Kenmore 153.331492, 153.331592 owner manual All Air from Outdoors, Louvers and Grilles

Page 17

gasutilizationequipmentintheareaIfyouareunsurethatthe.

structuremeetsthisrequirement,contactyourlocalgasutility

companyorotherqualifiedagencyforasafetyinspection.

Eachofthetwoopeningsshallhaveaminimumfreeareaof1

squareinchper1,000BTUHofthetotalinputratingofallgas

utilizationequipmentintheconfinedarea,butnotlessthan100 squareinches(Figure13).

CONFINED

SPACE

PERMANENT

OPENINGS

INCH/1000

BTUH

(MINIMUM

_100SQUARE. IN.)

TABLE 3

Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only.

Based on total BTUH input rating for all utilizing equipment within the confined space.

 

 

Minimum Free

Area

Reference

Opening

Source

Per Opening (sq. in.)

Drawing

*Direct to outdoors

1 sq. in, per 4000

BTUH

Figure

14

Vertical

Ducts

1 sq. in, per 4000

BTUH

Figure

15

Horizontal

Ducts

1 sq. in, per 2000

BTUH

Figure

16

Single Opening

1 sq. in, per 3000

BTUH

Figure

17

Example: A water heater with an input rating of 50,000 BTUH using horizontal ducts would require each opening to have a minimum free area of 25 square inches.

Minimum free area = 50,000 BTUH x 1 sq. in. ! 2000 BTUH = 25 sq. in.

*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through an outside walt.

Consult the local codes of your area for specific ventilation and combustion air requirements.

FIGURE 13.

All Air from Outdoors

Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside.

Ductwork must be of the same cross-sectional area as the free area of the opening to which they connect. The minimum

dimension of rectangular air ducts cannot be less than three inches.

The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 3 to calculate the minimum free area for each opening. Figures 14, 15, 16 and 17 are typical examples of each method.

GABLE VENT

j TO OUTDOORS

INSTALLABOVE

INSULATION

CONFINED

AIR TO

ATTIC 1 SQ.

INCH PER

4000 BTUH

ALTERNATE

INLET AIR FROM

AIR INLET

 

1 SQ.

INCH

PER

 

 

OPEN

 

4000

BTUH

 

 

FOUNDATION

'_

 

 

 

 

 

VENT

 

ALL

AIR

FROM

OUTDOORS:

INLET

AIR FROM VENTILATED

CRAWL

SPACE/OUTLET

AIR TO

VENTILATED

ATTIC

FIGURE 14.

Louvers and Grilles

In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 114" mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area.

Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation.

Keep louvers and grilles clean and free of debris or other obstructions.

,GABLE VENT TO OUTDOORS

• INSTALL ABOVE INSULATION

-.-,...

OUTLET AIR

1SQ. INCH

PER4000

BTUH

INLET AIR DUCT

1 SQ. INCH PER

4000 BTUH

12" MAXIMUM

ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC

FIGURE 15.

17

Image 17 Contents
=iI=1,Ctd,,,it= 153.331492 Gallon 153.331592Important Definitions Read and follow water heater warnings and instructionsFire Hazard Improper installation and use may result in property damageFire or Explosion Harzard GAS Supply Troubleshootingguide Year Limited Warranty on Water Heater Important Information About This Water Heater Excessive Weight HazardMaterials Needed Vent Pipe Inner Door Gas Control GET to Know Your Water Heater GAS ModelsInstallation Checklist Manualgas SHUT-OFFVALVE Removing the Old Water HeaterCSite Location Location RequirementsCarbon Monoxide Poisoning Hazard Fire or Explosion Hazard Insulation Blankets Clearances and Accessibility Property Damage Hazard Breathing Hazard Carbon Monoxide GasGas Requirements Filling the Water HeaterGas Piping Explosion HazardGas Pressure Gas Pressure TestingUnconfined Space Carbon Monoxide WarningAll Air from Inside the Building Confined SpaceLouvers and Grilles All Air from OutdoorsVent Connectors Draft Hood InstallationVent Pipe Size Vent Pipe SystemVertical Exhaust Gas Vent Chimney ConnectionTvALvE Piping InstallationTemperature & Pressure Relief Valve Temperature and Pressure Relief ValveClosed System/Thermal Expansion Explosion HarzardWhat to do if YOU Smell GAS Lighting InstructionsChecking the Draft Water Temperature RegulationBurner Flames Emergency Shut DownGascontroutemperatureknob Vent System Inspection Tank Sediment CleaningBurner Inspection Caon Monoxide and Fire HazardHousekeeping Temperature-Pressure Relief Valve OperationAnode Rod Inspection Draining and FlushingService Full Assembly Electronic Control Module External Inspection & Cleaning Base-Ring Filter Replacement PartsRemoving the Burner from the Manifold Burner Assembly Removing the Manifold/Burner AssemblyExplosion Hazard Cleaning the Combustion Chamber and Flame-arrestorPiezoelectric Igniter System Expansion Tank Sizing Chart Expansion Tank SpecificationsStart Up Conditions Strange SoundsOperational Conditions Page Problemled Status Problem Page Page Page Page Page