Desa VYGF33PRC installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 7

AIR FOR COMBUSTION

AND VENTILATION

Continued

Example:

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vent-free fireplace +

33,000

Btu/Hr

Total

=

73,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________Btu/Hr (maximum the space can support)

_________Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi- mum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an uncon- fined space. You will need no additional fresh air ventilation.

WARNING:Iftheareainwhich the fireplace may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustionandventilationairby one of the methods described in theNationalFuelGasCode,ANSI Z223.1/NFPA 54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting

the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see option 3, Figure 3). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

 

 

12"

Ventilation

 

Ventilation Grills

Grills

 

Into Adjoining

Or

Into Adjoining Room,

Room,

Option 2

Remove

Option 1

 

Door into

 

 

 

 

Adjoining

 

 

Room,

 

 

Option

 

 

3

 

12"

Figure 3 - Ventilation Air from Inside

Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 4 - Ventilation Air from Outdoors

113109-01B

www.desatech.com

7

Image 7
Contents Patent Pending What to do if YOU Smell GASTable of Contents Safety Information Product Identification Log Base AssemblyAIR for Combustion Ventilation Product FeaturesLocal Codes UnpackingConfined and Unconfined Space Providing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location Unusually Tight ConstructionVentilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Electrical Hookup InstallationInstalling Hood Check GAS TypeRepeat steps 1 through 6 for other side Installation ClearancesPlacing Hearth Base Accessory Against Wall Conventional Fireplace InstallationModels VYGF33PRB and VYGF33NRB BUILT-IN Fireplace InstallationModels FPVF33PRA and FPVF33NRA Connecting Duplex OutletMantel Clearances for Built-In Installation Installing GAS Piping to Fireplace LocationInstallation Items Needed Natural Gas Connecting Fireplace to GAS SupplyPropane/LP Test Pressures In Excess Of 1/2 Psig 3.5 kPa Checking GAS ConnectionsTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Pressurize supply piping system by eitherVygf Models Only Installing LogsFpvf Models Only Installing Remote Receiver UnitInstalling 9-Volt Battery in Hand-Held Remote Control Unit Installing 9-VOLT BatteriesFor Your Safety Read Before Lighting Installing 9-Volt Battery in ReceiverPilot Propane/LP Lighting InstructionsON/OFF Series Model Ghrcb Manual Lighting ProcedureTo Turn OFF GAS To Appliance Optional HAND-HELD Remote OperationOptional Blower Operation Thermostat Series Model GhrctbBurner Primary AIR Holes Inspecting BurnerPilot Flame Pattern Burner Flame PatternBurner Injector Holder and Pilot AIR Inlet Hole Cleaning MaintenanceLogs Observed Problem Possible Cause Remedy TroubleshootingDiagram, Maintenance, Gas leak. See Warning Fireplace produces unwantedTechnical Service Wiring DiagramSpecifications Replacement PartsModels VYGF33PRC and VYGF33NRC Shown Illustrated Parts BreakdownParts List Models FPVF33PRA and FPVF33NRA KEY Part Number FPVF33PRA FPVF33NRA Description QTY Firebox Models VYGF33PRC and VYGF33NRC KEY Part Number Description QTY Firebox Models FPVF33PRA and FPVF33NRA Parts List Accessories Laminate Trim for Hearth or Mantel Receiver and HAND-HELD Remote Control KIT Ghrcb SeriesWALL-MOUNT ON/OFF Switch Cabinet Mantel and Full Hearth BaseKeep this Warranty Warranty InformationLimited Warranty VENT-FREE GAS Fireplace