New Buck Corporation FP-BR-10-ZC manual Ventilation Air From Inside Building

Page 18
VENTILATION AIR

A.Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See “Ventilation Air From Inside Building”, page 21.

B.Vent room directly to the outdoors. See “Ventilation Air From Outdoors”, page 22.

C.Install a lower BTU/Hr heater, if lower BTU/Hr size makes room unconfined.

If the actual BTU/Hr used is less than the maximum BTU/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

VENTILATION AIR

VENTILATION AIR FROM INSIDE BUILDING

This fresh air would come from an adjoining unconfined space. When venting to an adjoining space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces. (See Options 1 and 2, Figure 7.) You can also remove door into adjoining room. (See Option 3, Figure 7.)

NOTE: Each opening shall have a minimum free area of 1 square inch per 1000 BTU’s per hour of the total input ratings of all gas utilization equipment in the confined space, but not less than 100 square inches.

Figure 7 Ventilation Air From Inside Building

Page 16

Image 18
Contents Manufacturer NEW BUCK CORPORATION MODEL FP-BR-10-ZC VENT-FREEMarch P.O. Box 69 8000 Highway 226 SouthPage TABLE OF CONTENTS Page Page Page Page GAS LINES INSTALLATIONCHOOSING THE LOCATION FOR YOUR FIREPLACE DRAFTS1/8” 11 5/8”1/8” 25 1/8” 24” 1 3/4” 25 1/8”Install the Firebox INSTALLING THE FIREBOXFIREPLACE CLEARANCES 17-3/4SIDE WALL FINISHING YOUR FIREPLACECLEARANCES 7 MINof Unit if mantel is 10 wide or more MANTEL PROFILES FOR ZERO CLEARANCE CABINETMUST BE FOLLOWED if mantel is 12 wide or lessNOTE See page 18 for “Gas Pressure Check” MANTEL BASE 1/2 WOOD SCREWSTOP MANTEL REARINSTALLATION AFTER-MARKETMOBILE HOMES GAS CONNECTIONFLAME PRODUCING ADEQUATE VENTILATION DETERMINING FRESH-AIRFLOW FOR HEATER LOCATION VENTILATION AIR VENTILATION AIR FROM INSIDE BUILDINGOutlet Air VENTILATION AIR FROM OUTDOORSVentilated Attic Outlet Air To AtticGAS PRESSURE CHECK Front View of Logs LOG PLACEMENTLogs are shipped secured in unit PageOPERATING INSTRUCTIONS Page Page Page FLAME CHECK FLAME NATURAL PROPANEMOTOR WIRING DIAGRAMPOWER CORD JUMPERTHERMOSTATNOTE #PESBRO84 Blower Motor Rating 120 volts/60HZ/0.54 Amps. 1 P.HPage IMPORTANT SAFEGUARDS CLEANINGSOLUTION TROUBLESHOOTINGPROBLEM OBSERVEDDepleted gas supply 6. Burner backfiring during WARNING above Important aboveWARNING above WARNING aboveREPAIR PARTS SERVICINGPARTS LIST Maxitrol ValveBLOWN UP VIEW OF BURNER ASSEMBLY PageLIMITED WARRANTY MODEL FP-BR10-ZC NEW BUCK CORPORATIONPage