Venting Installation
instructions
Continued
INSTALLATION PLANNING
There are two basic types of
•Horizontal Termination
•Vertical Termination
Horizontal Termination Installation IMPORTANT: Horizontal square terminations require only inner portion of wall firestop. Hori- zontal installations using round termination require exterior portion of wall firestop (see Figure 14, page 12).
1. Set the fireplace in its desired location and |
determine the route your horizontal venting |
will take. Do not secure the fireplace until |
all venting has been installed. Some installa- |
tions require sliding the fireplace in and out |
of position to make final venting connections. |
Figures 14 through 18 on pages 12 through |
14 show different configurations for venting |
with horizontal termination that will help |
you decide which application best suits your |
installation. Check to see if wall studs or roof |
rafters are in the path of your desired venting |
route. If they are, you may want to adjust the |
location of the fireplace. |
2. Direct vent pipe sections and components are |
5.Carefully determine the location where the vent pipe assembly will penetrate the outside wall. The center of the hole should line up with the
Female
Locking Lugs
Male
Slots
Figure 8 - Vent Pipe Connections
Vent Opening
Combustible Wall 10 3/4" Inside Framing
10 3/4"(27.3 cm)
(27.3 cm)
10 3/4"
(27.3 cm)
(Framing
designed with special |
Vent Opening
Detail)
the pipes have locking lugs (indentations). |
These lugs will slide straight into matching |
slots on the male ends of adjacent pipes. Push |
pipe sections together and twist one section |
clockwise approximately |
until the sections are fully locked (see Figure |
8). Note: Horizontal runs of vent must be |
supported every three feet. Use wall straps |
for this purpose. |
3. Use a 45° elbow to connect venting system |
to fireplace flue collar. The elbow is designed |
to be |
described in step 2. IMPORTANT: Do not |
attempt to alter the configuration of the elbow |
by cutting, twisting, bending, etc. |
4. Assemble the desired combination of pipe and |
elbows to the fireplace flue collar. If there are |
long portions of venting run, |
pipe sections may be installed as subassem- |
blies for convenience. |
Noncombustible Wall
8 1/2" |
(21.6 cm) |
Center of |
Hole |
Figure 9 - Vent Opening Requirements |
10 | www.desatech.com |