Allied Air Enterprises 92G1UH, A95UH, 95G1UH Gas Piping, Leak Check, Fire or Explosion Hazard

Page 31

Gas Piping

CAUTION

If a flexible gas connector is required or allowed by the authority that has jurisdiction, black iron pipe shall be installed at the gas valve and extend outside the furnace cabinet. The flexible connector can then be added between the black iron pipe and the gas supply line.

WARNING

Do not exceed 600 in.-lbs. (50 ft.-lbs.) torque when attaching the gas piping to the gas valve.

1.Gas piping may be routed into the unit through either the left or right hand side. Supply piping enters into the gas valve from the side of the valve as shown in Figure 47. Move Bellows grommet to side which gas line enters. Ensure opposite gas line hole is plugged with supplied plug.

IMPORTANT

The gas valve requires a low inlet pressure switch in LP/propane applications. A 4” BIP nipple must be installed in the gas valve inlet when right-side gas entry is used in LP/propane applications. See Figure 47.

2.When connecting gas supply, factors such as length of run, number of fittings and furnace rating must be considered to avoid excessive pressure drop. Table 7 list recommended pipe sizes for typical applications.

NOTE: Use two wrenches when connecting gas piping to avoid transferring to the manifold.

3.Gas piping must not run in or through air ducts, clothes chutes, chimneys or gas vents, dumb waiters or elevator shafts. Center gas line through piping hole. Gas line should not touch side of unit. See Figures 47 and 48.

4.Piping should be sloped 1/4 “ per 15 feet (6 mm per 5.6 m) upward toward the gas meter from the furnace. The piping must be supported at proper intervals, every 8 to 10 feet (2.44 to 3.05 m), using suitable hangers or straps. Install a drip leg in vertical pipe runs to serve as a trap for sediment or condensate.

5.A 1/8” N.P.T. plugged tap or pressure post is located on the gas valve to facilitate test gauge connection. See Figure 55.

6.In some localities, codes may require installation of a manual main shut-off valve and union (furnished by installer) external to the unit. Union must be of the ground joint type.

IMPORTANT

Compounds used on threaded joints of gas piping must be resistant to the actions of liquified petroleum gases.

Leak Check

After gas piping is completed, carefully check all piping connections (factory and field installed) for gas leaks. Use a leak detecting solution or other preferred means.

Never use an open flame to test fro gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection.

The furnace must be isolated from the gas supply system by closing its individual manual shut-off valve during any pressure testing of the gas supply system at pressures more than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).

Figure 46

IMPORTANT

When testing pressure of gas lines, gas valve must be disconnected and isolated. See Figure 46. Gas valves can be damaged if subjected to pressures greater than 1/2 psig (3.48 kPa).

WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death, or property damage. Never use an open flame to test for gas leaks. Check all connections using a commercially available soap solution made specifically for leak detection. Some soaps used for leak detection are corrosive to certain metals. Carefully rinse piping thoroughly after leak test has been completed.

506501-01

Issue 1031

Page 31 of 48

Image 31
Contents A95UH, A93UH, 95G1UH & 92G1UH Table of ContentsFront View Side View A95UH, A93UH, 95G1UH & 92G1UH Unit Dimensions inches mmExpanded View Building Codes Safety InformationA95UH, A93UH, 95G1UH &92G1UH Gas Furnace Shipping and Packing ListInstalled in Combination with a Cooling Coil Installed LocationsUse of Furnace as a Construction Heater Combustion, Dilution & Ventilation Air Product Contains Fiberglass WoolEquipment in Confined Space All Air From Inside Unconfined SpaceConfined Space Air from InsideAir from Outside Upflow Applications InstallationSetting Equipment Shipping Bolt RemovalReturn Air Guidlines Installation ClearancesSide Return Air With transition and filter Removing the Bottom Panel Optional Return Air Base Upflow Applications OnlyHorizontal Applications Suspended Installation of Horizontal Unit Horizontal Application Installation ClearancesDuct System Pipe & Fittings SpecificationsReturn Air -- Horizontal Applications FiltersCanadian Applications Only Piping and Fittings SpecificationsOutdoor Termination Kits Usage Joint Cementing ProcedureExhaust Piping Figures 22 Horizontal Application Exhaust PipeMinimum Vent Pipe Lengths Maximum Allowable Vent Length Right Hand Discharge Shown Intake Piping Figures 24 through Typical AIR Intake Pipe Connections General Guidelines for Vent Terminations For Canadian Installations OnlyVent Termination Clearances For NON-DIRECT Vent INSTALLATiONS in the USA and CanadaFor Direct Vent INSTALLATiONS in the USA and Canada Field Supplied Wall Termination 15F75 or 44J41Direct Vent Concentric Rooftop Termination Direct Vent Application Using Existing Chimney Condensate Piping NON-DIRECT Vent Application Using Existing ChimneyNON-DIRECT Vent Roof Termination KIT NON-DIRECT Vent Field Supplied Wall TerminationUnit shown in upflow position Condensate Trap and Plug LocationsUnit shown in upflow position with remote trap Condensate Trap LocationsLeak Check Gas PipingFire or Explosion Hazard Horizontal Applications Possible Gas Piping Configurations Carbon Monoxide Poisoning Hazard Electrical Precautions and ProceduresInterior MAKE-UP BOX Installation Accessory TerminalsGenerator Use Voltage Requirements Typical Field Wiring DiagramFurnace & Condensing Unit Thermostat Designations Indoor Blower SpeedsTypical Wiring Diagram Automatic Hot Surface Ignition System Unit Start-Up Integrated ControlPlacing the furnace into operation GAS Valve Shown in on Position High Altitude Information Gas Pressure AdjustmentSupply Pressure Measurement Manifold Pressure MeasurementCarbon Monoxide Poisoning Hazard Heat FAN-OFF Time Seconds Electrical SHOCK, Fire Or Explosion Hazard Cleaning the Burner Assembly Failure Codes Planned ServiceBlower Parts Repair Parts ListCabinet Parts Heating Parts Control Panel PartsUnit SET UP Unit Operation Manufacturer Requirements BELOW. Keep Clear of ALL Obstructions

92G1UH, 95G1UH, A95UH, A93UH specifications

Allied Air Enterprises is renowned for producing high-quality HVAC systems, and its models A93UH, 92G1UH, A95UH, and 95G1UH are no exception. These units exemplify cutting-edge technology, efficiency, and reliability, making them popular choices for residential and commercial applications.

The A93UH model is a high-efficiency gas furnace designed with advanced features that maximize performance while maintaining low operating costs. It boasts a 93% Annual Fuel Utilization Efficiency (AFUE) rating, which ensures that a significant portion of the fuel consumed translates into heat. The A93UH incorporates variable-speed blower technology, allowing for precise airflow adjustments that enhance comfort and energy savings.

Similarly, the 92G1UH is built to provide exceptional heating capabilities. With a robust construction and innovative design, this model also achieves a 92% AFUE rating. It features a durable heat exchanger and a reliable ignition system that ensures consistent performance. The 92G1UH is engineered for quiet operation, minimizing noise levels and contributing to a more comfortable indoor environment.

Moving on to the A95UH, this unit represents the pinnacle of efficiency with its impressive 95% AFUE rating. This model not only emphasizes energy savings but also focuses on long-term durability. Equipped with a two-stage gas valve, the A95UH allows for flexible heating based on demand, which translates into enhanced comfort and efficiency. Additionally, the integrated SmartComfort technology provides homeowners with user-friendly control options.

The 95G1UH model shares many of the same advanced features as the A95UH but is tailored for different installation scenarios. With a comparable efficiency rating, the 95G1UH emphasizes ease of maintenance and installation. Its compact design and lightweight construction make it an ideal choice for various settings where space is limited.

All four models incorporate the latest in comfort control technology, allowing for seamless connectivity and programmability. Homeowners can utilize smart thermostats to optimize their heating schedules, further enhancing energy savings. The featured robust warranty and service support from Allied Air Enterprises provide peace of mind, ensuring that these units will deliver reliable performance for years to come.

Overall, the A93UH, 92G1UH, A95UH, and 95G1UH models stand out in the HVAC market due to their efficiency, innovative features, and durability. These units cater to a variety of heating needs while keeping operational costs low, making them wise investments for any property owner.