Kenmore 153.331572 Draft Hood Installation, Vent Pipe System, Vent Pipe Size, Vent Connectors

Page 18

 

1 SQ. INCH PER

 

2000 BTUH

CONFINED

OUTLET

 

SPACE

 

 

OUTDOOR

 

AIR DUCTS

using the manufacturer’s instructions and local codes, rules, or regulations.

IMPORTANT: If you lack the necessary skills required to properly install this venting system, you should not proceed, but get help from a qualified technician.

Draft Hood Installation

SHEET METAL SCREWS (FOUR PROVIDED)

INLET

LEGS

DRAFT HOOD

1 SQ. INCH PER

2000 BTUH

ALL AIR FROM OUTDOORS USING HORIZONTAL DUCTS

FIGURE 16.

 

ALTERNATIVE

 

OPENING

 

LOCATION

CONFINED

1 SQ. INCH

PER 3000 BTUH

SPACE

 

ALL AIR FROM OUTDOORS - USING A SINGLE PERMANENT OPENING

FIGURE 17.

Vent Pipe System

This water heater uses a non-direct, single-pipe vent system to remove exhaust gases created by the burning of fossil fuels. Air for combustion is taken from the immediate water heater location or is ducted in from the outside (see “Combustion Air Supply and Ventilation”).

This water heater must be properly vented for the removal of exhaust gases to the outside atmosphere. Correct installation of the vent pipe system is mandatory for the proper and efficient operation of this water heater and is an important factor in the life of the unit.

The vent pipe must be installed according to all local and state codes or, in the absence of local and state codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 54)-current edition. The vent pipe installation must not be obstructed so as to prevent the removal of exhaust gases to the outside atmosphere.

IMPORTANT: The use of vent dampers is not recommended by the manufacturer of this water heater. Although some vent dampers are certified by CSA International, this certification applies to the vent damper device only and does not mean they are certified for use on this water heater.

U.L. recognized fuel gas and carbon monoxide (CO) detectors are recommended in all applications and should be installed

18

LEGS

SLOT

SLOT

 

JACKET TOP

INSTALL THE DRAFT HOOD WITH

THE FOUR SCREWS PROVIDED.

FIGURE 18.

Align the legs of the draft hood with the slots provided. Insert the legs and secure the draft hood to the water heater’s top with the four screws provided as shown in Figure 18. Do not alter the draft hood in any way. If you are replacing an existing water heater, be sure to use the draft hood supplied with this water heater.

Vent Pipe Size

It is important that you follow the guidelines in these instructions for sizing a vent pipe system. If a transition to a larger vent size is required, the vent transition connection must be made at the draft hood outlet.

Vent Connectors

1.Type B, Double wall, U.L. Listed Vent Pipe.

2.Single wall Vent Pipe.

Maintain the manufacturer’s specified minimum clearance from combustible materials when using type B double wall vent pipe.

Vent connectors made of type B, double wall vent pipe material may pass through walls or partitions constructed of combustible material if the minimum listed clearance is maintained.

Maintain a six inch minimum clearance from all combustible materials when using single wall vent pipe.

IMPORTANT: Single wall vent pipe cannot be used for water heaters located in attics and may not pass through attic spaces, crawl spaces or any confined or inaccessible location. A single wall metal vent connector cannot pass through any interior wall.

When installing a vent connector, please note the following (See Figures 19-21):

Install the vent connector avoiding unnecessary bends, which create resistance to the flow of vent gases.

Install without dips or sags with an upward slope of at least 1/4-inch per foot.

Joints must be fastened by sheet metal screws or other approved means. It must be supported to maintain clearances and prevent separation of joints and damage.

The length of the vent connector cannot exceed 75% of the vertical vent height.

Image 18
Contents Power Miser GAS Water Heater Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.ASafe INSTALLATION, USE and Service Safety PrecautionsFire or Explosion Harzard Table of Contents Troubleshooting Guide Product Warranty Year Limited Warranty on Water HeaterProduct Specifications Customer ResponsibilitiesMaterials and Basic Tools Needed Materials NeededTypical Installation GET to Know Your Water Heater GAS ModelsInstallation Checklist Important Information about this Water HeaterInstallation Instructions Removing the Old Water HeaterLocation Requirements Site LocationClearances and Accessibility Insulation BlanketsGas Requirements Filling the Water HeaterGAS Supply Gas PipingGas Pressure Testing Gas PressureLP Gas Only Combustion AIR Supply & Ventilation Unconfined SpaceAll Air from Inside the Building All Air from Outdoors Louvers and GrillesVent Pipe System Draft Hood InstallationVent Connectors Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingTemperature and Pressure Relief Valve Closed System/Thermal ExpansionOperating Your Water Heater Lighting InstructionsChecking the Draft Water Temperature Regulation Burner FlamesEmergency Shut Down White Rodgers GAS Valve GAS Control Knob OFF-PILOT-ON Burner Cleaning Service and AdjustmentTank Sediment Cleaning Vent System Inspection Burner InspectionAnode Rod Inspection Temperature-Pressure Relief Valve OperationHousekeeping Draining and FlushingService Maintenance of Your Water Heater Replacing the Pilot/ Pilot Tube Assembly Cleaning the Combustion Chamber and Flame-arrestorReplacing the Manifold/Burner Assembly Piezoelectric Igniter SystemTesting the Igniter System Fvir System Operational ChecklistRemoving and Replacing the Gas Control Valve/Thermostat Troubleshooting Guide Start Up ConditionsOperational Conditions CondensationLeakage Checkpoints Troubleshooting Chart Problem Possible Causes Corrective ActionThermostat Fails to Pilot Light Troubleshooting Flowchart YESParts Order List Model NumbersPage Get it fixed, at your home or ours MY-HOME1-800-469-4663