Kenmore 153.33385 owner manual Venting, Draft Hood Installation

Page 15

To fill the water heater with water:

1.Close the water heater drain valve by turning the handle to the right (clockwise). The drain valve is on the lower front of the water heater.

2.Open the cold water supply valve to the water heater.

NOTE: The cold water supply valve must be left open when the water heater is in use.

3.To insure complete filling of the tank, allow air to exit by opening the nearest hot water faucet. Allow water to run until a constant flow is obtained. This will let air out of the water heater and the piping.

4.Check all water piping and connections for leaks. Repair as needed.

VENTING

Place the draft hood legs in the receiving holes on the top of the water heater. The legs will snap in the holes to give a tight fit.

Place the vent pipe over the draft hood. With the vent pipe in position, drill a small hole through both the vent pipe and draft hood. Secure them together with a sheet metal screw.

DRAFT HOOD INSTALLATION

FIGURE 14.

VENT DAMPERS - Any vent damper, whether it is operated thermally or otherwise must be removed if its use inhibits proper drafting of the water heater.

Thermally Operated Vent Dampers: Gas-fired water heaters having thermal efficiency in excess of 80% may produce a relatively low flue gas

temperature. Such temperatures may not be high enough to properly open thermally operated vent dampers. This would cause spillage of the flue gases and may cause carbon monoxide poisoning.

Vent dampers must bear evidence of certification as complying with the current edition of the American National Standard ANSI Z21.68 (ANSI Z21.66 & 67, respectively, cover electrically and mechanically actuated vent dampers). Before installation of any vent damper, consult the local gas utility for further information.

To insure proper venting of this gas-fired water heater, the correct vent pipe diameter must be utilized. Any additions or deletions of other gas appliances on a common vent with this water heater may adversely affect the operation of the water heater. Consult your gas supplier if any such changes are planned.

Periodically check the venting system for signs of obstruction or deterioration and replace if needed.

The combustion and ventilation air flow must not be obstructed.

The water heater with draft hood installed must be connected to a roof jack, which terminates to the outdoors. Never operate the water heater unless it is vented to the outdoors and has adequate air supply to avoid risks of improper operation, explosion or asphyxiation.

Obstructed or deteriorated vent systems may present serious health risk or asphyxiation.

The vent pipe from the water heater must be no less than the diameter of the draft hood outlet on the water heater.

All vent gases must be completely vented to the outdoors of the structure (dwelling). Install only the draft hood provided with the new water heater and no other draft hood.

Vent pipes must be secured at each joint with sheet metal screws.

There must be a minimum of 6 inches (153 mm) clearance between single wall vent pipe and any combustible material. For other than single wall, follow vent pipe manufacturer’s clearance specifications.

Failure to have required clearances between vent piping and combustible material will result in a fire hazard.

The water heater must be connected to a roof jack: The vent pipe from the water heater to the roof jack must be no less than the diameter of the draft hood outlet (min. 3” [76 mm]) on the water heater.

This water heater may be installed with single wall or Type B vent pipe connection to the draft hood and the following U.L. listed roof jacks not furnished.

Van Dyke Ind. No. 987

Vent Line No. 2073

White Metal Products 3RJ

There must be a minimum clearance of 12” (305 mm) between the top of the draft hood and the top of the enclosure.

The draft hood and combustion air inlet to the water heater must be in the same atmospheric pressure zone. Do not separate by a wall, shelf, ceiling, partition, or any other means.

There must be a minimum of 6 inch clearance between single wall vent pipe and any combustible material. Fill and seal any clearance between single wall vent pipe and combustible material with mortar mix, cement or other noncombustible substance. For other than single wall, follow vent pipe manufacturer’s clearance specifications.

Be sure vent pipe is properly connected to prevent escape of dangerous flue gases which could cause deadly asphyxiation.

15

Image 15
Contents Economizer GAS Water Heater Important Definitions Safe INSTALLATION, USE and ServiceGeneral Safety Table of Contents Product Specifications Preparing for the InstallationCustomer Responsibilities Materials Needed Materials and Basic Tools NeededALL Piping Materials to be Supplied by Customers Install PERGET to Know Your Water Heater ReliefRemoving the OLD Water Heater Installation InstructionsHotter Water can Scald Typical InstallationsFacts to Consider about the Location Locating the NEW Water HeaterInsulation Blankets Installing the NEW Water Heater Securing Water Heater to Floor and Wall Water PipingValve and Pipe Insulation TEMPERATURE-PRESSURE Relief Valve Water Piping Pressure TestOr Property Damage Filling the Water Heater Venting Draft Hood InstallationGAS Piping Alternative Sediment Trap Location Sediment TrapsPage Page Operating Instructions Before Lighting the Pilot Installation ChecklistSetting Temperature RegulationBurner Inspection Service and AdjustmentBurner Cleaning Venting System InspectionTEMPERATURE-PRESSURE Relief Valve Operation Anode ROD InspectionDraining Service Drain Valve Washer ReplacementStart UP Conditions Troubleshooting GuideCondensation Operational ConditionsLeakage Checkpoints Troubleshooting Guidelines Parts Order List Burner AssemblyPage Sears Installation Service Year Limited Warranty on Water HeaterYear Exclusive Kenmore Labor Warranty Warranty Service