Lennox Hearth L30 DVF-2 operation manual Installation, Max. Vertical Pipe Length 25 feet

Page 7

INSTALLATION

This appliance is designed to be vented with a 4” x 6 5/8” direct-vent pipe. Each direct-vent appliance must use its own separate vent system

VERTICAL TERMINATION

VERTICAL TERMINATION

 

 

HORIZONTAL TERMINATION

WITH NO OFFSETS

WITH 2 OFFSETS

 

 

WITH 1 OFFSET

Min. Vertical Pipe Length: 5 feet

Min. Vertical Pipe From Appliance

to first

Min. Vertical Pipe From Appliance to offset:

Max. Vertical Pipe Length: 25

offset: 2 feet (*see note).

 

 

2 feet (*see note).

feet

Min. Total Vertical Pipe Length: 5 feet

 

 

Max. Vertical Pipe Length: 25 feet

 

 

 

Max. Total Vertical Pipe Length: 25 feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16 Feet Max.

 

 

 

For every 1 feet of

 

 

 

 

 

 

 

 

 

 

 

 

vertical pipe (from

 

 

 

 

 

 

 

 

 

 

 

 

unit to first offset), 2

 

 

 

 

 

 

 

 

 

 

 

 

feet of horizontal

 

 

 

 

 

 

 

 

 

 

 

 

run is allowed (not

 

 

 

 

 

 

 

 

 

 

 

 

to exceed 16 ft.

 

 

 

 

 

For every 1 feet of vertical

 

 

 

 

 

 

 

 

 

 

pipe (from unit to first offset),

 

 

 

Example – with a 6’ ver-

 

 

 

 

 

2 feet of horizontal run is

 

 

 

 

 

 

 

 

allowed (not to exceed 16 ft.

 

 

 

tical pipe off unit, 12’ of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

horizontal run is allowed.

 

 

 

 

 

Example – with a 8’ ver-

 

 

 

 

 

 

 

 

 

 

tical pipe off unit, 16’ of

 

 

 

 

 

 

 

 

 

 

horizontal run is allowed.

 

5 Feet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

 

At 2’ Min. Vertical, 2’ Max.

 

 

Min.

 

 

5 Feet

 

 

Feet

 

 

 

25 Feet

 

 

 

Min.

 

 

Max.

 

Horizontal is allowed.

 

 

 

 

 

 

 

Max.

 

Horizontal

 

25

 

 

 

 

 

Horizontal runs

 

 

 

runs require

 

Feet

 

 

 

 

 

 

 

 

¼” rise per

 

Max.

 

 

 

 

 

require ¼” rise

 

 

 

 

 

 

 

 

 

per foot.

 

 

 

 

 

 

 

 

 

 

 

foot.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* 2 Feet Min.

 

 

 

* 2 Feet Min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall

 

 

 

 

 

 

 

 

 

 

 

Penetration

 

 

 

 

 

 

 

 

 

 

 

Detail

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum total offsets allowed: Not to exceed 180 degrees.

Maximum allowable horizontal pipe run is 16 feet.

With 2 feet of vertical pipe installed from the appliance (* see note), a 2 foot maximum horizontal run allowed. For installations with more than 2 feet of vertical pipe, calculate allowable horizontal run as indicated in applicable illustration above.

See page 10 for Vent Termination Requirements.

Also see pipe manufacturers instructions for additional vent installation requirements. Horizontal vent clearances: 3“ minimum top 1“ minimum on bottom and sidewalls. Vertical vent clearances: 1” minimum.

Install vent support brackets every 4 feet of vertical pipe unless otherwise specified by vent manufacturer.

*Note: If using Propane Gas (LP), it may be necessary to install (as a minimum) 3 feet of vertical pipe from the appliance prior to an offset to ensure optimum product performance. This may be necessary due to variations in vent configuration and other numerous factors which affect exhaust flow and air delivery such as BTU value, ambient temperature, wind conditions, altitude, etc.

PAGE 7

Image 7
Contents Retain this Manual for Future Reference Freestanding Vented GAS Fired Room Heaters775,029M Rev. B, 8/04 Important Warnings / Cautions Table of Contents LOW High Planning Your InstallationLocal and National Code Requirements Tool / Equipment ListQuestions to ASK the Local Building Official Corner Clearances to Combustible MaterialsManufactured Mobile Home Requirements Rear Wall or AlcoveMax. Vertical Pipe Length 25 feet InstallationMax. Total Vertical Pipe Length 25 feet Symptoms Excessive Combustion Air Vent Restrictor Ring InstallationSV 0 SHK Direct Vent System Components Model L30 DVF-2SV4MCK Vertical Vent Termination ClearancesHorizontal Vent Termination Requirements GAS Supply Hookup Pressure TestingSupply Line Size Requirements Door Operation Installing LOG SET GAS Appliance Final AssemblyGlowing Embers Adjust gap as shown in following picture Installation Check ListLighting and Shutdown Instructions Pilot AssemblyCare and Operation Gas Control KnobsVariable Speed Control for Air Circulation Blower BREAK-IN PeriodCombustion Chamber Relief Doors Circulation Blower OperationCanada Parts ListPropane Conversion Procedure Propane ConversionBurner Flame Appearance Reference InformationMaintenance Pilot Flame Appearance Air Shutter AdjustmentPeriodic Check of Pilot and Burner Flames Cycle unit a minimum of 2 timesGAS Control and Safety System Wiring Diagram Wiring DiagramsCirculating Blower Wiring Diagram Troubleshooting Qualified Technicians Only Item # Description Cat. No Replacement Parts Model L30 DVF-2Item # Description Catalog # Model Optional AccessoriesTop View Side View Safety TestDards. Z21.88-1998 CSA 2.33a M98 Vented Gas Fireplace HeaterSafety / Listing Label Rating Plate Ownership Records Service and Maintenance LOG775,029M REV. B 08/2004

L30 DVF-2 specifications

The Lennox Hearth L30 DVF-2 is an impressive direct vent gas fireplace known for its aesthetic appeal and innovative technologies. This model stands out in the realm of residential heating solutions, combining efficiency, performance, and design into a singular unit that enhances any living space.

One of the primary features of the L30 DVF-2 is its efficient heating capacity. With a heating output of up to 30,000 BTUs, it effectively warms large areas while maintaining a steady and comfortable indoor climate. This model uses a direct vent system, allowing for clean and safe operation by taking air from the outside for combustion and expelling exhaust gases outside as well. This not only minimizes the risk of indoor air pollution but also allows for versatile installation options without the need for a traditional chimney.

In terms of design, the L30 DVF-2 offers a sleek and modern appearance, making it a stylish addition to any room. The fireplace features a large viewing area with a contemporary surround that can be customized in various finishes to match the décor of your home. Additionally, a variety of decorative options such as glass media and ceramic logs add to its aesthetic appeal, providing a beautiful flame presentation.

The Lennox L30 DVF-2 is also equipped with advanced technology, including an electronic ignition system that ensures reliable startups without requiring manual assistance. The fireplace can be conveniently controlled using a wall switch or remote control, allowing users to adjust the heat and flame settings with ease. The model is designed with a blower option that enhances heat distribution, helping to circulate warm air throughout the room more effectively.

Moreover, energy efficiency is a hallmark of the L30 DVF-2. Rated with a high Annual Fuel Utilization Efficiency (AFUE), this fireplace not only provides warmth but does so while minimizing energy consumption and utility costs. This efficiency extends the value of your investment by ensuring lower operating expenses over time.

Overall, the Lennox Hearth L30 DVF-2 combines cutting-edge technology, aesthetic versatility, and energy efficiency into a gas fireplace that offers both style and substance. It caters to modern homeowners looking to enhance their living spaces with a reliable and attractive heating solution.