Honeywell PRO22ENC2, PRO22ENC1 Dimensions, Conduit Knockouts, Power Supply, Maintenance

Page 9
Dimensions

10Installation Guide PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2

Dimensions

 

ENC1

ENC2

Height:

13.9" [0.353 m]

13.9" [0.353 m]

Width:

17" [0.4318 m]

18.9" [0.48006 m]

Depth:

9" [0.2286 m]

9" [0.2286 m]

Metal thickness: .05" [1.27 mm]

Color: Autumn White

Installation holes: Four hangers in a rectangular pattern 12.1” [0.30734 m] H x 16" [0.40640 m] W

Conduit Knockouts

 

½" [0.0127 m]

2" [0.05080 m]

Back:

9

2

Top:

9

2

Right Side:

2

1

Left Side:

2

1

Power Supply

Use PRO22E1PS or other approved power supply. (See Installation Manual for details).

Maintenance

Oil lock once per year. If battery backup is used, change battery every 2 to 2 1/2 years.

Installation Instructions

1.Measure and install four mounting screws with heads smaller than .4" [0.01016 m] using proper techniques for the material on which the PRO-2200 is being mounted. Use a rectangular screw pattern 12.1" [0.30734 m] H x 16" [0.40640 m] W. Leave the screws exposed approximately 1/2" [0.0127 m].

2.Open the door of the enclosure and place the hanging slots over the mounting screws. Push the enclosure over the mounting screws and allow the screws to slide into the slots. Finish tightening the mounting screws to securely hold the enclosure.

3.Run all appropriate wiring to the case. Mark each wire as to the panel, location and input type. All cable shields should tie to the copper grounding lug found on the bottom right of the enclosure.

4.Install the required panels into the metal runners. The PRO22E1PS should be placed in the right most location and installed according to its own instruction manual. The PRO22IC should be installed next to it as the right-most panel.

5.Wire the readers, input and output connections (see wiring guide at end of manual)

6.CHECK ALL CONNECTIONS PRIOR TO POWERING UP THE ENCLOSURE AND PANELS.

Image 9
Contents PRO-2200 Enclosure Installation Manual Part Number PRO22ENC1 PRO22ENC2TD1138 rev0801 Contents Warnings and Cautions Fire Safety and Liability NoticeBUT NOT BOTH Page Unpacking Procedure DisclaimerProduct Liability Mutual Indemnification Limited Warranty Shipping InstructionsTo ship equipment back to Engineered Systems Confidentiality Description PRO-2200EnclosurePower Supply DimensionsMaintenance Installation InstructionsInstallation Diagram Receiving Unit minimum configuration UL1076 SetupPC Minimum Requirements Peripheral Hardware RequirementsOther UL1075 Notes ProceduresA.Select Full Installation B.Select SQL for DatabaseEnterprise Manager Setup Second PC InstallationPre-RedundancyVerification DTS Package VerificationInterim Steps Before Full Redundancy Verification Redundant Test Examples Power Supply DimensionsExample #1 Example #2Power Supply Enclosure Installation DiagramDimensions Installation GuideInstallation Instructions InstallationCable Specifications ESG Cable Part Numbers PRO-2200Enclosure PRO22ENC1 & PRO22ENC2 Installation GuidePRO-2200Enclosure PRO22ENC1 & PRO22ENC2 Installation GuidePRO-2200Enclosure PRO22ENC1 & PRO22ENC2 Installation Guide2700 Blankenbaker Pkwy, Suite Louisville, KY Honeywell Security & Data Collection