New Buck Corporation 1110 manual Gas Pressure Check

Page 22
GAS PRESSURE CHECK

GAS PRESSURE CHECK

Check the inlet pressure to the burner to insure that it is as shown in the table below.

NOTE: The pressure check point is located on the right side of the valve facing burner.

The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5kPa).

The appliance must be isolated from the gas supply piping system by closing its equipment shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).

MODEL

1110

1110

Gas

Natural

Propane

Maximum Heat Input

10000

10000

Gas Inlet Pressure:

 

 

Maximum

10.5 ins. W.C.

13 ins. W.C.

Minimum

* 5 ins. W.C.

*11 ins. W.C.

Manifold Pressure

3.5 ins. W.C.

9 ins. W.C.

NOTE: On initial installation it may be necessary to bleed out air in the gas lines. Do this by holding the control knob and turning the knob to the pilot position for about 30 seconds.

To check the Regulator pressure, remove the pressure tag plug at the left side of the Regulator facing the heater. The pressure should be checked with the heater burning and the control set on high. After measuring the pressure, replace the pressure tap plug,ensuring that there are no leaks.

* For the purpose of minimum input adjustment.

Figure 12

20

Image 22
Contents Manufacturer NEW BUCK CORPORATION P.O. Box NEW BUCK CORPORATIONMODEL 1110 VENT-FREEGAS HEATER 8000 Highway 226 South Spruce Pine, NCPage TABLE OF CONTENTS Page SAFETY INFORMATION WARNINGS Do not try to light any appliance 22.”WARNING Failure to keep the primary air openings of the burners clean may result in sooting and property damage.” PRODUCT IDENTIFICATION SAFETY DEVICE PRODUCT FEATURESUNPACKING PIEZO IGNITION SYSTEMMINIMUM CLEARANCES TO COMBUSTIBLE CONSTRUCTION 2.Freestanding heater with optional pedestal INSTALLATION1.Wall Mounted 3.Freestanding with optional wooden mantelCLEANING INFORMATION FREESTANDING WITH OPTIONAL PEDESTAL INSTALLATION FREESTANDING OPTIONAL WOODEN MANTEL INSTALLATIONOPTIONAL “L” BRACKETS 2 AND SCREWS 2 PRO PRODUCING ADEQUATE VENTILATION DETERMINING FRESH-AIRFLOW FOR HEATER LOCATIONVent-freeheater VENTILATION AIR VENTILATION AIR FROM INSIDE BUILDINGVENTILATION AIR FROM OUTDOORS GAS CONNECTION FLAMEPropane Supply Tank CONNECTING TO A GAS SUPPLYExternal Regulator Vent Pointing Down Installation must include manual shutoff valve and plugged 1/2 NPT tap. Locate NPT tap within reach for test gauge hook-up.NPT tap must be upstream from unit GAS PRESSURE CHECK Logs are shipped secured in unit LOG PLACEMENT FORFront View of Logs LIGHTING INSTRUCTIONS MODULATING VALVEMAXITROL FOR YOUR SAFETY, READ BEFORE LIGHTINGOPERATING INSTRUCTIONS for “LOW” LIGHTING INSTRUCTIONSto IGNITE and for “HIGH”IGNITER ELECTRODE THERMO-COUPLE TO TURN OFF GAS TO APPLIANCEO.D.S PILOT BURNER MANUAL LIGHTING PROCEDURE THERMOSTAT CONTROL OPERATIONNATURAL FLAME CHECKFLAME PROPANEFigure 1815 - Correct Burner Flame Pattern BURNER FLAME PATTERNCORRECT FLAME PATTERN AT HIGH POSITION INCORRECT FLAME PATTERN AT HIGH POSITIONMOTOR WIRING DIAGRAMPOWER CORD JUMPERTHERMOSTATREPAIR PARTS SERVICINGIMPORTANT SAFEGUARDS CLEANINGTROUBLE-SHOOTING OBSERVED PROBLEMSOLUTION POSSIBLE1.Control knob is not fully pressed in Delayed ignition of burner 1. Heater produces a clinking MODEL TECHNICAL SERVICEMODULATING VALVE PARTS LIST BLOWN UP VIEW OF HEATER, FAN MOTOR, AND ALL REMOVABLE PARTSPARTS LIST Maxitrol ValveBLOWN UP VIEW OF BURNER ASSEMBLY LIMITED WARRANTY ON VENT-FREEGAS LOG HEATER NEW BUCK CORPORATION