Kenmore 153.331572 owner manual Chimney Connection, Vertical Exhaust Gas Vent

Page 19

The vent connector must be accessible for cleaning, inspection, and replacement.

Vent connectors cannot pass through any ceiling, floor, firewall, or fire partition.

It is recommended (but not mandatory) that a minimum 12 inches of vertical vent pipe be installed on the draft hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for obstructions, corrosion, and proper installation.

Chimney Connection

IMPORTANT: Before connecting a vent to a chimney, make sure the chimney passageway is clear and free of obstructions. The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces. Also consult local and state codes for proper chimney sizing and application or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.

The connector must be installed above the extreme bottom

 

of the chimney to prevent potentially blocking the flue

 

gases.

The connector must be firmly attached and sealed to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

separation, and maintain clearances to combustible materials (Figures 20 and 21).

IMPORTANT: This gas vent must be terminated in a vertical position to facilitate the removal of the burnt gases.

An unused chimney flue or masonry enclosure may be used as a passageway for the installation of a gas vent (Figure 21).

Common (combined) venting is allowable with vertical type B vent systems and lined masonry chimneys as long as proper draft for the water heater is established under all conditions of operation. CAUTION: DO NOT common vent this water heater with any power vented appliance.

Figures 19-21 are examples of vent pipe system installations and may or may not be typical for your specific application. Consult the “National Fuel Gas Code”, NFPA 54, ANSI Z223.1- current edition and the guidelines set forth by prevailing local codes.

LISTED VENT CAP

 

2 FT. MINIMUM ABOVE ANY OBJECT

3 FT. MINIMUM

WITHIN 10 FT. HORIZONTALLY

SUPPORT

STRAP

 

prevent it from falling out.

To aid in removing the connector, a thimble or slip joint may

 

be used.

The connector must not extend beyond the inner edge of

 

the chimney as it may restrict the space between it and the

 

opposite wall of the chimney (Figure 19).

LISTED LINED

CHIMNEY

*MAINTAIN CLEARANCE

VENT

CONNECTOR

SLOPE UP

1/4 IN. PER FT.

MINIMUM

TYPE B DOUBLE WALL VENT PIPE

**MAINTAIN

SPECIFIED CLEARANCE

 

2 FT. MINIMUM ABOVE ANY OBJECT

3 FT. MINIMUM

WITHIN 10FT. HORIZONTALLY

SUPPORT

STRAP

VERTICAL GAS VENT SYSTEM WITH

TYPE B DOUBLE WALL VENT PIPE.

FIGURE 20.

MAINTAIN

CLEARANCE*

SEAL

SLOPE

UP 1/4 IN.

PER FT.

MINIMUM

DO NOT EXTEND VENT BEYOND EDGE OF CHIMNEY

VENT

CONNECTOR

 

LISTED VENT CAP

 

5 FT. MINIMUM

 

**MAINTAIN

 

SPECIFIED

 

CLEARANCE

SUPPORT

 

STRAP

 

*MAINTAIN

 

CLEARANCE

SEAL

 

CHIMNEY TERMINATION VENT SYSTEM

FIGURE 19.

Do not terminate the vent connector in a chimney that has not been certified for this purpose. Some local codes may prohibit the termination of vent connectors in a masonry chimney.

Vertical Exhaust Gas Vent

Vertical exhaust gas vents must be installed with U.L. listed type B vent pipe according to the vent manufacturer’s instructions and the terms of its listing.

It must be connected to the water heater’s draft hood by a listed vent connector or by directly originating at the draft hood opening.

Vertical gas vents must terminate with a listed cap or other roof assembly and be installed according to their manufacturer’s instructions.

Gas vents must be supported to prevent damage, joint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

UNUSED CHIMNEY

SLOPE UP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLUE OR MASONRY

1/4 IN. PER FT.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ENCLOSURE

MINIMUM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VENTING THROUGH A CHIMNEY WITH

TYPE B DOUBLE WALL VENT PIPE.

FIGURE 21.

*Maintain vent pipe clearance requirements to local, state and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition.

**NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances states that these chimneys are intended to be installed in accordance with the installation instructions provided with each chimney support assembly. Minimum air space clearance to combustible materials should be maintained as marked on the chimney sections.

19

Image 19
Contents Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A Power Miser GAS Water HeaterSafety Precautions Safe INSTALLATION, USE and ServiceFire or Explosion Harzard Table of Contents Troubleshooting Guide Year Limited Warranty on Water Heater Product WarrantyCustomer Responsibilities Product SpecificationsMaterials Needed Materials and Basic Tools NeededGET to Know Your Water Heater GAS Models Typical InstallationImportant Information about this Water Heater Installation ChecklistRemoving the Old Water Heater Installation InstructionsSite Location Location RequirementsInsulation Blankets Clearances and AccessibilityGas Piping Filling the Water HeaterGAS Supply Gas RequirementsGas Pressure Gas Pressure TestingLP Gas Only Unconfined Space Combustion AIR Supply & VentilationAll Air from Inside the Building Louvers and Grilles All Air from OutdoorsVent Pipe Size Draft Hood InstallationVent Connectors Vent Pipe SystemVertical Exhaust Gas Vent Chimney ConnectionWater System Piping Piping InstallationClosed System/Thermal Expansion Temperature and Pressure Relief ValveLighting Instructions Operating Your Water HeaterBurner Flames Checking the Draft Water Temperature RegulationEmergency Shut Down White Rodgers GAS Valve GAS Control Knob OFF-PILOT-ON Vent System Inspection Burner Inspection Service and AdjustmentTank Sediment Cleaning Burner CleaningDraining and Flushing Temperature-Pressure Relief Valve OperationHousekeeping Anode Rod InspectionService Maintenance of Your Water Heater Cleaning the Combustion Chamber and Flame-arrestor Replacing the Pilot/ Pilot Tube AssemblyPiezoelectric Igniter System Replacing the Manifold/Burner AssemblyFvir System Operational Checklist Testing the Igniter SystemRemoving and Replacing the Gas Control Valve/Thermostat Start Up Conditions Troubleshooting GuideCondensation Operational ConditionsLeakage Checkpoints Problem Possible Causes Corrective Action Troubleshooting ChartThermostat Fails to YES Pilot Light Troubleshooting FlowchartModel Numbers Parts Order ListPage MY-HOME1-800-469-4663 Get it fixed, at your home or ours