16 | Installation Guide |
Redundant Test Examples
NOTE: Stop watch needed for all three test examples.
Example #1
1.Use the MAIN PC’s OFF button to shut it down. Turn on the REDUNDANT PC and start the stop watch.
2.Log into NT with Administrator rights.
3.Launch the User Interface and log in as ADMIN.
4.When the Alarm View pops up with Poll Response Normal, stop the stop watch. This time represents the amount of time that has passed since the MAIN PC went down.
Example #2
1.Unplug the power to the MAIN PC. Turn on the REDUNDANT PC and start the stop watch.
2.Log into NT with Administrator rights.
3.Launch the User Interface and log in as ADMIN.
4.When the Alarm View pops up with Poll Response Normal, stop the stop watch. This time represents the amount of time that has passed since the MAIN PC went down.
Example #3
1.Unplug the network cable from the HUB for the MAIN PC. Turn on the REDUN- DANT PC and start the stop watch.
2.Log into NT with Administrator rights.
3.Launch the User Interface and log in as ADMIN.
4.When the Alarm View pops up with Poll Response Normal, stop the stop watch. This time represents the amount of time that has passed since the MAIN PC went off line.
Power Supply Dimensions
Height: 15.5" (39.4cm)
Width: 12" (30.5cm)
Depth: 4.5" (11.43cm)
Color: Grey
Installation holes: Four hangers in a rectangular pattern 13.5" H x 9.825" W (34.3cm H x 25cm W)