Heat & Glo LifeStyle 6100PLUS Gas Information, Fuel Conversion Gas Connection, Gas Pressure

Page 12

7Gas Information

A. Fuel Conversion

C. Gas Connection

Before making gas connections ensure appliance being in- stalled is compatible with the available gas type.

Any natural or propane gas conversions necessary to meet the appliance and locality needs must be made by a quali-

ed technician using Hearth & Home Technologies specifi ed and approved parts.

Note: Have the gas supply line installed in accordance with local building codes, if any. If not, follow ANSI 223.1. Installation should be done by a qualifi ed installer approved and/or licensed as required by the locality. (In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fi tter.)

B. Gas Pressure

Proper input pressures are required for optimum appliance performance. Gas line sizing requirements need to be made following NFPA51.

WARNING

 

Fire Risk

 

Explosion Risk

 

High pressure will damage valve.

 

• Disconnect gas supply piping BEFORE

 

pressure testing gas line at test pressures

 

above 1/2 psig.

 

• Close the manual shutoff valve BEFORE

 

pressure testing gas line at test pressures

 

equal to or less than 1/2 psig.

 

 

 

WARNING

 

Fire Risk

 

Explosion Risk

 

Verify inlet pressures.

￿

 

High pressure may cause overfire condition.

Low pressure may cause explosion.

Verify minimum pressures when other household gas appliances are operating.

Install regulator upstream of valve if line pressure is greater than 1/2 psig.

Pressure requirements for appliance are shown in table be- low. Minimum pressures must be met when other household gas appliances are operating.

Note: A listed (and Commonwealth of Massachusetts approved) 1/2 in. (13 mm) T-handle manual shut-off valve and fl exible gas connector are connected to the 1/2 in. (13 mm) control valve inlet.

If substituting for these components, please consult local codes for compliance.

Refer to Reference Section 14 for location of gas line access in appliance.

Note: Gas line may be run from the left side of appliance using the knockout provided. Hole in outer shell NOT to exceed 2-1/2 in. and should never penetrate the fi rebox.

WARNING

Gas Leak Risk

Support control when attaching pipe to prevent bending gas line.

Note: The gap between supply piping and gas access hole may be caulked with high temperature caulk or stuffed with non-combustible, unfaced insulation to prevent cold air infi ltration.

Ensure that gas line does not come in contact with outer wrap of appliance. Follow local codes.

Incoming gas line should be piped into the valve compartment and connected to the 1/2 in. connection on the manual shutoff valve.

Pressure

Natural Gas

Propane

Minimum Inlet Pressure

5.0 in. w.c.

11.0 in. w.c.

Maximum Inlet Pressure

7.0 in. w.c.

14.0 in. w.c.

Manifold Pressure

3.5 in. w.c.

10.0 in. w.c.

12

Hearth & Home Technologies • 6100PLUS • 4041-127 Rev D • 09/05

Image 12
Contents Models 6100PLUS Fresh Air Fireplace What to do if you smell gasHomeowner Reference Information Listing Label Information/LocationTable of Contents High Altitude Installations Listing and Code ApprovalsAppliance Certification Non-Combustible MaterialsDesign and Installation Considerations Getting StartedTools and Supplies Needed Inspect the Appliance and ComponentsFraming and Clearances Select Appliance LocationFire Risk Construct the Appliance Chase Fire Risk Odor RiskClearances Mantel ProjectionsTermination Locations Vent Termination Minimum ClearancesFire Risk Explosion Risk Vent Information and Diagrams Fire Risk Fumes RiskAppliance Preparation Securing and Leveling the ApplianceGas Information Fuel Conversion Gas ConnectionGas Pressure Gas Leak RiskFire Risk Explosion Risk Asphyxiation Risk Recommendation for Wire Connecting to the ApplianceElectrical Information Shock Risk Explosion RiskSystem Wiring 6100PLUS RequirementsHRV200PLUS Control Wiring Between R2Appliance Circuit Board Wiring Wall Switch Optional Accessories RequirementsFlame On/Off Electric Embers On/OffJunction Box Installation Junction Box DetailFinishing Facing MaterialAppliance Setup Clean the ApplianceLava Rock, Rockwool, Silica Rock Placement Remove the Shipping MaterialsPlacing the Rock Wool Placing the Silica Rock Techno SilGrate and Log Assembly Place the GratePlace the Right Front Log Place the Top LogAppliance Mode Operating InstructionsSequence of Operation Fire Risk Burn RiskHRV200PLUS Defrost Mode Lighting the Appliance Initial Break-in Procedure Fire Risk High TemperaturesAfter the Appliance is Lit Troubleshooting Troubleshooting GuideAnnual Maintenance Ember Bed Bulb ReplacementCleaning the Burner and Control Compartment Maintaining and Servicing the ApplianceThis page intentionally left blank Appliance Dimension Diagram Reference MaterialsService Parts List 6100PLUSRefractory Assembly, Traditional Log Set6100PLUS Description of Part 6100PLUS 6100PLUS-LPRemote Control Wall Switch Optional ComponentsSpfl Spvn Spwd SpwvOptional Components 6100PLUS 6100PLUS-LP Qty Arched Cabinet Doors Essence SeriesArched Cabinet Doors Prism Series This page intentionally left blank Limited Lifetime Warranty Contact Information