gasutilizationequipmentintheareaIfyouareunsurethatthe.
structuremeetsthisrequirement,contactyourlocalgasutility
companyorotherqualifiedagencyforasafetyinspection.
Eachofthetwoopeningsshallhaveaminimumfreeareaof1
squareinchper1,000BTUHofthetotalinputratingofallgas
utilizationequipmentintheconfinedarea,butnotlessthan100 squareinches(Figure13).
CONFINED
SPACE
PERMANENT
OPENINGS
INCH/1000
BTUH
(MINIMUM
_100SQUARE. IN.)
TABLE 3
Minimum Free Area of Permanent Openings for Ventilation and Combustion Air Supply - All Air from Outdoors Only.
Based on total BTUH input rating for all utilizing equipment within the confined space.
|
| Minimum Free | Area | Reference | |
Opening | Source | Per Opening (sq. in.) | Drawing | ||
*Direct to outdoors | 1 sq. in, per 4000 | BTUH | Figure | 14 | |
Vertical | Ducts | 1 sq. in, per 4000 | BTUH | Figure | 15 |
Horizontal | Ducts | 1 sq. in, per 2000 | BTUH | Figure | 16 |
Single Opening | 1 sq. in, per 3000 | BTUH | Figure | 17 |
Example: A water heater with an input rating of 50,000 BTUH using horizontal ducts would require each opening to have a minimum free area of 25 square inches.
Minimum free area = 50,000 BTUH x 1 sq. in. ! 2000 BTUH = 25 sq. in.
*These openings connect directly with the outdoors through a ventilated attic, a ventilated crawl space, or through an outside walt.
Consult the local codes of your area for specific ventilation and combustion air requirements.
FIGURE 13.
All Air from Outdoors
Outdoor fresh air can be provided to a confined area either directly or by the use of vertical and horizontal ducts. The fresh air can be taken from the outdoors or from crawl or attic spaces that freely communicate with the outdoors. Attic or crawl spaces cannot be closed and must be properly ventilated to the outside.
Ductwork must be of the same
dimension of rectangular air ducts cannot be less than three inches.
The size of each of the two openings is determined by the method in which the air is to be provided. Refer to Table 3 to calculate the minimum free area for each opening. Figures 14, 15, 16 and 17 are typical examples of each method.
GABLE VENT
j TO OUTDOORS
INSTALLABOVE
INSULATION
CONFINED
AIR TO
ATTIC 1 SQ.
INCH PER
4000 BTUH
ALTERNATE | INLET AIR FROM |
AIR INLET |
|
1 SQ. | INCH | PER |
|
| OPEN |
|
4000 | BTUH |
|
| FOUNDATION | '_ | |
|
|
|
|
| VENT |
|
ALL | AIR | FROM | OUTDOORS: | INLET | AIR FROM VENTILATED | |
CRAWL | SPACE/OUTLET | AIR TO | VENTILATED | ATTIC |
FIGURE 14.
Louvers and Grilles
In calculating free area for ventilation and combustion air supply openings, consideration must be given to the blocking effect of protection louvers, grilles, and screens. These devices can reduce airflow, which in turn may require larger openings to achieve the required minimum free area. Screens must not be smaller than 114" mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the specified free area of the opening. If the design and free area are not known, it can be assumed that most wood louvers will allow 20 - 25% of free area while metal louvers and grilles will allow 60 - 75% of free area.
Louvers and grilles must be locked open or interconnected with the equipment so that they are opened automatically during equipment operation.
Keep louvers and grilles clean and free of debris or other obstructions.
,GABLE VENT TO OUTDOORS
• INSTALL ABOVE INSULATION
OUTLET AIR
1SQ. INCH
PER4000
BTUH
INLET AIR DUCT
1 SQ. INCH PER
4000 BTUH
12" MAXIMUM
ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC
FIGURE 15.
17