Desa (V)T32N SERIES, (V)T32P SERIES Test Pressures Equal To or Less Than Psig 3.5 kPa

Page 22

Fireplace

Installation

Continued

Pressure Testing Gas Supply

Piping System

Test Pressures In Excess Of 1/2 PSIG

(3.5 kPa)

1. Disconnect fireplace and its individual equip- ment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2. Cap off open end of gas pipe where equipment shutoff valve was connected.

3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace, or using compressed air.

4. Check all joints of gas supply piping system. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5. Reconnect fireplace and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than

1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see Figure 33).

2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fireplace, or using compressed air.

3. Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34 or 35). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Equipment

Open

Shutoff Valve

 

Closed

Figure 33 - Equipment Shutoff Valve

 

Equipment

Propane/LP

Shutoff Valve

 

Supply Tank

 

 

Gas Valve

Figure 34 - Checking Gas Joints for

Propane/LP Gas Fireplace

Equipment Shutoff Valve

Gas

Meter

Gas Valve

Figure 35 - Checking Gas Joints for

Natural Gas Fireplace

Pressure Testing Fireplace Gas

Connections

1. Open equipment shutoff valve (see Figure 33).

2. Open main gas valve located on or near gas meter for natural gas or open supply tank valve for propane/LP gas.

3. Make sure control knob of fireplace is in the OFF position.

4. Check all joints from equipment shutoff valve to thermostat gas valve (see Figure 34 or 35). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5. Light fireplace (see Operating Fireplace, page

27). Check all other internal joints for leaks.

6. Turn off fireplace (see To Turn Off Gas to Appliance, page 27).

22

www.desatech.com

111986-01D

Image 22
Contents What to do if YOU Smell GAS Table of Contents Safety InformationSafety Information Product Identification Product FeaturesLocal Codes High traffic areasThis fireplace does not require electricity to operate Pre-Installation PreparationLocation and space requirements Proper clearances must be maintainedFront Top of Standoffs Vent See venting ClearancesFraming and finishing Venting clearancesLocation of Termination Cap Balcony with Perpendicular Side WallVenting Installation Instructions Installation PrecautionsInstallation Planning Installing Horizontal Vent Cap Noncombustible Exterior Ground Floor Installation Snorkel Termination Installation Recommended Applications Corner ground floor installationHorizontal System Installation Using TWO 90 Elbows Flat Ceiling Installation Installation for vertical terminationConnect a section of pipe and extend up through the hole Twist-lock the vent cap onto the last section of vent pipe High Altitude Installation Vertical VentingDesa Terminations Desa Venting AccessoriesDesa Elbows Number DescriptionModel BK Installation Fireplace InstallationInstalling optional blower accessories Check GAS TypeModel BKT Installation Plug in blower power cord to duplex outletBlower Wiring Diagram Installing Gas Piping to Fireplace LocationInstallation Items Needed Connecting Fireplace to GAS Supply Checking GAS ConnectionsPressure Testing Fireplace Gas Connections Test Pressures Equal To or Less Than Psig 3.5 kPaInstalling Remote Receiver Installing optional wall mount switch GWMS2Open bottom louver and locate the switch Removing Louver Panels Cleaning Glass DoorRemoving/Replacing Glass Door Removing Glass DoorInstalling logs, lava rock and glowing embers Installing Optional Brick liner Model BL32DClose top and bottom louvers Installing Log No Lighting Instructions For your safety Read before lightingOperating Fireplace To Turn OFF GAS To ApplianceOn/Off Series Models HRC100 and HRC101 Manual Lighting ProcedureOptional Hand-Held Remote OperationAuto Shutoff Feature Operating optional blower accessorySafety Features Key Pad Lock FeatureInspecting Burners Cleaning MaintenancePilot Assembly Burner Flame PatternLogs Pilot and burnersVenting system Troubleshooting Observed Problem Possible Cause RemedyBurner orifice clogged Clean burner see Cleaning Is lit Mocouple to cool, causingProblem could be caused by Replace pilot assembly After pilot lights, keep gasOr shut off Service person Remote does not function When burner is litDirty or partially clogged 3. Clean burner see Cleaning Tery power is lowGas leak. See Warning Statement aboveTechnical Service Replacement PartsService Hints SpecificationsRolled Louver Trim kit Wall mounted on/off switch gwms2 Not ShownFace/Louver Panel kit Deflection hoodIllustrated Parts Breakdown Parts List Keep this Warranty Warranty InformationLimited Warranty DIRECT-VENT Fireplace

(V)T32N SERIES, (V)T32P SERIES specifications

Desa (V)T32P and (V)T32N Series are cutting-edge technological offerings from Desa, known for their precision and reliability in high-performance applications. These series are designed to meet the evolving needs of engineers and manufacturers in various sectors, including automotive, aerospace, and industrial automation. Both series boast an impressive array of features that enhance functionality, efficiency, and safety.

One of the main features of the (V)T32P Series is its advanced processing capabilities. These models come equipped with powerful processors that enable rapid data handling and processing. This makes them ideal for applications that require real-time monitoring and control. Additionally, the series supports a wide range of input and output options, allowing seamless integration into diverse systems.

The (V)T32N Series, on the other hand, focuses on connectivity and data communication. These models incorporate state-of-the-art networking technologies, including Ethernet, Wi-Fi, and various industrial communication protocols. This enables easy integration into existing networks, promoting collaborative environments where information can be shared quickly and securely. The series also features enhanced security protocols to safeguard sensitive data against cyber threats.

Both series are built with durability in mind. They utilize robust materials and advanced manufacturing techniques to withstand harsh operating conditions, reducing downtime and maintenance costs. Additionally, the devices in these series have been designed to be energy-efficient, adhering to industry standards and providing cost savings over time.

Another significant characteristic of both the (V)T32P and (V)T32N Series is their user-friendly interfaces. With intuitive controls and clear display options, users can easily navigate through settings and configurations, ensuring quick adaptation and efficient operation. This ease of use is further complemented by comprehensive documentation and support resources provided by Desa, ensuring that users can maximize the capabilities of their systems.

In summary, the Desa (V)T32P and (V)T32N Series represent a leap forward in technology for professionals seeking reliable, efficient, and user-friendly solutions. Their powerful processing capabilities, advanced connectivity options, durability, and ease of use make them ideal choices for a variety of applications, ensuring that users are well-equipped to tackle the challenges of modern engineering and manufacturing.