LOCKOUT BYPASS OPTION
!CAUTION
FOR QUALIFIED SERVICE TECHNICIANS’ USE ONLY. OPERATORS SHOULD NOT USE THIS FEATURE DUE TO POSSIBILITY OF EQUIPMENT OR PROPERTY DAMAGE, OR PERSONAL INJURY.
DO NOT USE THE LOCKOUT BYPASS OP- TION UNLESS THE COMPRESSOR OIL HEATERS HAVE BEEN OPERATIONAL FOR 6 HOURS AND THE SYSTEM HAS NOT BEEN OPERATIONAL FOR AT LEAST 5 MINUTES.
COMPRESSOR LONG TERM CYCLE
PROTECTION
To protect the compressor from potential damage due to temperature change of crankcase oil, this thermostat has a
than the power loss to the unit (up to 12 hours maximum lockout). During this time, auxiliary heat will be used when necessary to maintain setpoint temperature. DO NOT attempt to override this delay feature before crankcase temperature has stabi- lized (for example, if power has been out for three hours, the compressor should remain locked out for two hours).
COMPRESSOR SHORT TERM CYCLE
PROTECTION
This thermostat has a
press | ADV | and | HOLD | at the same time at initial |
PRGM | TEMP |
startup.
21