Lennox Hearth LMDVT-3328-CNM Table C, Maximum Minimum Feet Meter, Table D + H1 Maximum Minimum

Page 16

VERTICAL VENT FIGURES/TABLES (CONTINUED)

Table C

H+H1 Maximum

H Maximum

V Minimum

feet

(meter)

feet

(meter)

feet

(meter)

5

(1.524)

2

(0.610)

1

(0.305)

 

 

 

 

 

 

10

(3.048)

4

(1.219)

2

(0.610)

 

 

 

 

 

 

15

(4.572)

6

(1.829)

3

(0.914)

 

 

 

 

 

 

20

(6.096)

8

(2.438)

4

(1.219)

V + V1 + H + H1 = 40 feet (12.2 m) Max

H = 8 feet (2.438 meters) Max.

H + H1 = 20 feet (6.096 meters) Max.

uWhen using Secure Flex, use Firestop / Spacer SF4.5VF vWhen using Secure Flex, use Firestop / Spacer SF4.5HF

Example: If 20 feet total (H+H1) horizontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1(V) to 5(H) ratio. For every 1 foot of (V) vertical, you are allowed 5 feet of (H+H1) horizontal run up to a maximum total horizontal run of 20 feet.

Figure 31 - Rear Vent - three elbows

H1

uCeiling

Firestop / Spacer (SV4.5VF)

vWall Firestop/

Spacer (SV4.5HF)

V1

uCeiling

 

Firestop / Spacer

 

(SV4.5VF)

V

H

Table D

H + H1 Maximum

 

V Minimum

feet

 

(meter)

feet

 

(meter)

 

 

 

 

 

 

5

 

(1.524)

 

Elbow Only

 

 

 

 

 

5

 

(1.524)

1

 

(0.305)

 

 

 

 

 

 

10

 

(3.048)

2

 

(0.610)

15

 

(4.572)

3

 

(0.914)

 

 

 

 

 

 

20

 

(6.096)

4

 

(1.219)

 

 

 

 

 

 

 

H + H1 = 20 feet (6.096 m) Max.

 

V + V1 + H + H1 = 40 ft. (12.192 m) Max.

uWhen using Secure Flex, use Firestop / Spacer SF4.5VF vWhen using Secure Flex, use Firestop / Spacer SF4.5HF

Example: If 20 feet total (H+H1) horizontal vent run is needed,

then 4 feet minimum of (V) verti-

 

uCeiling

cal vent will be required.

 

 

Firestop / Spacer

This table shows a 1(V) to 5(H)

V1

(SV4.5VF)

ratio. For every 1 foot of (V)

 

 

vertical, you are allowed 5 feet

 

 

of (H+H1) horizontal run up to

 

 

a maximum total horizontal run

 

H

of 20 feet.

 

 

 

An elbow is acceptable as 1 foot

 

 

of vertical rise except where

 

 

an elbow is the only vertical

 

H1

component in the system. See

 

 

Figure 37.

vWall Firestop/

Spacer (SV4.5HF)

V

Figure 32 - Top Vent - three elbows

16

Horizontal (Outside Wall)

Termination System

Figure 33 on Page 17, and Figures 34 to 42 on Pages 18 to 21 and their associated Horizontal Vent Table illustrate the various horizontal venting configurations that are possible for use with these appliances. Secure Vent pipe applications are shown in these Figures; Secure Flex pipe may also be used. A Horizontal Vent Table summarizes each system’s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications.

Both of these horizontal vent systems terminate through an outside wall. Building Codes limit or prohibit terminating in specific areas. Refer to Figure 7 on Page 6 for location guidelines.

Secure Vent SV4.5 direct vent system compo- nents are unitized concentric pipe components featuring positive twist lock connection, (refer to Figure 22 on Page 13). All of the appli- ances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

A. Plan the vent run -

Analyze the vent routing and determine the types and quantities of sections required 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181

mm)net section lengths are available. Plan the vent lengths so that a joint does not occur at the intersection of ceiling or roof joists. Make allow- ances for elbows as indicated in Figure 24.

Maintain a minimum 1" (25 mm) clearance to combustibles on the vertical sections. Clear- ances for the horizontal runs are; 3" (76 mm) on top, 1" (25 mm) on sides, and 1" (25 mm) at the bottom.

Image 16
Contents 850,029M REV. G 05/2008 Vented GAS Fireplace Heaters Direct Vent ModelsOTL Report No -F-31-5 Table of Contents SIT Millivolt Honeywell MillivoltCold Climate Insulation LocationMassachusetts And New York City, NY Re- quirements MassachusettsManufactured Home Requirements Vertical Vent Termination ClearancesHorizontal Vent Termination Clearances Vent Termination ClearancesCanadian Installation US Installation Meter/regulator assembly= Clearance to service regulator vent outlet Feet 91cm Inches 30cmMinimum Clearances to Combustibles Appliance and Vent ClearancesPanel or louvers Adjacent to itDetailed Installation Steps Typical Installation SequenceFraming Routing Gas LineFireplace specifications FromThis center mark see Figure Vent Size Vertical Venting Through the CeilingFireplace Framing specifications Schedule Black Iron Pipe Inside Diameter InchesNatural PropaneThese fireplaces must be vented directly to the outside Install the Vent System General InformationCross Section Vertical Straight Installation Vent Section Length ChartVertical Termination Systems Roof Effective Vent LengthVertical Offset Installation Attach vent components to each otherPitch Vertical Vent FIGURES/TABLESIf the vent system extends more than 5 feet 610 305 219 829 914 438 Table B Maximum Minimum Feet Meter524 Elbow Only 305 048 610 572 914 096 219 Ratio V to H ratio isTable C Maximum Minimum Feet Meter524 610 305 048 219 572 829 914 096 438 Table D + H1 Maximum MinimumTypical Horizontal Vent Installation See on Page 12 or onSame manner as any SV4.5 vent component refer to Step E Install Firestop/Spacer at exterior wallSee on Page 9 for Min Horizontal Vent FIGURES/TABLES Table F MaximumFeet Meter 914Horizontal Vent Figures / Tables Minimum 524 Elbow Only524 305 048 610 572 914Flexible Vent Section Install the Outer Flex PipeAttach Flex Vent to Termination Wiring Optional Forced Air Blower Kit Field WiringSee Figure Connecting Gas Line Schematic Representation OnlyControl Compartment Access Louver Panel Instructions RefChecking Appliance Opera- tion SIT and Honeywell Millivolt Appliance CheckoutElectronic Appliance Checkout Install VERMICULITE, VOLCanic STONE, Glowing Embers and Logs Catalog Number H3366 LOG SETShown here 1 through 6 and per the instructions on Model LMDV-4035 Catalog Number H3365Installing the Glass Door Installing Glass Enclosure PanelsBurner Adjustments Flame Appearance and sooting Air Shutter Adjustment GuidelinesBurner Air Shutter Adjustment Procedure Hood InstallationFinishing Requirements Wall Details Drywall Bracket / Spacer12B Cat. No Model Description12C Cat. No Open Top, Chase Top ShroudListed Secure Flex Components LMDV-3328 & LMDV-3530 Models OnlyDescription All compressed flex vents can be expanded up to two timesH2009 H2011H2013 H2010Adjusting Knob Millivolt Appliances SIT SystemsSIT Millivolt Gas Valve Pilot for SIT Millivolt Gas ValvePilot Orifice Ignitor Assembly Electronic Appliances Honeywell SystemsSeries 850,029M REV. G 05/2008 West Taft Avenue Orange, CA

LMDV-3530-CNM, LMDV-35 Series, LMDVR-3328-CNE, LMDV-4035-CNE, LMDV-4035-CPM specifications

Lennox Hearth products are renowned for their quality, efficiency, and innovative technologies that optimize the home heating experience. Among the standout offerings in their lineup are the LMDV-3530-CPM, LMDVR-3328-CPM, LMDV-3530-CNE, LMDVT-3328-CPM, and LMDVR-3328-CNM models. Each of these products embodies the brand's commitment to performance and design, making them a popular choice for modern homeowners.

The LMDV-3530-CPM gas fireplace boasts a contemporary aesthetic combined with powerful heating capabilities. It features a clean face design that enhances the viewing experience while maximizing warmth in the room. The unit is equipped with advanced technology that includes multi-speed blowers for efficient air circulation, allowing users to enjoy consistent heat throughout the space. Its variable flame and heat control options ensure that homeowners can customize their ambience and comfort levels according to their preferences.

Similarly, the LMDVR-3328-CPM model is designed for versatility and efficiency. Its modern fireplace insert converts existing masonry fireplaces into high-efficiency heating systems. Featuring a sleek design, this insert incorporates innovative venting technologies that enable it to operate in diverse installation configurations, enhancing both aesthetic appeal and functionality. Homeowners can appreciate the adjustable flame and fan speed settings, which provide tailored heating solutions.

The LMDV-3530-CNE model distinguishes itself through eco-friendly features. It employs advanced combustion technology that reduces emissions without sacrificing heat output. This model stands out as an environmentally responsible option, suitable for conscious consumers who wish to reduce their carbon footprint. Its easy-to-use controls and stylish design make it a favored choice among discerning homeowners.

The LMDVT-3328-CPM continues the trend of performance and versatility. This model combines traditional charm with modern efficiency, featuring a large viewing area that allows for an inviting flame display. The unit’s heat exchanger is designed for maximum heat transfer, ensuring that warmth is efficiently distributed throughout the room.

Lastly, the LMDVR-3328-CNM model is perfect for those seeking an efficient upgrade for their traditional fireplace. With its stunning design and advanced features, including optional remote control and programmable settings, this model takes convenience to new heights.

Overall, Lennox Hearth’s suite of models combines elegance, efficiency, and innovation, ensuring that homeowners can find the perfect heating solution to complement their living spaces. Each product is engineered with state-of-the-art technologies that reflect Lennox’s dedication to quality and customer satisfaction.