Desa CGEFP33PR, VTGF33NR, VTGF33PR Connecting Fireplace to GAS Supply, Checking GAS Connections

Page 17

INSTALLATION

Connecting Fireplace To Gas Supply (Cont.) Checking Gas Connections

17

INSTALLATION

Continued

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

Phillips screwdriver

sealant (resistant to propane/LP gas, not provided)

1.If fireplace screen and floor are still installed, see Removing Fireplace Screen and Floor Assembly, page 8.

2.Route gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes.

NOTICE: Most building codes do not permit con- cealed gas connections. A flexible gas line is pro- vided to allow accessibility from the fireplace (see Figure 26). The flexible gas supply line connection to the equipment shutoff valve should be accessible.

3.Attach the flexible gas line to gas supply (see Figure 26). Check tightness of flexible gas line attached to gas regulator of fire- place (see Figure 26).

4.Check all gas connections for leaks. See Checking Gas Con- nections.

5.Replace fireplace floor assembly. Feed flexible gas line into fireplace base area while replacing fireplace floor assembly. Make sure the entire flexible gas line is in fireplace base area.

Note: Be careful of wires and components on underside of fireplace floor. Reattach fireplace floor assembly with screws removed in step 3 of Removing Fireplace Screen and Floor Assembly, page 8.

To Fireplace

Flexible Gas Line from

Gas Regulator

Fireplace Gas Regulator

 

 

 

Equipment Shutoff Valve Provided by Installer

From Gas Meter (Natural) From External Regulator (Propane/LP)

Figure 26 - Attaching Gas Lines Together

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

WARNING: For propane/LP units, make sure exter- nal regulator has been installed between propane/LP supply and heater. See guidelines under Installing Gas Piping to Fireplace Location, page 15.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect appliance with its appliance main gas valve (con- trol valve) and equipment shutoff valve from gas supply pip- ing system. Pressures in excess of 1/2 psig will damage fire- place gas regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using com- pressed air.

4.Check all joints of gas supply piping system. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect fireplace and equipment shutoff valve to gas sup- ply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 27, page 18).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using com- pressed air.

3.Check all joints from gas meter for natural or propane/LP sup- ply to equipment shutoff valve (see Figures 28 or 29, page 18). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.

4.Correct all leaks at once.

For morevisit www..com

108117

Image 17
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualSafety Information Table of ContentsProduct Identification Fireplace Floor Assembly EFP33PR ShownUnpacking Product FeaturesLocal Codes Providing Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined Space and Unconfined SpaceVentilation AIR Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside BuildingVentilation Air From Outdoors InstallationInstallation Sequence Installation ClearancesRemoving Fireplace Screen and Floor Assembly Check GAS TypeRelocating Wall Switch Electrical Connections for Power CordRelocating Switch and Wall Plate Ing from inside mantel see Figure Installing Variable Speed Blower AccessoryAttaching Speed Control to Firebox VTGF33NR/ VTGF33PR Shown Operating the Blower Installing Thermostatic Blower AccessoryAttaching Speed Control VTGF33NR/VTGF33PR Shown Installing GAS Piping to Fireplace Location Installation Items Needed Installation Items Needed Connecting Fireplace to GAS SupplyPressure Testing Gas Supply Piping System Checking GAS ConnectionsPressure Testing Fireplace Gas Connections Conventional Fireplace InstallationInstalling Cabinet Mantel BUILT-IN Fireplace InstallationAssembling and Attaching Optional Brass Trim Mantel Clearances for Built-In InstallationInstalling Hood Installing Logs VTGF33NR/VTGF33PRInstalling Installing Logs CGEFP33PR/CGEFP33NRInstalling Logs EFP33PR/EFP33NR For Your Safety Read Before Lighting Installing Battery Into RemoteInstalling Screen Operating FireplaceTo Turn OFF GAS to Appliance Normal Lighting InstructionsOptional Blower Operation Manual Lighting Instructions for Electrical Power OutageShutting Off Heater When Manually Lit Pilot Flame Pattern Inspecting BurnersFront Burner Flame Pattern VTGF33 Series only Main BurnerCleaning Burner Injector Holder Cleaning MaintenanceCleaning Pilot AIR Inlet Hole LogsObserved Problem Possible Cause Remedy TroubleshootingFor Com Gas leak. See Warning statement Service Hints SpecificationsTechnical Service Replacement PartsEFP33NR/EFP33PR and CGEFP33NR/CGEFP33PR VTGF33NR/VTGF33PR Wiring DiagramIllustrated Parts Breakdown KEY Part Number EFP33 CGEFP33 Description QTY Parts ListFirebox EFP33PR/NR CGEFP33PR/NR7 KEY Part Number Description QTY Firebox EFP33PR/NR CGEFP33PR/NRRemote Control LOG Base Assembly VTGF33PR and VTGF33NR Shown Contains Items 28, 30, 31, 33 Firebox VTGF33NR VTGF33PR Firebox VTGF33NR and VTGF33PR Blower Accessories AccessoriesCorner Mantel Accessory with Fireplace Perimeter Brass Trim Equipment Shutoff Valve GA5010Corner Hearth Base Cleaning KIT CCK/GCKLaminate Trim for Hearth or Mantel Slim Hearth BaseFor . .com Diameter Holes TemplatesThis page Intentionally Left Blank Owners Registration Form Postage Required 108117 Not a UPC

VTGF33NR, CGEFP33PR, VTGF33PR specifications

Desa VTGF33PR, CGEFP33PR, and VTGF33NR are innovative heating solutions designed to enhance comfort and provide efficient warmth in various living spaces. These products are particularly popular for their advanced features, energy efficiency, and usability.

The Desa VTGF33PR is a natural gas vent-free infrared heater that showcases a sleek design and powerful performance. One of its standout features is its infrared technology, which allows for direct heating by warming surfaces in the room rather than just the air. This results in faster warmth and efficient energy use. The VTGF33PR also comes equipped with a thermostat, ensuring optimal temperature regulation and control over heating preferences. With a heating capacity of 33,000 BTUs, it is suitable for larger areas, providing consistent and reliable warmth even in larger spaces.

Moving on to the CGEFP33PR, this model operates on propane and combines both elegance and efficiency. This direct vent fireplace offers a unique balance between aesthetics and performance. The CGEFP33PR features a contemporary design, making it a stylish addition to modern homes. With its high-efficiency venting system, it ensures that combustion gases are safely expelled outside while maximizing heat output into the living space. It also showcases an adjustable flame feature, allowing users to set their desired ambiance while maintaining energy efficiency. Like the VTGF33PR, it includes a thermostat control for precise temperature adjustments.

Finally, the VTGF33NR is another noteworthy entry in Desa’s lineup. It operates similarly to the VTGF33PR, with a focus on infrared heating. However, the VTGF33NR distinguishes itself with its impressive portability and versatility. It is designed to be easy to install and relocate, making it a perfect choice for both homeowners and renters. Its space-saving design allows it to fit seamlessly into various room setups. This model also boasts a robust safety feature set, including an oxygen depletion sensor and an automatic shut-off mechanism, ensuring safe operation in any environment.

In summary, Desa’s VTGF33PR, CGEFP33PR, and VTGF33NR present a range of heating solutions that prioritize energy efficiency, safety, and user comfort. With advanced technologies such as infrared heating and sleek designs, these models stand out as practical solutions for any home looking to enhance its heating capabilities while maintaining modern aesthetics.