Allied Air Enterprises 92G1UH, A95UH, 95G1UH Unconfined Space, Confined Space, Air from Inside

Page 7

air is brought into the house for combustion, negative pressure (outside pressure is greater than inside pressure) will build to the point that a down draft can occur in the furnace vent pipe or chimney. As a result, combustion gases enter the living space creating a potentially dangerous situation.

In the absence of local codes concerning air for combustion and ventilation, use the guidelines and procedures in this section to install these furnaces to ensure efficient and safe operation. You must consider combustion air needs and requirements for exhaust vents and gas piping. A portion of this information has been reprinted with permission from the National Fuel Gas Code (ANSI-Z223.1/NFPA 54). This reprinted material is not the complete and official position of ANSI on the referenced subject, which is represented only by the standard in its entirely.

In Canada, refer to the CSA B149 Installation codes.

CAUTION

Do not install the furnace in a corrosive or contaminated atmosphere. Meet all combustion and ventilation air requirements, as well as all local codes.

All gas-fired appliances require air for the combustion process. If sufficient combustion air is not available, the furnace or other appliance will operate inefficiently and unsafely. Enough air must be provided to meet the needs of all fuel-burning appliances and appliances such as exhaust fans which force air out of the house. When fireplaces, exhaust fans, or clothes dryers are used at the same time as the furnace, much more air is required to ensure proper combustion and to prevent a down draft. Insufficient air causes incomplete combustion which can result in carbon monoxide.

In addition to providing combustion air, fresh outdoor air dilutes contaminants in the indoor air. These contaminants may include bleaches, adhesives, detergents, solvents and other contaminants which can corrode furnace components.

The requirements for providing air for combustion and ventilation depend largely on whether the furnace is installed in an unconfined or a confined space.

Unconfined Space

An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This space also includes adjacent rooms which are not separated by a door. Though an area may appear to be unconfined, it might be necessary to bring in outdoor air for combustion if the structure does not provide enough air by

infiltration. If the furnace is located in a building of tight construction with weather stripping and caulking around the windows and doors, follow the procedures in the “Air from Outside” section.

Confined Space

A confined space is an area with a volume less than 50 cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the combined input rating of all appliances installed in that space. This definition includes furnace closets or small equipment rooms.

When the furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace. This is especially important when the furnace is mounted on a platform in a confined space such as a closet or small equipment room. Even a small leak around the base of the unit at the platform or at the return air duct connection can cause a potentially dangerous negative pressure condition. Air for combustion and ventilation can be brought into the confined space either from inside the building or from outside.

Air from Inside

If the confined space that houses the furnace adjoins a space categorized as unconfined, air can be brought in by providing two permanent openings between the two spaces. Each opening must have a minimum free area of 1 square inch (645 mm²) per 1,000 Btu (.29 kW) per hour of total input rating of all gas-fired equipment in the confined space. Each opening must be at least 100 square inches (64516 mm²). One opening shall be within 12 inches (305 mm) of the top of the enclosure and one opening within 12 inches (305 mm) of the bottom. See Figure 4.

Equipment in Confined Space - All Air From Inside

NOTE: Each opening shall have a free area of at least one square inch per 1,000 Btu (645 mm² per .29 kW) per hour of the total input rating of all equipment in the enclosure, but not less than 100 square inches (64546 mm²).

Figure 4

506501-01

Issue 1031

Page 7 of 48

Image 7
Contents A95UH, A93UH, 95G1UH & 92G1UH Table of ContentsFront View Side View A95UH, A93UH, 95G1UH & 92G1UH Unit Dimensions inches mmExpanded View Building Codes Safety InformationA95UH, A93UH, 95G1UH &92G1UH Gas Furnace Shipping and Packing ListInstalled in Combination with a Cooling Coil Installed LocationsUse of Furnace as a Construction Heater Combustion, Dilution & Ventilation Air Product Contains Fiberglass WoolEquipment in Confined Space All Air From Inside Unconfined SpaceConfined Space Air from InsideAir from Outside Upflow Applications InstallationSetting Equipment Shipping Bolt RemovalReturn Air Guidlines Installation ClearancesSide Return Air With transition and filter Removing the Bottom Panel Optional Return Air Base Upflow Applications OnlyHorizontal Applications Suspended Installation of Horizontal Unit Horizontal Application Installation ClearancesDuct System Pipe & Fittings SpecificationsReturn Air -- Horizontal Applications FiltersCanadian Applications Only Piping and Fittings SpecificationsOutdoor Termination Kits Usage Joint Cementing ProcedureExhaust Piping Figures 22 Horizontal Application Exhaust PipeMinimum Vent Pipe Lengths Maximum Allowable Vent Length Right Hand Discharge Shown Intake Piping Figures 24 through Typical AIR Intake Pipe Connections General Guidelines for Vent Terminations For Canadian Installations OnlyVent Termination Clearances For NON-DIRECT Vent INSTALLATiONS in the USA and CanadaFor Direct Vent INSTALLATiONS in the USA and Canada Field Supplied Wall Termination 15F75 or 44J41Direct Vent Concentric Rooftop Termination Direct Vent Application Using Existing Chimney Condensate Piping NON-DIRECT Vent Application Using Existing ChimneyNON-DIRECT Vent Roof Termination KIT NON-DIRECT Vent Field Supplied Wall TerminationUnit shown in upflow position Condensate Trap and Plug LocationsUnit shown in upflow position with remote trap Condensate Trap LocationsLeak Check Gas PipingFire or Explosion Hazard Horizontal Applications Possible Gas Piping Configurations Carbon Monoxide Poisoning Hazard Electrical Precautions and ProceduresInterior MAKE-UP BOX Installation Accessory TerminalsGenerator Use Voltage Requirements Typical Field Wiring DiagramFurnace & Condensing Unit Thermostat Designations Indoor Blower SpeedsTypical Wiring Diagram Automatic Hot Surface Ignition System Unit Start-Up Integrated ControlPlacing the furnace into operation GAS Valve Shown in on Position High Altitude Information Gas Pressure AdjustmentSupply Pressure Measurement Manifold Pressure MeasurementCarbon Monoxide Poisoning Hazard Heat FAN-OFF Time Seconds Electrical SHOCK, Fire Or Explosion Hazard Cleaning the Burner Assembly Failure Codes Planned ServiceBlower Parts Repair Parts ListCabinet Parts Heating Parts Control Panel PartsUnit SET UP Unit Operation Manufacturer Requirements BELOW. Keep Clear of ALL Obstructions

92G1UH, 95G1UH, A95UH, A93UH specifications

Allied Air Enterprises is renowned for producing high-quality HVAC systems, and its models A93UH, 92G1UH, A95UH, and 95G1UH are no exception. These units exemplify cutting-edge technology, efficiency, and reliability, making them popular choices for residential and commercial applications.

The A93UH model is a high-efficiency gas furnace designed with advanced features that maximize performance while maintaining low operating costs. It boasts a 93% Annual Fuel Utilization Efficiency (AFUE) rating, which ensures that a significant portion of the fuel consumed translates into heat. The A93UH incorporates variable-speed blower technology, allowing for precise airflow adjustments that enhance comfort and energy savings.

Similarly, the 92G1UH is built to provide exceptional heating capabilities. With a robust construction and innovative design, this model also achieves a 92% AFUE rating. It features a durable heat exchanger and a reliable ignition system that ensures consistent performance. The 92G1UH is engineered for quiet operation, minimizing noise levels and contributing to a more comfortable indoor environment.

Moving on to the A95UH, this unit represents the pinnacle of efficiency with its impressive 95% AFUE rating. This model not only emphasizes energy savings but also focuses on long-term durability. Equipped with a two-stage gas valve, the A95UH allows for flexible heating based on demand, which translates into enhanced comfort and efficiency. Additionally, the integrated SmartComfort technology provides homeowners with user-friendly control options.

The 95G1UH model shares many of the same advanced features as the A95UH but is tailored for different installation scenarios. With a comparable efficiency rating, the 95G1UH emphasizes ease of maintenance and installation. Its compact design and lightweight construction make it an ideal choice for various settings where space is limited.

All four models incorporate the latest in comfort control technology, allowing for seamless connectivity and programmability. Homeowners can utilize smart thermostats to optimize their heating schedules, further enhancing energy savings. The featured robust warranty and service support from Allied Air Enterprises provide peace of mind, ensuring that these units will deliver reliable performance for years to come.

Overall, the A93UH, 92G1UH, A95UH, and 95G1UH models stand out in the HVAC market due to their efficiency, innovative features, and durability. These units cater to a variety of heating needs while keeping operational costs low, making them wise investments for any property owner.