Harman Stove Company 1-90-79700 owner manual Clearances To Combustibles

Page 10

Oakleaf Woodburning Stove

B. Clearances To Combustibles

CLEARANCE TO COMBUSTIBLES: Vertical Venting Configuration

Location

AUnit to Side Wall

B Unit to Back Wall

C Vent Pipe to Side Wall

D*

Vent Pipe to Back Wall

17" / 432 mm 14" / 356 mm 26.75" / 679 mm *17.5" / 444 mm

Pipe clearance may be reduced using double wall or insulated connector pipe, provided that you adhere to the specified clearances from the stove itself. Follow pipe manufacturer's guidelines.

C

A

D*

B

*NFPA 211 specifies 18" clearance to single wall connector pipe. This lower clearance is based on actual safety test conditions.

For clearance reduction methods, refer to NFPA 211 or Local Codes

CLEARANCE TO COMBUSTIBLES: Vertical Vent, Horizontal Exit

Location

AUnit to Side Wall

B Unit to Back Wall

C Vent Pipe to Side Wall

D*

Vent Pipe to Back Wall

E*

Vent Pipe to Ceiling

FMinimum Vertical

16" / 407 mm 13" / 330 mm 25.25" / 641 mm *17" / 432 mm *16" / 407 mm 0" / 0 mm

Pipe clearance may be reduced using double wall or insulated connector pipe, provided that you adhere to the specified clearances from the stove itself. Follow pipe manufacturer's guidelines.

*NFPA 211 specifies 18" clearance to single wall connector pipe. This lower clearance is based on actual safety test conditions.

 

E

F

C

 

A

C

A

E

D

B

10 Dry Seasoned Wood Only!

3-90-798

Save These Instructions

Image 10
Contents Installation and Operation Do Not DiscardOakleaf Woodburning Stove Table of Contents 1Listing and Code Approvals This appliance is also approved for installation in a shopMobile Home Approved If the alarm sounds 2Special Warnings and Notes3Getting Started Design, Installation & Location ConsiderationsFire Safety Appliance LocationComponent Locations Flue Direction ConversionPre- Use Check List Fire Risk4Dimensions & Clearances Appliance DimensionsClearances To Combustibles 17 / 432 mm 14 / 356 mm 26.75 / 679 mm *17.5 / 444 mmClearance to Combustibles Corner Installation Floor Protection Floor Protection RequirementsFloor Protection Requirements RequirementsDraft Chimney ConnectorsChimneys and Venting Wall Pass-thrusChimney 3-foot, 2-foot, 10 foot ruleVenting to a Masonry Chimney Installing to a Prefabricated ChimneyExisting Masonry Chimneys Venting to a Masonry Fireplace ChimneyAttic Factory-BuiltShield Metal ChimneyAirtight insulated Clean- out Oakleaf Woodburning Stove Full Relining Fireplace Conversion Freestanding Appliance Chimney Breach Fireplace Conversion with Combustible Wall Mobile Home Installation 6Mobile HomeLeveling the Appliance 7Appliance Set-UpOutside Air Attachment Optional Cooking GrillOptional Rear-vent Rear Shield Optional Blower InstallationOptional Bottom Heat Shield 8Operating Instructions Fuel SpecificationsAlways wear fire retardant gloves When operating the stove General Operating InformationDoors Or change the configuration of this grate systemCombustion Process GratesBefore Your First Fire User ControlsBuilding and Maintaining a Fire Oakleaf Woodburning Stove Seasonal cleaning Service & MaintenanceCreosote- Formation and Need For Removal By User Wear Leather Gloves To Prevent Skin Burns General Maintenance ProceduresAsh Removal Door GlassFirebox Blower- If installedChimney Oakleaf Optional Blower Kit #1-00-797032 Wiring Diagram 10Reference MaterialsService parts Part number list on followingStocked At depotStocked at depot Grams Per Hour 50% 60% 70% 80% 90% 100%Limited Lifetime Warranty Hearth & Home Technologies IncWarranty Conditions This warranty is void ifService & Maintenance Log Page Signature of Boxer Proudly Printed On 100% Recycled Paper