DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 3168 cu. ft. (volume of space) 50 cu. ft. = 63.3 or 63,300 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

 

___________________ Btu/Hr

 

 

 

 

Gas water heater*

 

___________________ Btu/Hr

 

 

 

 

Gas furnace

 

___________________ Btu/Hr

Example:

 

 

 

Vented gas heater

 

___________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Vent-free fireplace

+

33,000

Btu/Hr

Other gas appliances*

+

___________________ Btu/Hr

Total

=

73,000

Btu/Hr

Total

=

___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_____________ Btu/Hr (maximum the space can support)

_____________ Btu/Hr (actual amount of Btu/Hr used)

Example: 63,300 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework work sheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air from Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 6.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Continued

107569

5

For more information, visit www.desatech.com

Image 5
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualUnvented Natural GAS Fireplace Safety InformationUnpacking Product IdentificationLocal Codes AIR for Combustion and Ventilation Product FeaturesDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsInstallation Clearances InstallationCheck GAS Type Electrical HookupRelocating Wall Switch Installation SequenceRemoval of Fireplace Screen and Floor Assembly Lines and wiring when moving floor Mounting Wall Switch to Side of Mantel Installing Variable Speed Blower AccessoryOperating the Blower Installing Plastic Bushing for Power CordLower Rear Wall Firebox Blower Installing Thermostatic Blower AccessoryInstalling Bushings Left Side Exit shown Installation Items Needed Installing GAS Piping to Fireplace LocationConnecting Fireplace to GAS Supply Pressure Testing Gas Supply Piping System Conventional Fireplace InstallationPressure Testing Fireplace Gas Connections Checking GAS ConnectionsActual Framing Height 32 3/8 Front Width Depth BUILT-IN Fireplace InstallationNails or Wood Screws Mantel Clearances for Built-In InstallationInstalling Logs CGEFP33NR Installing HoodMiddle Log #1 Shaped Cutout in Base Burner Installing Logs EFP33NRInstalling Battery Into Remote Installing ScreenFor Your Safety Read Before Lighting Operating FireplaceUsing Hand-Held Wireless Remote Control Manual Lighting Instructions For Electrical Power OutageShutting Off Heater Wall Switch Shutting Off Heater Wireless Remote ControlInspecting Burners Shutting Off Heater When Manually LitOptional Blower Operation Pilot Flame PatternLogs Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Observed Problem Possible Cause TroubleshootingObserved Problem Possible Cause Remedy Gas leak. See Warning statement Wiring Diagram Replacement Parts SpecificationsService Hints Technical ServiceParts Dealers Illustrated Parts Breakdown Remote Control Fireplace EFP33NR and CGEFP33NR Parts ListFirebox KEY Part Number Description QTY Blower Accessory GA3750 Series and GA3650T Series AccessoriesCorner Mantel Equipment Shutoff Valve GA5010Diameter Holes This page Intentionally Left Blank 107569 Warranty Information

CGEFP33NR specifications

Desa CGEFP33NR is an innovative and efficient electrical appliance designed to cater to modern household needs. At the forefront of its offering is its exceptional energy efficiency, which allows it to provide substantial heating power while minimizing energy consumption. This model is equipped with advanced heating technologies that ensure quick and consistent warmth throughout any space it occupies.

One of the standout features of the Desa CGEFP33NR is its dual-fuel capability. This versatile appliance can operate on both natural gas and propane, making it a flexible choice for various residential settings. Users can easily switch between fuel types based on availability or preference, ensuring that they have a dependable heating source regardless of external conditions.

The unit also boasts an impressive heat output of up to 33,000 BTUs, which is suitable for heating spaces up to 1,500 square feet. This powerful heating capability is complemented by a built-in thermostat that allows for precise temperature control, ensuring that users can maintain their desired comfort level. The adjustable flame settings further enhance user control, letting individuals customize the heat output according to their specific requirements.

In terms of design, the Desa CGEFP33NR features a sleek and modern aesthetic that fits seamlessly into any home decor. Its compact size allows for easy installation, and it can be mounted on the wall or used as a freestanding unit, providing flexibility in placement. Safety is a top priority with this appliance, featuring built-in safety mechanisms such as an automatic shut-off system that activates in case of any irregularities.

The Desa CGEFP33NR is also equipped with a robust ignition system that ensures reliable start-up during operation. With its durable construction and high-quality materials, this unit is built to withstand the rigors of daily use while providing long-lasting performance.

In conclusion, the Desa CGEFP33NR is a remarkable heating solution that combines efficiency, versatility, and modern design. Its range of features, including dual-fuel capability, adjustable heat settings, and safety mechanisms, make it an ideal choice for homeowners looking to enhance their living spaces with effective and reliable heating solutions while also being energy-conscious.