Roberts Gorden 10081601NA Rev H 12/11 service manual Commissioning the Corayvac System

Page 50

ROBERTS GORDON® ULTRAVAC™ CONTROLLER INSTALLATION MANUAL

SECTION 8: COMMISSIONING THE CORAYVAC® SYSTEM

NOTE: The ROBERTS GORDON® ULTRAVAC™ software must be installed on the PC, the communi- cation connection must be made to the controller and all wiring of the ROBERTS GORDON® ULTRAVAC™ control boards, relay boards, burners, pumps and VFD must be completed before starting the commis- sioning procedure.

8.1 Setting The CORAYVAC® End Burner Vacuum

It is important to understand that the frequency that the VFD runs the motor at, determines the speed of the impeller in the pump. Variation of the impeller speed will increase or decrease vacuum in the sys- tem. The following procedure will help you set mini- mum and maximum VFD frequency settings to achieve proper vacuum in the system.

Step 8.1.1 At the controller, turn on the 24 V power switch on the relay board. At the PC, "connect" to the controller (see the ROBERTS GORDON® ULTRAVAC™ Software Installation and Operation Manual, P/N 10081600NA for details) and then open the manual override screen(Alt + M). On the screen, click the "ON" button for the vacuum pump. Wait 30 seconds then click the ON button for zones 1- 3.

Step 8.1.2 The pump should be running and the

burners should light within 60 seconds. At the VFD, verify that the number displayed on the LCD screen is "60.0" If it is lower than 60.0, hit the "up" arrow but- ton on the VFD until the number reads 60.0 Let the burners fire for approximately 20-30 minutes to warm up the system. Using a manometer, check the end vent vacuum in each zone (each branch of burners). See Page 45, Figure 26.

If the lowest end vent vacuum reading is above 3.0" wc, reduce the vacuum pump speed. Generally, the lowest end vent vacuum reading is on the longest branch of the system. Use the down arrow button on the VFD to reduce the frequency of the output signal to the pump, thus reducing the pump speed and low- ering the end vent vacuum reading. Continue to reduce the frequency until the end vent vacuum read- ing is between 2.5" - 3.0" wc. Make note of this fre- quency setting below. The frequency is found on the VFD’s LCD screen.

2.5" wc - 3.0" wc VFD Frequency Setting

Record Frequency Setting Here:

To avoid damage to the pump motor, do not adjust the frequency above 60.0 Hz. Verify that the end vent

vacuum readings in the remaining branches are proper. If necessary, adjust the proper damper cou- pling to achieve an end vent vacuum of 2.5" - 3.0" wc. See Page 45, Figure 26. Damper couplings should be found near the end of the radiant portion of the pipe in each branch or where a branch connects to other branches at a cross or tee. See Page 46, Fig- ure 27.

44 of 62

Image 50
Contents UltraVac Page Roberts-Gordon LLC Page Table of Figures Page Page Corayvac Design Requirements Introduction 1.1 SafetyWhat is Roberts Gordon ULTRAVAC? Example Site Layout Check Installation Materials 1.6.1 Switchable LoadsSafety Labels and Their Placement Programming DetailsUltravac Controller Label Placement Ultravac BMS Link Controller Label Placement VFD Label Placement Repeater Label Placement Connected Components Connected Components Carton Contents Urvsc Ultravac Satellite Controller Urvccm Ultravac Central Controller with Modem Urvccr Ultravac Central Controller with RS-485 Converter Standard Parts List Urvbnc Ultravac BMS Link ControllerCommon Components of Roberts Gordon Ultravac Controls Example Site Layout Specifications Line Reactor 480 V / 4 a Output Nema 4 Enclosure for Indoor Sensor P/NVoltage Surge Suppressor 277 / 480 Line Reactor 480 V / 4 a InputRoberts Gordon Ultravac Controller Specifications Variable Frequency Drive VFD 2.7.1 Enclosure Standard Models Nema 4 ModelsVariable Frequency Drive Components Factory pre-wiring shown VFD should be mounted in locations where InstallationPreparation Ultravac BMS Link Controller Cable RequirementsUltravac Controller Variable Frequency Drive VFDPump Requirements Variable Frequency Drive RequirementsOutside Air Supply Indoor Sensor PlacementOutdoor Sensor Placement Typical External Diagrams Roberts Gordon Ultravac Central Controller External Wiring Roberts Gordon Ultravac Central Controller External Wiring Roberts Gordon Ultravac Satellite Controller External Wiring Roberts Gordon Ultravac Satellite Controller External Wiring Communications Dedicated Phone Line for Central Controller ModemRS-485 Converter for Central Controller RS-485 PC ConnectionTCP/IP Communication Module TCP/IP Communication Module MountingTCP/IP Communication Module Wiring Direct ConnectPin Adapter for PC Communications Between Multiple Controllers Repeater External Wiring Repeater Communication Wiring Between Multiple Controllers Ultravac BMS Link Controller Ultravac BMS Link Controller OverviewUltravac BMS Link Controller Technical Data Ultravac BMS Link Controller ProgrammingUltravac BMS Link Controller Roberts Gordon Ultravac VFD Parameter Settings For Use WithVariable Frequency Drive Programming Parameter Factory New Number Name Default Altering VFD ParametersSetting The Corayvac End Burner Vacuum Commissioning the Corayvac SystemEnd Vent Vacuum Possible Damper Couplings’ Locations Parameter Factory New Number Name Default Troubleshooting Electrical Shock Hazard Disconnect electric before serviceTroubleshooting Flow Chart Troubleshooting Flow Chart Troubleshooting Flow Chart Troubleshooting Flow Chart Troubleshooting Flow Chart Repeater Troubleshooting Flow Chart BACnet Replacement Parts Roberts Gordon Ultravac Controller Replacement Parts Roberts Gordon Ultravac Controller Components DiagramVariable Frequency Drive Replacement Parts Variable Frequency Drive Components DiagramUltravac BMS Link Controller Replacement Parts Ultravac BMS Link Controller Components DiagramRepeater Replacement Parts Repeater Components Diagram10.5.3 10080122 Eprom Chip Control Board Power LED10.5.4 24V Power 1 a Fuse Variable Frequency Drive 25 a or 10 a FuseReplacement Parts ROBERTS-GORDON will not PAY for Roberts Gordon Ultravac Limited WarrantyWarranty is Void if Limitations on Authority Representatives

10081601NA Rev H 12/11 specifications

Roberts Gorden is known for manufacturing high-quality heating systems, and one of their standout products is the model 10081601NA Rev H from December 2011. This unit exemplifies reliable performance and innovative technology, making it a popular choice in various industrial and commercial applications.

The Roberts Gorden 10081601NA Rev H is designed with efficiency in mind. One of its main features is the advanced infrared heating technology that ensures uniform heat distribution across large spaces. This is particularly beneficial in environments with high ceilings or open layouts, where traditional heating methods may struggle to maintain consistent temperatures. The infrared system allows for energy savings, as it heats objects and people directly rather than wasting energy on heating the air.

Another notable characteristic of the 10081601NA Rev H is its robust construction. Built to withstand rigorous operational environments, it often includes durable materials that enhance longevity and reliability. This product typically features corrosion-resistant components, making it suitable for use in various settings, including warehouses, manufacturing plants, and other commercial facilities.

The unit is also designed with user-friendly controls that allow for easy temperature adjustments and monitoring of performance. Advanced digital control systems may be integrated, providing precise control over heating levels. This feature ensures that users can tailor the heating output to their specific needs, optimizing energy consumption and comfort.

Safety is a priority with the Roberts Gorden 10081601NA Rev H, as it usually comes equipped with multiple safety features. These may include flame detection systems, automatic shutoff capabilities, and user alerts for maintenance requirements. Such features help ensure not only the efficiency of the heating system but also the safety of the personnel operating in the vicinity.

In summary, the Roberts Gorden 10081601NA Rev H is a cutting-edge heating solution that combines efficiency, durability, ease of use, and safety. Its main features, such as advanced infrared technology, robust construction, user-friendly controls, and safety mechanisms, make it an ideal choice for industries that demand reliable and effective heating solutions. Whether in a manufacturing setup or a large commercial space, this model stands out as a leading heating technology.