from bypass.

NOTE: If modulating dampers are used, setup switch SW-5 (MZ) should be in ON position. This allows furnace control center to compensate for modulating dampers. The control re-calibrates for new system static conditions once every minute while operating in low-heat or continuous fan modes.

PROCEDURE 3—PRIME CONDENSATE TRAP WITH WATER

CAUTION: Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has 2 internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap.

1.Remove upper inducer housing drain connection cap. (See Fig. 54.)

2.Connect field-supplied 1/2-in. ID tube to upper inducer housing drain connection.

3.Insert field-supplied funnel into tube.

4.Pour 1 quart of water into funnel/tube. Water should run through inducer housing, overfill condensate trap, and flow into open field drain. (See Fig. 55.)

5.Remove funnel and tube from inducer housing and replace drain connection cap and clamp.

PROCEDURE 4—PURGE GAS LINES

If not previously done, purge the lines after all connections have been made and check for leaks.

WARNING: Never purge a gas line into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the purpose of checking leakage. Use a soap-and-water solution to check for leakage. Failure to follow this warning could result in fire, explosion, personal injury, or death.

PROCEDURE 5—ADJUSTMENTS

A. Set Gas Input Rate

Furnace gas input rate on rating plate is for installations at altitudes up to 2000 ft.

In the U.S.A., the input rating for altitudes above 2000 ft must be reduced by 2 percent for each 1000 ft above sea level. In Canada, the input rating must be derated by 5 percent for altitudes of 2000 ft to 4500 ft above sea level.

—50—

Image 50
Contents Installation, Start-up, and Operating Instructions Table of ContentsLocation Codes and Standards Safety ConsiderationsIntroduction Dimensions Unit SizeInstaller Packet Includes Clearances to CombustiblesElectrostatic Discharge ESD Precaution Procedure Applications Procedure 1-GENERALCondensate Trap Tubing Factory-Shipped Orientation Procedure 2-UPFLOW ApplicationsCondensate Trap Location Factory-Shipped Orientation Condensate Trap Location Alternate Upflow Orientation Condensate Trap Tubing Alternate Upflow OrientationCondensate Trap Field Drain Attachment Pressure Switch TubingProcedure 3-DOWNFLOW Applications Condensate Trap Freeze ProtectionDownflow Tube Configuration Right-Hand Trap Installation Condensate Trap TubingCondensate Trap Field Drain Attachment Condensate Trap Field Drain Attachments Construct a Working PlatformAttic Location and Working Platform Horizontal Right Tube Configuration Location Procedure 1-GENERAL Furnace Location for Proper Condensate DrainageProhibit Installation on Back Procedure 2-LOW-FIRE only InstallationInstallation Procedure 1-LEVELING Legs if Desired Procedure 3-FURNACE Location Relative to CoolingequipmentProcedure 4-HAZARDOUS Locations Opening Dimensions Furnace Plenum Opening Floor OpeningFloor and Plenum Opening Dimensions Procedure 3-INSTALLATION in Horizontal ApplicationsProcedure 4-AIR Ducts General RequirementsReturn Air Connections Ductwork Acoustical TreatmentSupply Air Connections Procedure 7-GAS Piping Procedure 5-FILTER ArrangementProcedure 6-BOTTOM Closure Panel Filter InformationBottom Filter Arrangement Internal Pipe Diameter Size Maximum Capacity of PipeNominal Length of Pipe FT Procedure 8-ELECTRICAL Connections WiringAccessories Electrical DataProcedure 9-DIRECT Venting Removal of Existing Furnaces from Common Vent SystemsUnit Wiring Diagram Control Center Combustion-Air and Vent Piping355MAV Variable Speed Furnace Control Location Clearance FT OpeningCombustion-Air and Vent Pipe Connections Short Vent 5 to 8 ft System Maximum Allowable Pipe Length ft Altitude FT4001 to 5000‡ Intake Housing Plug Fitting Drain Roof Termination Preferred Concentric Vent and Combustion-Air RoofTermination Preferred Sidewall Termination of Less than 12 General Procedure 10-CONDENSATE DrainMultiventing and Vent Terminations Condensation Drain Protection ″ 25 mm Maximum TYP Example of Field Drain Attachment Sequence of OperationProcedure 3-HEATING MODE-TWO Stage Procedure 1-SELF-TEST ModeProcedure 2-HEATING Mode Procedure 4-EMERGENCY Heat ModeSingle-Speed Applications Procedure 5-COOLING ModeProcedure 6-HEAT Pump Mode Two-Speed ApplicationsProcedure 7-CONTINUOUS FAN Mode Procedure 8-COMPONENT TestProcedure 9-BYPASS Humidifier Mode Procedure 10-DEHUMIDIFICATION ModeProcedure 2-SELECT Setup Switch Positions Procedure 11-ZONE ModeSTART-UP Procedures Procedure 1-GENERAL AIR Setup Allowable Furnace Model Setup Air Conditioning A/C Airflow Switch PositionSetup Switches SW Switch Position TonsProcedure 5-ADJUSTMENTS Procedure 3-PRIME Condensate Trap with WaterProcedure 4-PURGE GAS Lines Filling Condensate Trap Altitude Altitude AVG GAS Specific Gravity of Natural GASHeat Value United States Canada Set Temperature Rise Redundant Automatic Gas ValveExample Altitude Derate Multiplier for U.S.ASet Thermostat Heat Anticipator Altitude Percent Derate MultiplierGas Rate Cu Ft/Hr Procedure 6-CHECK Safety ControlsCheck Pressure Switches Check Primary Limit ControlProcedure 7-CHECKLIST Amp Draw Check with AmmeterCHECKLIST-INSTALLATION Combustion and Vent Piping CHECKLIST-START-UPBook/Tab 1/6 Catalog No
Related manuals
Manual 12 pages 42.74 Kb

355MAV specifications

The Bryant 355MAV is a remarkable model that stands out in the HVAC (heating, ventilation, and air conditioning) industry for its efficiency, reliability, and advanced technology. This unit is specifically designed to provide homeowners with excellent comfort while maintaining energy efficiency, making it an ideal choice for residential applications.

One of the standout features of the Bryant 355MAV is its variable speed compressor. This technology allows the system to adjust its cooling output based on the current temperature needs of the home. By operating at multiple speed levels, the compressor can maintain a more consistent indoor climate while using significantly less energy than traditional single-speed systems. This capability translates to lower energy bills and enhanced comfort.

Additionally, the Bryant 355MAV integrates an advanced control system that offers precise temperature regulation. Homeowners can easily set their desired indoor conditions, and the thermostat will communicate with the system to ensure optimal performance. This smart technology not only enhances comfort but also extends the lifespan of the unit by preventing unnecessary strain during operation.

The 355MAV also features significant advancements in sound reduction technology. Designed with noise-absorbing materials and a quiet operation mode, this unit ensures that indoor comfort is maintained without the disruption of loud operational sounds. This makes it a perfect choice for residential settings, particularly in areas where noise sensitivity is a concern.

Energy efficiency is another key characteristic of the Bryant 355MAV. The unit is certified with a high Seasonal Energy Efficiency Ratio (SEER) rating, which means it meets strict energy consumption standards. This not only reflects its eco-friendliness but also contributes to significant savings on utility bills over time.

Moreover, the Bryant 355MAV uses environmentally friendly refrigerants that comply with EPA regulations, further solidifying its commitment to sustainability. This, combined with durable construction and a reliable warranty, ensures that homeowners can expect lasting performance from the system.

In conclusion, the Bryant 355MAV offers an impressive array of features, including a variable speed compressor, advanced control systems, sound reduction technology, and high energy efficiency. These characteristics make it an exceptional option for those seeking a reliable and efficient HVAC solution in their homes. With its commitment to comfort, savings, and sustainability, the Bryant 355MAV continues to be a popular choice among homeowners looking to enhance their indoor environments.