Lennox Hearth LMDVR-3328-CNE Horizontal Vent FIGURES/TABLES, Table F Maximum, Feet Meter, 914

Page 19

HORIZONTAL VENT FIGURES/TABLES

Notes:

Secure Vent components (rigid vent pipe and terminal) are shown in the Figures; Secure Flex components (flexible vent pipe and terminal) may also be used.

Two 45 degree elbows may be used in place of one 90 degree elbow. The same rise to run ratios, as shown in the venting Figures for 90 elbows,must be followed if 45 degree elbows are used.

SV4.5VF (Secure Vent), SF4.5VF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible floor or ceil- ing. SV4.5HF (Secure Vent), SF4.5HF (Secure Flex) firestop/spacer must be used anytime vent pipe passes through a combustible wall.

It is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level.

The tables show a 1(V) to 5(H) ratio up to a maximum horizontal run of 20 feet except for installations where an elbow is the only vertical vent section in the system (see Figure 37).

AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM. See Figure 37.

Venting Components Required for Various Exterior Wall Thick-

nesses, when using Square Termination Kit (SV4.5HT-2)

Vent Components Required

Exterior Wall Thickness - inches (mm)

 

 

Termination Kit Only

6 to 9-1/4 (152 to 235)

Termination Kit and 6 In. Vent

10-3/4 to 14 (273 to 356)

Section (SV4.5L6)

 

WARNING

Under no circumstances, may separate sections of concentric flexible vent pipe be joined together.

 

Table F

 

 

H Maximum

V Minimum

 

feet

(meter)

feet

(meter)

 

3

(0.914)

Elbow Only

 

Square termination

 

 

 

(SV4.5HT-2) shown.

 

H

 

 

 

 

 

V

 

When using

Secure

Flex,

Wall

 

 

 

 

use Firestop/Spacer

Firestop/Spacer

 

SF4.5HF

(SV4.5HF)

 

 

 

See Table 12 as an aid in venting component selection for a particular

range of exterior wall thicknesses.

Figure 37 - Top Vent -

 

 

ONE 90 DEGREE ELBOW - ELBOW CONNECTION AT APPLIANCE

Termination

Kit and 12 in.

16-3/4 to 20 (426 to 508)

Vent Section (SV4.5L12)

 

 

 

 

Termination

Kit and Tele-

11-3/4 to 20 (299 to 508)

scopic Section (SV4.5L12)

 

Table 12

 

Note: See Figure 35 showing wall thickness range

 

when using SV4.5HT-2 termination kit only.

 

 

See Table 12 as an aid in venting component selection for a particular range of exterior wall thicknesses.

H = 28 in. (711 mm) Maximum.

When using Secure Flex,

H

use Firestop/Spacer

 

SF4.5HF

 

Wall Firestop/Spacer (SV4.5HF)

 

 

 

Table G

 

 

 

 

 

 

 

 

H Maximum

V Minimum

 

 

 

 

 

 

 

feet

 

(meter)

feet

(meter)

 

 

 

 

 

 

 

5

 

(1.524)

1

(0.305)

 

10

 

(3.048)

2

(0.610)

 

 

 

 

 

 

 

15

 

(4.572)

3

(0.914)

 

 

 

 

 

 

 

20

 

(6.096)

4

(1.219)

 

 

 

 

 

 

 

 

V + H = 40 feet (12.2 m) Max.

 

 

 

H = 20 ft. (6.096 m) Max.

When using Secure Flex,

 

 

 

use Firestop/Spacer

 

 

 

 

 

SF4.5VF.

 

 

 

When using Secure Flex,

 

 

 

use Firestop/Spacer

 

 

 

 

 

 

 

 

 

SF4.5HF.

 

 

 

Example: If 20 feet of (H) hori- zontal vent run is needed, then 4 feet minimum of (V) vertical vent will be required.

This table shows a 1(V) to 5(H) ratio. For every 1 foot of vertical, you are allowed 5 feet of (H) horizontal run up to a maximum (H) horizontal run of 20 feet.

H

V

7 in. (178 mm)

Square termination (SV4.5HT-2) shown.

Figure 36 - Rear Vent - NO ELBOWS - Square Horizontal Termination (SV4.5HT-2)

 

Wall Firestop/Spacer

 

(SV4.5HF)

Square termination

Ceiling

Firestop/Spacer

(SV4.5HT-2) shown.

(SV4.5VF)

See Table 12 as an aid in venting component selection for a particular range of exterior wall thicknesses.

Figure 38 - Top Vent - ONE 90 DEGREE ELBOW -

ELBOW CONNECTION NOT DIRECTLY AT APPLIANCE

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

19

Image 19
Contents 850,029M REV. G 05/2008 Vented GAS Fireplace Heaters Direct Vent ModelsOTL Report No -F-31-5 Table of Contents Honeywell Millivolt SIT MillivoltMassachusetts Cold Climate InsulationLocation Massachusetts And New York City, NY Re- quirementsVent Termination Clearances Manufactured Home RequirementsVertical Vent Termination Clearances Horizontal Vent Termination ClearancesInches 30cm Canadian Installation US InstallationMeter/regulator assembly = Clearance to service regulator vent outlet Feet 91cmAdjacent to it Minimum Clearances to CombustiblesAppliance and Vent Clearances Panel or louversRouting Gas Line Detailed Installation StepsTypical Installation Sequence FramingVent Size Vertical Venting Through the Ceiling Fireplace specificationsFrom This center mark see FigurePropane Fireplace Framing specificationsSchedule Black Iron Pipe Inside Diameter Inches NaturalThese fireplaces must be vented directly to the outside Install the Vent System General InformationCross Section Effective Vent Length Vertical Straight InstallationVent Section Length Chart Vertical Termination Systems RoofAttach vent components to each other Vertical Offset InstallationPitch Vertical Vent FIGURES/TABLESIf the vent system extends more than 5 feet Ratio V to H ratio is 610 305 219 829 914 438Table B Maximum Minimum Feet Meter 524 Elbow Only 305 048 610 572 914 096 219Table D + H1 Maximum Minimum Table CMaximum Minimum Feet Meter 524 610 305 048 219 572 829 914 096 438See on Page 12 or on Typical Horizontal Vent InstallationSame manner as any SV4.5 vent component refer to Step E Install Firestop/Spacer at exterior wallSee on Page 9 for Min 914 Horizontal Vent FIGURES/TABLESTable F Maximum Feet MeterHorizontal Vent Figures / Tables 048 610 572 914 Minimum524 Elbow Only 524 305Flexible Vent Section Install the Outer Flex PipeAttach Flex Vent to Termination Wiring Optional Forced Air Blower Kit Field WiringSee Figure Schematic Representation Only Connecting Gas LineSIT and Honeywell Millivolt Appliance Checkout Control Compartment AccessLouver Panel Instructions Ref Checking Appliance Opera- tionElectronic Appliance Checkout Install VERMICULITE, VOLCanic STONE, Glowing Embers and Logs Catalog Number H3366 LOG SETShown here 1 through 6 and per the instructions on Catalog Number H3365 Model LMDV-4035Air Shutter Adjustment Guidelines Installing the Glass DoorInstalling Glass Enclosure Panels Burner Adjustments Flame Appearance and sootingDrywall Bracket / Spacer Burner Air Shutter Adjustment ProcedureHood Installation Finishing Requirements Wall Details12B Cat. No Model Description12C Open Top, Chase Top Shroud Cat. NoAll compressed flex vents can be expanded up to two times Listed Secure Flex ComponentsLMDV-3328 & LMDV-3530 Models Only DescriptionH2010 H2009H2011 H2013Pilot for SIT Millivolt Gas Valve Adjusting KnobMillivolt Appliances SIT Systems SIT Millivolt Gas Valve850,029M REV. G 05/2008 West Taft Avenue Orange, CA Pilot Orifice Ignitor AssemblyElectronic Appliances Honeywell Systems Series

LMDV-3530-CNM, LMDV-35 Series, LMDVR-3328-CNE, LMDV-4035-CNE, LMDV-4035-CPM specifications

Lennox Hearth products are renowned for their quality, efficiency, and innovative technologies that optimize the home heating experience. Among the standout offerings in their lineup are the LMDV-3530-CPM, LMDVR-3328-CPM, LMDV-3530-CNE, LMDVT-3328-CPM, and LMDVR-3328-CNM models. Each of these products embodies the brand's commitment to performance and design, making them a popular choice for modern homeowners.

The LMDV-3530-CPM gas fireplace boasts a contemporary aesthetic combined with powerful heating capabilities. It features a clean face design that enhances the viewing experience while maximizing warmth in the room. The unit is equipped with advanced technology that includes multi-speed blowers for efficient air circulation, allowing users to enjoy consistent heat throughout the space. Its variable flame and heat control options ensure that homeowners can customize their ambience and comfort levels according to their preferences.

Similarly, the LMDVR-3328-CPM model is designed for versatility and efficiency. Its modern fireplace insert converts existing masonry fireplaces into high-efficiency heating systems. Featuring a sleek design, this insert incorporates innovative venting technologies that enable it to operate in diverse installation configurations, enhancing both aesthetic appeal and functionality. Homeowners can appreciate the adjustable flame and fan speed settings, which provide tailored heating solutions.

The LMDV-3530-CNE model distinguishes itself through eco-friendly features. It employs advanced combustion technology that reduces emissions without sacrificing heat output. This model stands out as an environmentally responsible option, suitable for conscious consumers who wish to reduce their carbon footprint. Its easy-to-use controls and stylish design make it a favored choice among discerning homeowners.

The LMDVT-3328-CPM continues the trend of performance and versatility. This model combines traditional charm with modern efficiency, featuring a large viewing area that allows for an inviting flame display. The unit’s heat exchanger is designed for maximum heat transfer, ensuring that warmth is efficiently distributed throughout the room.

Lastly, the LMDVR-3328-CNM model is perfect for those seeking an efficient upgrade for their traditional fireplace. With its stunning design and advanced features, including optional remote control and programmable settings, this model takes convenience to new heights.

Overall, Lennox Hearth’s suite of models combines elegance, efficiency, and innovation, ensuring that homeowners can find the perfect heating solution to complement their living spaces. Each product is engineered with state-of-the-art technologies that reflect Lennox’s dedication to quality and customer satisfaction.