Friedrich 2008, 2009 service manual

Models: 2009 2008

1 68
Download 68 pages 41.17 Kb
Page 20
Image 20
1.Activate Error Code Mode by pressing the “TIMER ON/ OFF” button on XQ models. LED for the “TIMER ON/ OFF” will flash 1 bps while Error Code Mode is active. Pressing the “TEMP/HR  ” button will display 00. Consecutive presses will scroll through all error codes logged. Press the “TEMP/HR  ” button to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear.

Activating Error Code Mode: (Submode of Test Mode) Unit must be in Test Mode to enter Error Code Mode

1.Activate Error Code Mode by pressing the “TIMER ON/ OFF” button on XQ models. LED for the “TIMER ON/ OFF” will flash 1 bps while Error Code Mode is active. Pressing the “TEMP/HR Manual backgroundbutton will display 00. Consecutive presses will scroll through all error codes logged. Press the “TEMP/HR Manual backgroundbutton to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear.

Activate Error Code Mode by pressing at the same time the “A/C START” button and the “ON/OFF” button on QME models. LED for the “TIMER ON/OFF” will flash 1 bps while Error Code Mode is active. Pressing the “TEMP Manual backgroundbutton will display 00. Consecutive presses will scroll through all error codes logged. Press the “TEMP Manual backgroundbutton to see the reverse order of all error codes logged. When the end of logged error codes is reached the temperature set point will appear.

IMPORTANT: Error Codes are cleared from the log by exiting from Error Code Mode. To exit on XQ models, press Timer On/Off button. To exit QME models, press A/C Start and On/Off buttons. Or unplug unit to exit Error Code Mode. Plug unit in after 5 seconds to resume normal operation of unit.

TESTING THE ELECTRONIC CONTROL ERROR CODE LISTINGS

E1 SHORT CYCLE SITUATION: Defined as (compressor powered on before the three minute time delay ten times in one hour. Investigate and correct short cycling problem.

E2 KEYBOARD STUCK ERROR: If key button(s) are pressed continuously for twenty seconds or more. If MODE key is stuck, unit will default to cool. Exit Error Code Mode to see if error “E2” is no longer displayed and unit is functioning. Replace board if “E2” still displays after exiting Error Code Mode.

E3 FROST PROBE OPEN: Normal operation is allowed. Ohm frost probe. Replace probe if ohm value not read. If ohm value is present replace board.

E4 FROST PROBE SHORT: Normal operation allowed. Replace probe.

E5 INDOOR PROBE OPEN: Control assumes indoor ambient temperature is 90 degree F and unit will operate. Ohm indoor probe. Replace probe if ohm value not read.

E6 INDOOR PROBE SHORT: Control assumes ambient temperature is 90 degree F and unit will operate. Replace probe.

NOTE: All Error Code displays for Frost & Indoor Probe will allow unit to operate. Unit may or will ice up if faulty components not replaced.

FROST PROBE SENSOR: disables compressor at 35 degrees F.

INDOOR PROBE SENSOR: Control range is 60 degrees F to 90 degrees F +/- 2 degrees F.

Indoor temperature will be displayed by pressing: (QME units) The Fan Speed button and the Temperature Manual background button.

(XQ units) The Fan Speed button and the “TEMP Manual background “ button.

The indoor temperature will be displayed for 10 seconds. The display will change back to the Set Point temperature by pressing any key button except for the On/Off button. The indoor temperature can be viewed in all modes, including test mode.

Check Filter: The Check Filter indicator turns on after the fan motor has been operating for 250 hours. The Check Filter indicator is reset by pressing the Check Filter button one time only. Power failures will not reset the 250 hour timer. All time elapsed is stored in memory and resumes counting after power is restored.

Keep Alive: The electronic control has a memory to retain all functions and status as set up by the user in the event of a power failure. Once power is restored to the unit there is a two second delay before the fan comes on and approximately three minutes delay before the compressor is activated, providing that the mode was set for cooling and the set point temperature has not been met in the room.