ROBERTS GORDON® ULTRAVAC™ CONTROLLER INSTALLATION MANUAL

10.5Replacement Parts Instructions

DANGER

Electrical Shock Hazard

Disconnect electric before service.

Controller must be properly grounded to an electrical source.

Failure to follow these instructions can result in death or electrical shock.

10.5.1 Plug-In Relay

To replace the plug-in relay, turn off 120 V power to the relay board. Turn off the 24 V power switch on the relay board. Locate the malfunctioning relay and pull the relay from its socket.

Fit a new relay in the socket. Return 120 V power to the relay board and turn on the 24 V power switch on the relay board. Press the reset button on the control board and close the doors.

10.5.2 Control Board Power LED

The LED is linked to the 24 Vac input which supplies the control board with power. If the LED is not lit, there is no power to the board. If this is the case, check the 120 V power wiring to the relay board, the 24 Vac power wiring from the relay board to the con- trol board and the 24 V power 1 A fuse.

10.5.3 10080122 Eprom Chip

The Eprom is where the controller's program (not settings) is stored. To take out the Eprom. The following steps must be taken:

Turn off the power to the control board by turning off the 24 V power switch on the relay board.

Locate the Eprom and with a small terminal screw driver placed underneath the device, pry the Eprom out of the socket.

To fit a new Eprom, look for the notch on one end of the Eprom.There is a notch on the socket and a notch on the Eprom. The Eprom should be fit so that the notch on the socket and the Eprom are aligned.

Turn on the 24 V power switch on the relay board, press the reset button on the control board and close

60 of 62

the doors.

10.5.4 24V Power 1 A Fuse

To replace the 1 A fuse, turn off power to the relay board and turn off the 24 V power switch on the relay board.

Locate the 1A fuse and remove it from its socket

using a flathead screwdriver. Twist the fuse a 1/4 turn counter-clockwise until the fuse pops out of the socket. Replace it with a new fuse.

Slide the fuse back into the socket, press down and turn the fuse a 1/4 turn clockwise until secure.

Return 120 V power to the relay board and turn on the 24 V power switch on the relay board. Press the reset button on the control board and close the doors.

10.5.5 Variable Frequency Drive (VFD)

To replace the Variable Frequency Drive, turn off all power to the drive assembly at the breaker or discon- nect switch. Turn off 120 V power to the relay board inside the ROBERTS GORDON® ULTRAVAC™ Con- troller. Turn off the 24 V power switch on the relay board.

Mark all wires connected to the VFD, noting the ter- minals that they are secured to. Remove all wires from the VFD terminals.

Remove the VFD from its mounting plate by remov- ing the four securing screws.

Verify that the input voltage noted on the rating plate of the VFD matches the input voltage of the old VFD. Secure the new VFD to the mounting plate with the four screws. Return all wires to the correct VFD ter- minals. If possible, it may be easier to partially re- wire the new VFD before mounting it to the mounting plate.

Close the door and return power to the VFD. Return 120 V power to the relay board. Turn on the 24 V power switch on the relay board. Press the reset but- ton on the control board and close the doors.

10.5.6 Variable Frequency Drive 25 A or 10 A Fuse

To replace a fuse, turn off input power to the variable frequency drive assembly at the breaker or disconnect switch.

Turn off 120 V power to the relay board inside the ROBERTS GORDON® ULTRAVAC™ Controller. Turn off the 24 V power switch on the relay board.

Inside the VFD assembly, open the fuse holder by

Image 66
Contents UltraVac Page Roberts-Gordon LLC Page Table of Figures Page Page Introduction 1.1 Safety What is Roberts Gordon ULTRAVAC?Corayvac Design Requirements Example Site Layout Check Installation Materials 1.6.1 Switchable LoadsSafety Labels and Their Placement Programming DetailsUltravac Controller Label Placement Ultravac BMS Link Controller Label Placement VFD Label Placement Repeater Label Placement Connected Components Connected Components Carton Contents Urvsc Ultravac Satellite Controller Urvccm Ultravac Central Controller with Modem Urvccr Ultravac Central Controller with RS-485 Converter Standard Parts List Urvbnc Ultravac BMS Link ControllerCommon Components of Roberts Gordon Ultravac Controls Example Site Layout Specifications Line Reactor 480 V / 4 a Output Nema 4 Enclosure for Indoor Sensor P/NVoltage Surge Suppressor 277 / 480 Line Reactor 480 V / 4 a InputRoberts Gordon Ultravac Controller Specifications Variable Frequency Drive VFD 2.7.1 Enclosure Standard Models Nema 4 ModelsVariable Frequency Drive Components Factory pre-wiring shown Installation PreparationVFD should be mounted in locations where Ultravac BMS Link Controller Cable RequirementsUltravac Controller Variable Frequency Drive VFDPump Requirements Variable Frequency Drive RequirementsIndoor Sensor Placement Outdoor Sensor PlacementOutside Air Supply Typical External Diagrams Roberts Gordon Ultravac Central Controller External Wiring Roberts Gordon Ultravac Central Controller External Wiring Roberts Gordon Ultravac Satellite Controller External Wiring Roberts Gordon Ultravac Satellite Controller External Wiring Communications Dedicated Phone Line for Central Controller ModemRS-485 Converter for Central Controller RS-485 PC ConnectionTCP/IP Communication Module TCP/IP Communication Module MountingTCP/IP Communication Module Wiring Direct ConnectPin Adapter for PC Communications Between Multiple Controllers Repeater External Wiring Repeater Communication Wiring Between Multiple Controllers Ultravac BMS Link Controller Ultravac BMS Link Controller OverviewUltravac BMS Link Controller Technical Data Ultravac BMS Link Controller ProgrammingUltravac BMS Link Controller VFD Parameter Settings For Use With Variable Frequency Drive ProgrammingRoberts Gordon Ultravac Parameter Factory New Number Name Default Altering VFD ParametersSetting The Corayvac End Burner Vacuum Commissioning the Corayvac SystemEnd Vent Vacuum Possible Damper Couplings’ Locations Parameter Factory New Number Name Default Troubleshooting Electrical Shock Hazard Disconnect electric before serviceTroubleshooting Flow Chart Troubleshooting Flow Chart Troubleshooting Flow Chart Troubleshooting Flow Chart Troubleshooting Flow Chart Repeater Troubleshooting Flow Chart BACnet Replacement Parts Roberts Gordon Ultravac Controller Replacement Parts Roberts Gordon Ultravac Controller Components DiagramVariable Frequency Drive Replacement Parts Variable Frequency Drive Components DiagramUltravac BMS Link Controller Replacement Parts Ultravac BMS Link Controller Components DiagramRepeater Replacement Parts Repeater Components Diagram10.5.3 10080122 Eprom Chip Control Board Power LED10.5.4 24V Power 1 a Fuse Variable Frequency Drive 25 a or 10 a FuseReplacement Parts ROBERTS-GORDON will not PAY for Roberts Gordon Ultravac Limited WarrantyWarranty is Void if Limitations on Authority Representatives

10081601NA Rev H 12/11 specifications

Roberts Gorden is known for manufacturing high-quality heating systems, and one of their standout products is the model 10081601NA Rev H from December 2011. This unit exemplifies reliable performance and innovative technology, making it a popular choice in various industrial and commercial applications.

The Roberts Gorden 10081601NA Rev H is designed with efficiency in mind. One of its main features is the advanced infrared heating technology that ensures uniform heat distribution across large spaces. This is particularly beneficial in environments with high ceilings or open layouts, where traditional heating methods may struggle to maintain consistent temperatures. The infrared system allows for energy savings, as it heats objects and people directly rather than wasting energy on heating the air.

Another notable characteristic of the 10081601NA Rev H is its robust construction. Built to withstand rigorous operational environments, it often includes durable materials that enhance longevity and reliability. This product typically features corrosion-resistant components, making it suitable for use in various settings, including warehouses, manufacturing plants, and other commercial facilities.

The unit is also designed with user-friendly controls that allow for easy temperature adjustments and monitoring of performance. Advanced digital control systems may be integrated, providing precise control over heating levels. This feature ensures that users can tailor the heating output to their specific needs, optimizing energy consumption and comfort.

Safety is a priority with the Roberts Gorden 10081601NA Rev H, as it usually comes equipped with multiple safety features. These may include flame detection systems, automatic shutoff capabilities, and user alerts for maintenance requirements. Such features help ensure not only the efficiency of the heating system but also the safety of the personnel operating in the vicinity.

In summary, the Roberts Gorden 10081601NA Rev H is a cutting-edge heating solution that combines efficiency, durability, ease of use, and safety. Its main features, such as advanced infrared technology, robust construction, user-friendly controls, and safety mechanisms, make it an ideal choice for industries that demand reliable and effective heating solutions. Whether in a manufacturing setup or a large commercial space, this model stands out as a leading heating technology.