Lennox Hearth LMDV-3530-CPM Vertical Offset Installation, Attach vent components to each other

Page 13

Vertical (Offset) Installation

Analyze the vent routing and determine the quantities of vent sections and number of elbows required. Refer to Vertical Vent Figures and Tables on Pages 15 and 16 to select the type of vertical installation desired. Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm). Refer to the Vent Section Length Chart on Page 12 for an aid in selecting length combinations. Elbows are available in 90° and 45° configurations. Refer to Figure 24 on Page 14 for the SV4.5E45 and SV4.5E90 elbow dimensional specifications.

Where required, a telescopic vent section (SV4.5LA) may be used to provide the installer with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location, or will not build up to the required length. The SV4.5LA Telescopic Vent Section has an effective length of from 1-1/2" (38 mm) to 7-1/2" (191 mm). The SV4.5LA is fitted with a locking inclined channel end (identical to a normal vent section component) and a plain end with 3 pilot holes. Slip the plain end over the locking channel end of a standard SV4.5 vent component the required distance and secure with three screws.

Maintain a minimum 1" (25 mm) clearance to combustiblematerialsforallverticalelements. Clearances for all horizontal elements are 3" (76 mm) on top, 1" (25 mm) on sides and 1" (25 mm) on the bottom.

A. Frame ceiling opening - Use a plumb line from the ceiling above the appliance to locate center of the vertical run. Cut and/or frame an opening, 10-1/2" x 10-1/2" (267mm x 267mm) inside dimensions, about this center mark (Figure 21).

10-1/2" Min. (267 mm)

10-1/2" Min.

(267 mm)

Figure 21

B. Attach vent components to appliance - Secure Vent SV4.5 direct vent system compo- nents are unitized concentric pipe components featuring positive twist lock connections (see Figure 22).

All of the appliances covered in this document are fitted with collars having locking inclined channels. The dimpled end of the vent com- ponents fit over the appliance collar to create the positive twist lock connection.

 

Align the dimple (four places) of the

 

upper vent section with the opening

 

of the locking incline channel on the

 

lower vent section or appliance col-

 

lar. Twist vent component clockwise

 

to engage and seal until arrow and

Arrow

dimple align.

 

 

Dimple

 

 

Locking Incline

 

 

Channel

 

 

Connected Vent

Arrow

 

Sections

 

Appliance Collar or

Vent Section

Figure 22

Toattachaventcomponenttotheappliancecollar, align the dimpled end over the collar, adjusting the radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar (refer to Figure 22). Push the vent component against the collar until it fully engages, then twist the component clockwise, running the dimples down and along the incline channels until they seat at the end of the chan- nels. The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe without the need for sealant or screws. If desired, a #6 x 1/2" screw may be used at the joint, but is not required as the pipe will securely lock when twisted.

Note: An elbow may also be attached to the appliance collar. Attach in the same manner as you would a vent section.

C. Attach vent components to each other

-Other vent sections may be added to the previously installed section in accordance with the requirements of the vertical vent Figures and Tables.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

To add another vent component to a length of vent run, align the dimpled end over the inclined channel end of the previously installed section, adjusting the radial alignment until the four lock- ing dimples are aligned with the inlets of the four incline channels of the previous section.

Push the vent component against the previous section until it fully engages, then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels. This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 22.

D. Install firestop/spacer at ceiling - When using Secure Vent, use SV4.5VF firestop/spacer at ceiling joists; when using Secure Flex, use SF4.5VF firestop/spacer. If there is living space above the ceiling level, the firestop/spacer must be installed on the bottom side of the ceiling. If attic space is above the ceiling, the firestop/spacer must be installed on the top side of the joist. Route the vent sections through the framed opening and secure the firestop/spacer with 8d nails or other appropriate fasteners at each corner. Remember to maintain 1" (25 mm) clearance to combustibles, framing members, and attic or ceiling insulation when running vertical chimney sections. Attic insulation shield (H3907) may be used to obtain the required clearances indicated here. See installation accessories Pages 31 & 32.

E. Support the vertical vent run sections - Note - Proper venting support is very important. The weight of the vent must not be supported by the fireplace in any degree.

Support the vertical portion of the venting system every 8 feet (2.4m) above the fireplace vent outlet.

Blocking

Support Straps

(Plumber's tape)

8 feet (2.4 m)

Maximum

1 inch (25.4

mm) minimum

clearance to

combustibles

Figure 23

13

Image 13
Contents 850,029M REV. G 05/2008 Vented GAS Fireplace Heaters Direct Vent ModelsOTL Report No -F-31-5 Table of Contents Honeywell Millivolt SIT MillivoltLocation Cold Climate InsulationMassachusetts And New York City, NY Re- quirements MassachusettsVertical Vent Termination Clearances Manufactured Home RequirementsHorizontal Vent Termination Clearances Vent Termination ClearancesMeter/regulator assembly Canadian Installation US Installation= Clearance to service regulator vent outlet Feet 91cm Inches 30cmAppliance and Vent Clearances Minimum Clearances to CombustiblesPanel or louvers Adjacent to itTypical Installation Sequence Detailed Installation StepsFraming Routing Gas LineFrom Fireplace specificationsThis center mark see Figure Vent Size Vertical Venting Through the CeilingSchedule Black Iron Pipe Inside Diameter Inches Fireplace Framing specificationsNatural PropaneThese fireplaces must be vented directly to the outside Install the Vent System General InformationCross Section Vent Section Length Chart Vertical Straight InstallationVertical Termination Systems Roof Effective Vent LengthAttach vent components to each other Vertical Offset InstallationPitch Vertical Vent FIGURES/TABLESIf the vent system extends more than 5 feet Table B Maximum Minimum Feet Meter 610 305 219 829 914 438524 Elbow Only 305 048 610 572 914 096 219 Ratio V to H ratio isMaximum Minimum Feet Meter Table C524 610 305 048 219 572 829 914 096 438 Table D + H1 Maximum MinimumSee on Page 12 or on Typical Horizontal Vent InstallationSame manner as any SV4.5 vent component refer to Step E Install Firestop/Spacer at exterior wallSee on Page 9 for Min Table F Maximum Horizontal Vent FIGURES/TABLESFeet Meter 914Horizontal Vent Figures / Tables 524 Elbow Only Minimum524 305 048 610 572 914Flexible Vent Section Install the Outer Flex PipeAttach Flex Vent to Termination Wiring Optional Forced Air Blower Kit Field WiringSee Figure Schematic Representation Only Connecting Gas LineLouver Panel Instructions Ref Control Compartment AccessChecking Appliance Opera- tion SIT and Honeywell Millivolt Appliance CheckoutElectronic Appliance Checkout Install VERMICULITE, VOLCanic STONE, Glowing Embers and Logs Catalog Number H3366 LOG SETShown here 1 through 6 and per the instructions on Catalog Number H3365 Model LMDV-4035Installing Glass Enclosure Panels Installing the Glass DoorBurner Adjustments Flame Appearance and sooting Air Shutter Adjustment GuidelinesHood Installation Burner Air Shutter Adjustment ProcedureFinishing Requirements Wall Details Drywall Bracket / Spacer12B Cat. No Model Description12C Open Top, Chase Top Shroud Cat. NoLMDV-3328 & LMDV-3530 Models Only Listed Secure Flex ComponentsDescription All compressed flex vents can be expanded up to two timesH2011 H2009H2013 H2010Millivolt Appliances SIT Systems Adjusting KnobSIT Millivolt Gas Valve Pilot for SIT Millivolt Gas ValveElectronic Appliances Honeywell Systems Pilot Orifice Ignitor AssemblySeries 850,029M REV. G 05/2008 West Taft Avenue Orange, CA

LMDV-3530-CNM, LMDV-35 Series, LMDVR-3328-CNE, LMDV-4035-CNE, LMDV-4035-CPM specifications

Lennox Hearth products are renowned for their quality, efficiency, and innovative technologies that optimize the home heating experience. Among the standout offerings in their lineup are the LMDV-3530-CPM, LMDVR-3328-CPM, LMDV-3530-CNE, LMDVT-3328-CPM, and LMDVR-3328-CNM models. Each of these products embodies the brand's commitment to performance and design, making them a popular choice for modern homeowners.

The LMDV-3530-CPM gas fireplace boasts a contemporary aesthetic combined with powerful heating capabilities. It features a clean face design that enhances the viewing experience while maximizing warmth in the room. The unit is equipped with advanced technology that includes multi-speed blowers for efficient air circulation, allowing users to enjoy consistent heat throughout the space. Its variable flame and heat control options ensure that homeowners can customize their ambience and comfort levels according to their preferences.

Similarly, the LMDVR-3328-CPM model is designed for versatility and efficiency. Its modern fireplace insert converts existing masonry fireplaces into high-efficiency heating systems. Featuring a sleek design, this insert incorporates innovative venting technologies that enable it to operate in diverse installation configurations, enhancing both aesthetic appeal and functionality. Homeowners can appreciate the adjustable flame and fan speed settings, which provide tailored heating solutions.

The LMDV-3530-CNE model distinguishes itself through eco-friendly features. It employs advanced combustion technology that reduces emissions without sacrificing heat output. This model stands out as an environmentally responsible option, suitable for conscious consumers who wish to reduce their carbon footprint. Its easy-to-use controls and stylish design make it a favored choice among discerning homeowners.

The LMDVT-3328-CPM continues the trend of performance and versatility. This model combines traditional charm with modern efficiency, featuring a large viewing area that allows for an inviting flame display. The unit’s heat exchanger is designed for maximum heat transfer, ensuring that warmth is efficiently distributed throughout the room.

Lastly, the LMDVR-3328-CNM model is perfect for those seeking an efficient upgrade for their traditional fireplace. With its stunning design and advanced features, including optional remote control and programmable settings, this model takes convenience to new heights.

Overall, Lennox Hearth’s suite of models combines elegance, efficiency, and innovation, ensuring that homeowners can find the perfect heating solution to complement their living spaces. Each product is engineered with state-of-the-art technologies that reflect Lennox’s dedication to quality and customer satisfaction.