Desa DVFE34 installation manual General Venting

Page 6

DIRECT-VENT FIREPLACE

GENERAL VENTING Continued

D

E V

B L

C

H

N

N

 

Fixed

V

 

Closed

 

 

F

Openable

 

V

 

B

Openable Fixed

Closed

V

B

I

G

B

B

V J X

G

A

M

V

K X

V

G V A

V TERMINATION CAP

X AIR SUPPLY INLET

 

GAS METER

 

RESTRICTED AREA (TERMINATION PROHIBITED)

A= clearance above grade, veranda, porch, deck, or balcony [*12 inches (305mm) minimum]

B= clearance to window or door that may be opened

[12 inches (305mm) minimum]

C = clearance to permanently closed window [minimum 12 inches (305mm) recommended to prevent condensation on window]

D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (610mm) from the center-line of the terminal [18 inches (457mm) minimum]

E= clearance to unventilated soffit [12 inches (305mm) minimum]

F= clearance to outside corner (see below)

G= clearance to inside corner (see below)

H= *not to be installed above a meter/regulator assembly within

36 inches (914mm) horizontally from the center-line of the regulator

I= clearance to service regulator vent outlet [*72 inches (1829mm) minimum]

J= clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [*12 inches (305mm) minimum]

K= clearance to a mechanical air supply inlet [*72 inches (1829mm) minimum]

L= † clearance above paved side-walk or a paved driveway located on public property [*84 inches (2133mm) minimum]

M= clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡]

N= clearance above a roof shall extend a minimum of 24 inches (610mm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 inches (457mm)

vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings*

‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*

* as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow the current National Fuel Gas Code, ANS Z223.1

Note: Local codes or regulations may require different clearances

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Inside Corner

A

 

A = 6" (152mm)

 

V

Outside Corner

V

B B = 6" (152mm)

Recessed Location

D

C

C

E

V

Balcony with No Side Wall

G

V

G = Combustible 24" (610mm) Noncombustible 18" (457mm)

Balcony with Perpendicular Side Wall

H

V

J

Combustible &

Noncombustible

H = 24" (610mm)

J = 20" (508mm)

C = Maximum depth of 48" (1219mm) for recessed location

D = Minimum width for back wall of recessed location - Combustible - 38" (965mm) Noncombustible - 24" (610mm)

E = Clearance from corner in recessed location- Combustible - 6" (152mm) Noncombustible - 2" (51mm)

Figure 8 - Minimum Clearances for Vent Terminations

For more information, visit www.desatech.com

6

107205

Image 6
Contents For Your Safety For Your Safety What to do if YOU Smell GASDVFE34 Natural Electronic Ignition Safety Information DIRECT-VENT Fireplace Glossary Terms Product Identification Local Codes OperationClearances PRE-INSTALLATION PreparationLocation and Space Requirements Framing and FinishingPRE-INSTALLATION General Venting Preparation Location of VentTermination General Venting Installation Planning Venting InstallationInstallation Precautions Installing Vent System in a ChaseInstallation for Horizontal Termination Snorkel TerminationFor vinyl siding use vinyl siding stand Rigid Vent Pipe Horizontal Termination Configurations Rigid Vent Pipe Horizontal VentingVenting with Two 90 Elbows Installation for Vertical Termination Flat Ceiling InstallationCathedral Ceiling Installation Vertical Termination Configurations Venting with Two 90 Elbow sVertical Venting High Altitude Installation Parts Lists for Venting Kits and ComponentsFMI Rigid Venting Installing GA3700/DA3610TA Blowers Fireplace InstallationInstalling Optional Blower Accessory Check GAS TypeIf your fireplace system is installed Installing GAS Piping to Fireplace Location Installation Items NeededConnecting Fireplace to GAS Supply Pressure Testing Gas Supply Piping SystemChecking GAS Connections Pressure Testing Fireplace Gas Connections Close equipment shutoff valve see Fig- ureInstalling Optional Wall Mount Switch GWMS2 REMOVING/REPLACING Glass DoorInstalling Optional Brick Liner D8037A Attaching Magnetic Decorative Brass StripsInstalling LOGS, Lava Rock and Glowing Embers Installing Log NoLighting Instructions For Your Safety Read Before LightingOperating Fireplace To Turn OFF GAS To AppliancePilot Assembly Operating Optional Blower AccessoryOperating Optional GWMS2 Wall Mounted Switch Inspecting BurnersPilot and Burners Cleaning and MaintenanceGlass Door LogsTroubleshooting Observed Problem Possible Cause RemedyOrifice Gas leak. See Warning statement Technical Service Replacement PartsService Hints Wiring DiagramsSpecifications DVFE34Illustrated Parts Breakdown DVFE34Parts List KEY Part Number Description QTYAccessories 107205 Warranty Information