Viking VFR-400 instruction manual Test Procedure Canada

Page 13

VFR-400 • 5403548 • REV D • 10/07

have activated. Pressing the SIGNAL SILENCE button changes the flashing Red Zone LED to steady on and the flashing Red Output LED mapped to that zone off unless the output is programmed as RELEASE. In addition, the Yellow ALARM/ SILENCE LED will light.

Any zone programmed as WATERFLOW is considered non-silenceable so the signal and buzzer silence buttons will have no effect on the flashing zone and output LED's. A buzzer on the annunciator sounds for any trouble condition. When the panel has a trouble or supervisory condition, pressing the SILENCE/LAMP TEST button silences the condition at the panel and all annunciators. When the panel is in a normal state, pressing the SILENCE/LAMP TEST button can be used to test the LED's.

The release panel supervises and communicates with the annunciator via separate connections for the RS-485 communication and 24VDC power requirements of the RA-4410-RC. Separate cables should be used for power and communication. Shielded cable shall be used for the communication line. Up to three annunciators can be connected to one panel. A rotary switch is provided on the panel to indicate how many annunciators are connected. Another rotary switch is on the annunciator to set the address. The annunciators must be addressed consecutively. See page 54 for wiring information. Refer to bulletin #8840024 for installation instructions and maximum wire run.

Test Procedure

The system should be inspected, tested, and maintained in accordance with NFPA-72 National Fire Alarm Code, Chapter 10 and any other requirements of the local authority having jurisdiction.

Test Procedure (Canada)

The system should be inspected, tested, and maintained in accordance with ULC Standard CAN/ULC-S536 and any other requirements of the local authority having jurisdiction.

Testing should be done as a minimum as described below:

1)Notify the fire department or other receiving station if alarm, supervisory and/or trouble signals are transmitted.

2)Notify the proper building personnel so that audible and/or visual signals can be ignored.

3)If the release panel is monitored by a building fire alarm panel, take appropriate action to eliminate any unwanted events.

4)Momentarily open each of the following circuits.

a)Each initiating device zone

b)Supervisory circuit

c)Indicating Appliance/Releasing circuit - observe that this results in a trouble condition and all indicators operate as described in the appropriate preceding section for the particular circuit that is faulted.

5)Move the PROGRAM switch down. The LCD should respond: “LOOK AT HISTORY?”. Press the FUNCTION button until the display reads PASSWORD=000. Enter password if changed from factoy or press the SET button three times. Press the FUNCTION (bottom) button until the LCD reads “SYSTEM MODE: NORMAL”. Press the SELECT button. The LCD will read “SYSTEM MODE:

ONE MAN WALKTEST”. Press the SET button then move the PROGRAM switch up. The panel will respond with “ONE MAN WALKTEST” and the time. The trouble LED will light. Any output described as “RELEASING” will automatically be disabled.

Failure to enter the walktest mode and subsequent operation of initiating zones may result in a release.

After 30 minutes of no activity in the walk test mode the panel automatically reverts to normal operation.

6)Operate each initiating device on all zones. All audible and visual alarm devices should operate for about 3 seconds. Then the system will automatically reset allowing the user to go to the next initiating device.

7)Operate each initiating device on the supervisory circuit. Observe that all the indications described in the section on supervisory conditions occur.

8)Move the PROGRAM switch down again. The LCD should respond: “LOOK AT HISTORY?”

Press the FUNCTION button until the display reads PASSWORD=000. Enter password if changed from factory or press the SET button three times.

Press the FUNCTION (bottom) button until the LCD reads: “SYSTEM MODE: ONE MAN WALKTEST”

Press the SELECT (middle) button. The LCD will read: “SYSTEM MODE: NORMAL”

Press the SET (top) button then restore the PROGRAM switch to the up position. The LCD will show the normal banner message.

9)All audible and visual indicators should be off.

10)Notify all building, fire department, and/or other receiving station personnel that the test has concluded.

Maintenance: Test batteries per local and national standards. At a minimum replace batteries every four (4) years or sooner depending on test results. The date of purchase shall be marked on all batteries.

13

Image 13
Contents VFR-400 Contents VFR-400 5403548 REV D 10/07 Operating Instructions Form Fire Alarm System LimitationsDesign Guidelines System FeaturesGeneral Description Specifications OptionsControl Buttons VFR-400 Visual IndicatorsCircuit Parameters Initiating Device ZonesInput Power Low/Missing BatteryBackup Power Requirements Dedicated Supervisory ZonesAuxiliary Power Service UseOptional Accessories Initiating Device Circuits Alarm ConditionSupervisory Low Air AlarmTrouble Conditions Notification Appliance/Releasing CircuitsLoss Or Reduction Of AC Power Ground FaultLow Battery Voltage Loss Of Auxiliary Power OutputTo Reset an Alarm or Supervisory Condition To Silence a Signaling ApplianceTo Reset a Trouble Condition Lamp TestTest Procedure Canada Test ProcedurePanel Visual Display Programming Mode InstructionsHistory Date/Time PasswordZone Disabled/Enabled VFR-400 Standard Program Information One Man WalktestNot available on Supervisory Zones Sup 1 or Sup SET OutputsSelect Function This page intentionally left blank Outputs SUP Program #1Zone Output Program #2 DWG#14165VKG PRGM2 Program #3 DWG# 14166 VKG PRGM3 Program #4 DWG# 14167 VKG PRGM4 Program #5 DWG# 14168 VKG PRGM5 Firecycle Program #6DWG# 14169 VKG PRGM6 Program #7 DWG# 14171 VKG PRGM7 Program #8 DWG# 14171 VKG PRGM8 Program #9 DWG# 14172 VKG PRGM9 Program #10 DWG# 14173 VKG PRGM10 Program #11 DWG# 14175 VKG PRGM11 Program #12 DWG#14178 VKG PRGM12 Custom Program Zones SUP Outputs Initiating Zone Description VFR-400 Custom Program InformationSET Select Function Soak Timer Description Normal/Cross-Zoning Custom Message Installation Instructions Alarm Zones Supervisory ZonesVFR-400 False Front Removal/Assembly Drawing Wire CheckoutMounting Instructions Battery Size Requirements And Maintenance Battery Size CalculationsInactive Circuits Current Requirements Secondary Power Supply RequirementsCalculation Table Typical 2 Wire Detector Connection Drawing Typical Firecycle WiringTypical Style B Class B Wiring Using SB-46 Base Typical Style D Class a WiringIdentifier a Detection Systems Max. No. Of Detectors Per Zone Is Releasing Device Compatibility Wire Routing for VFR-400NEC -54. Installation of Conductors and Equipment Panel Panel

VFR-400 specifications

The Viking VFR-400 is a light sport aircraft that has garnered attention for its innovative design and advanced technology. This aircraft is known for its versatility, performance, and safety features, making it a suitable choice for both recreational flying and pilot training.

One of the standout features of the VFR-400 is its efficient aircraft structure. Constructed primarily of high-strength composite materials, the VFR-400 boasts a lightweight yet durable frame. This not only enhances its aerodynamics but also contributes to increased fuel efficiency. The aircraft is powered by a reliable Rotax engine, which is well-regarded in the aviation community for its exceptional performance and low operational costs.

The VFR-400 is equipped with a low-wing design, which is optimized for stability and maneuverability. Pilots appreciate the responsive handling characteristics, which make it an enjoyable aircraft to fly, whether on short excursions or longer journeys. The spacious cabin design offers ample room for two occupants, ensuring comfort during flights. Large cockpit glass provides excellent visibility during takeoff and landing, critical times when situational awareness is paramount.

In terms of avionics, the VFR-400 features advanced electronic systems, including a modern glass cockpit display. This integration of technology provides pilots with real-time flight data, ensuring better navigation and situational awareness. Moreover, the aircraft often comes equipped with autopilot features, enhancing the flying experience, especially on longer flights.

Safety is a key aspect of the VFR-400 design. It incorporates redundant control systems, advanced braking systems, and robust structural integrity to withstand various in-flight scenarios. The landing gear is designed for easy maintenance and reliability, allowing for smooth landings on various surface types.

The VFR-400 is designed with fuel efficiency in mind, allowing for longer flight durations while keeping operational costs low. Its impressive range and payload capacity make it a highly flexible option for different mission profiles, from pilot training to leisurely flights.

Overall, the Viking VFR-400 exemplifies the spirit of modern aviation with its combination of performance, safety, and comfort. It stands out in the light sport aircraft category for its thoughtful engineering and commitment to delivering a quality flying experience. Whether for a seasoned aviator or someone new to flying, the VFR-400 offers a compelling platform for exploration and adventure in the skies.