Heat & Glo LifeStyle 8000TVD Installing the Vent System Vent System Approvals, System Components

Page 13

Step 4. Installing the Vent System

A. Vent System Approvals

Model 8000TVD is approved to use 6-inch (152mm) diameter B-type vent. B-type vent must be used when the vent system is within combustible construction.

These models may also use single wall rigid or flexible gas vent IF and ONLY IF the vent system is installed within non-combustible construction such as a masonry chimney. The same diameter noted above for B-type vent must be used for single-wall vent. See Figure 5.

For B-type vent the clearance to combustibles is 1-inch. Follow vent manufacturers REQUIRED clearances.

The flame and ember appearance may vary based on the type of fuel burned and the venting configuration used.

B. System Components.

Vent System Configuration

RISE TO RUN RATIO = 2:1

MAXIMUM TOTAL HORIZONTAL RUN = 15 FT.

MINIMUM TOTAL VERTICAL RISE = 9 FT.

MAXIMUM NO. Of ELBOWS: 2 - 90o or 4 - 45o

Plan and install the vent system using the parameters shown above.

!WARNING: YOU MUST NOT EXCEED THESE PARAMETERS.

Connect a B-Type vent component to the flue outlet collar. Look at the vent pipe through the holes in the 10 5/8” ring to check that the vent pipe is attached.

NOTE: It is always better to first attach a straight section of vent to the unit before attaching an elbow. Avoid using elbows in the vent system if possible.

A 90-degree elbow can be attached directly to the unit. If it is, it can be followed by a MAXIMUM 15-feet horizontal run, a second 90-degree elbow ending in a minimum 30 foot vertical.

A minimum of 9 foot vertical rise ending in a listed termination cap is required for the unit.

Continue to add vent components, until the vent run is completed.

WARNING: YOU MUST NOT EXCEED A TOTAL ! MAXIMUM HORIZONTAL RUN OF 15 FEET FOR

THE ENTIRE VENT SYSTEM.

LISTED

TERMINATION CAP

LISTED

SINGLE-WALL

GAS VENT

NON-COMBUSTIBLE

CONSTRUCTION

B-TYPE

VENT

H

V

MINIMUM VERTICAL RISE = 9FT

MAXIMUM HORIZONTAL RUN = 15FT

V:H = 2:1

Figure 5. Vent System Attachment

NOTE: The vent termination must be in a vertical posi- tion and the termination cap must be listed for the vent pipe used.

Consult Local Building Code Officials and Codes for proper vent system installations.

!WARNING: THIS GAS FIREPLACE MUST NEV- ER BE VENTED BY CONNECTING TO A CHIM- NEY FLUE SERVING A SEPARATE SOLID FUEL BURNING APPLIANCE.

13

Image 13
Contents What to do if you smell gas Installers GuideSafety and Warning Information Table of Contents Log Set Assembly Service PartsCommon Parts / Piéces Communes Standing Pilot Ignition Valve Assembly 8000TVD-IPI Intermittent Pilot Ignition Valve AssemblyHigh Altitude Installations Installation Codes1Approvals Codes Appliance Certification2Getting Started Pre-install PreparationIntroducing the Heat-N-Glo Gas Fireplaces Unit with damaged, incomplete, or substitute partsDiagram of 8000TVD Locating the Fireplace 3Installing the FireplaceFraming the Fireplace Negative Pressure Make-up Air Installing Optional Outside Make-up AirAir Damper System Components Installing the Vent System Vent System ApprovalsRise to RUN Ratio = Maximum NO. Of Elbows 2 90o or 4 45oPositioning, Leveling, and Securing the Fireplace Vice Must be Wired to the Fireplace Junction BOXGas Control Systems Roof PitchGas Pressure Requirements Gas Supply LinePressure Natural Gas Propane Standing PilotFor Standing Pilot Ignition Wiring Appliance Requirements Wiring the FireplaceWall Switch Optional AccessoriesOperation using Battery Power For Intermittent Pilot Ignition IPI Wiring Volt TransformerFinishing Installing Trim, Logs, and Ember MaterialDouble-check for faulty components After the InstallationBefore Lighting the Fireplace Lighting the FireplaceMaintaining and Servicing Your Fireplace Fireplace MaintenanceImportant Turn OFF the GAS Before Servicing Your Fireplace