Allied Air Enterprises 95G1UH, A95UH, A93UH, 92G1UH 15F75 or 44J41, Field Supplied Wall Termination

Page 25

Details of Intake and Exhaust Piping Terminations for Direct Vent Installations

NOTE: In Direct Vent installations, combustion air is taken from outdoors and flue gases are discharged to outdoors.

Intake and exhaust pipes may be routed either horizontally through and outside wall or vertically through the roof. In attic or closet installations, vertical termination through the roof is preferred. Figures 30 through 40 show typical terminations.

1.Exhaust and intake exits must be in same pressure zone. Do not exit one through the roof and one on the side. Also, do not exit the intake on one side and the exhaust on another side of the house or structure.

2.Intake and exhaust pipes should be placed as close together as possible at termination end (refer to illustrations). Maximum separation is 3” (76 mm) on roof terminations and 6” (152 mm) on sidewall terminations.

3.On roof terminations, the intake piping should terminate straight down using two 90° elbows (See Figure 30).

4.Exhaust piping must terminate straight out or up as shown. A reducer may be required on the exhaust piping at the point where it exits the structure to improve the velocity of exhaust away from the intake piping. See Table 6.

EXHAUST PIPE TERMINATION SIZE REDUCTION

Table 6

NOTE: Care must be taken to avoid recirculation of exhaust back into intake pipe.

DIRECT VENT ROOF TERMINATION KIT

(15F75 OR 44J41)

Figure 30

FIELD SUPPLIED WALL TERMINATION

See venting Table 5 for maximum venting lengths with this arrangement.

*Use wall support every 24” (610 mm). Use two wall supports if extension is greater than 24” (610 mm) but less than 48” (1219 mm).

NOTE: One wall support must be 6” (152 mm) from top of each pipe (intake and exhaust).

Figure 31

506501-01

Issue 1031

Page 25 of 48

Image 25
Contents A95UH, A93UH, 95G1UH & 92G1UH Table of ContentsFront View Side View A95UH, A93UH, 95G1UH & 92G1UH Unit Dimensions inches mmExpanded View A95UH, A93UH, 95G1UH &92G1UH Gas Furnace Safety InformationShipping and Packing List Building CodesInstalled in Combination with a Cooling Coil Installed LocationsUse of Furnace as a Construction Heater Combustion, Dilution & Ventilation Air Product Contains Fiberglass WoolConfined Space Unconfined SpaceAir from Inside Equipment in Confined Space All Air From InsideAir from Outside Setting Equipment InstallationShipping Bolt Removal Upflow ApplicationsReturn Air Guidlines Installation ClearancesSide Return Air With transition and filter Removing the Bottom Panel Optional Return Air Base Upflow Applications OnlyHorizontal Applications Suspended Installation of Horizontal Unit Horizontal Application Installation ClearancesReturn Air -- Horizontal Applications Pipe & Fittings SpecificationsFilters Duct SystemCanadian Applications Only Piping and Fittings SpecificationsOutdoor Termination Kits Usage Joint Cementing ProcedureExhaust Piping Figures 22 Horizontal Application Exhaust PipeMinimum Vent Pipe Lengths Maximum Allowable Vent Length Right Hand Discharge Shown Intake Piping Figures 24 through Typical AIR Intake Pipe Connections General Guidelines for Vent Terminations For Canadian Installations OnlyVent Termination Clearances For NON-DIRECT Vent INSTALLATiONS in the USA and CanadaFor Direct Vent INSTALLATiONS in the USA and Canada Field Supplied Wall Termination 15F75 or 44J41Direct Vent Concentric Rooftop Termination Direct Vent Application Using Existing Chimney NON-DIRECT Vent Roof Termination KIT NON-DIRECT Vent Application Using Existing ChimneyNON-DIRECT Vent Field Supplied Wall Termination Condensate PipingUnit shown in upflow position Condensate Trap and Plug LocationsUnit shown in upflow position with remote trap Condensate Trap LocationsLeak Check Gas PipingFire or Explosion Hazard Horizontal Applications Possible Gas Piping Configurations Carbon Monoxide Poisoning Hazard Interior MAKE-UP BOX Installation Precautions and ProceduresAccessory Terminals ElectricalFurnace & Condensing Unit Thermostat Designations Typical Field Wiring DiagramIndoor Blower Speeds Generator Use Voltage RequirementsTypical Wiring Diagram Automatic Hot Surface Ignition System Unit Start-Up Integrated ControlPlacing the furnace into operation GAS Valve Shown in on Position Supply Pressure Measurement Gas Pressure AdjustmentManifold Pressure Measurement High Altitude InformationCarbon Monoxide Poisoning Hazard Heat FAN-OFF Time Seconds Electrical SHOCK, Fire Or Explosion Hazard Cleaning the Burner Assembly Failure Codes Planned ServiceCabinet Parts Heating Parts Repair Parts ListControl Panel Parts Blower PartsUnit SET UP Unit Operation Manufacturer Requirements BELOW. Keep Clear of ALL Obstructions

92G1UH, 95G1UH, A95UH, A93UH specifications

Allied Air Enterprises is renowned for producing high-quality HVAC systems, and its models A93UH, 92G1UH, A95UH, and 95G1UH are no exception. These units exemplify cutting-edge technology, efficiency, and reliability, making them popular choices for residential and commercial applications.

The A93UH model is a high-efficiency gas furnace designed with advanced features that maximize performance while maintaining low operating costs. It boasts a 93% Annual Fuel Utilization Efficiency (AFUE) rating, which ensures that a significant portion of the fuel consumed translates into heat. The A93UH incorporates variable-speed blower technology, allowing for precise airflow adjustments that enhance comfort and energy savings.

Similarly, the 92G1UH is built to provide exceptional heating capabilities. With a robust construction and innovative design, this model also achieves a 92% AFUE rating. It features a durable heat exchanger and a reliable ignition system that ensures consistent performance. The 92G1UH is engineered for quiet operation, minimizing noise levels and contributing to a more comfortable indoor environment.

Moving on to the A95UH, this unit represents the pinnacle of efficiency with its impressive 95% AFUE rating. This model not only emphasizes energy savings but also focuses on long-term durability. Equipped with a two-stage gas valve, the A95UH allows for flexible heating based on demand, which translates into enhanced comfort and efficiency. Additionally, the integrated SmartComfort technology provides homeowners with user-friendly control options.

The 95G1UH model shares many of the same advanced features as the A95UH but is tailored for different installation scenarios. With a comparable efficiency rating, the 95G1UH emphasizes ease of maintenance and installation. Its compact design and lightweight construction make it an ideal choice for various settings where space is limited.

All four models incorporate the latest in comfort control technology, allowing for seamless connectivity and programmability. Homeowners can utilize smart thermostats to optimize their heating schedules, further enhancing energy savings. The featured robust warranty and service support from Allied Air Enterprises provide peace of mind, ensuring that these units will deliver reliable performance for years to come.

Overall, the A93UH, 92G1UH, A95UH, and 95G1UH models stand out in the HVAC market due to their efficiency, innovative features, and durability. These units cater to a variety of heating needs while keeping operational costs low, making them wise investments for any property owner.