Desa UNVENTED (VENT-FREE) NATURAL GAS FIREPLACE Air For Combustion And Ventilation

Page 6
AIR FOR COMBUSTION AND VENTILATION

AIR FOR COMBUSTION AND VENTILATION

6

WARNING

WARNING ICON

G 001

This fireplace must have fresh air for proper operation. If not, poor fuel combustion could result. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.

Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.

While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. Fresh air enters the home through and around doors and windows. This may provide enough fresh air for combustion and ventilation. All fuel-burning appliances need fresh air for proper combustion and ventilation.

Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

In the absence of local codes, use the following excerpts from the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications:

1. Unusually Tight Construction; 2. Unconfined Space; 3. Confined Space.

The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for com- bustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a continu- ous water vapor retarder with a rating of one perm or less with open- ings gasketed or sealed and

b.weather stripping has been added on openable windows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 8.

If your home does not meet all of the three criteria above, proceed to page 7.

Unconfined Space

An unconfined space has a minimum air volume of 50 cubic feet for each 1000 BTU/Hr input rating of all appliances in the space (cubic feet equals length x width x height of space). Include adjoining rooms only if there are doorless passageways or ventilation grills between the rooms.

If the BTU per 50 cubic feet is less than 1000 BTU/Hr, then the fresh air will be provided by the natural air flow into the house.

Confined Space

A confined space has an air volume of less than 50 cubic feet for each 1000 BTU/ Hr input rating of all appliances in the space (cubic feet equals length x width x height of space). Include adjoining rooms only if there are doorless passageways or ventilation grills between the rooms.

101742

Image 6
Contents OWNER’S OPERATION AND INSTALLATION MANUAL Save this manual for future referenceUNVENTED VENT-FREENATURAL GAS FIREPLACE DANGER CONTENTS SAFETY INFORMATIONWARNINGS Safety Information continues on next pageSAFETY INFORMATIONContinued PRODUCT IDENTIFICATION Figure 1 - Log Base AssemblyFigure 2 - Fireplace Operation LOCAL CODES UNPACKING PRODUCT FEATURESSafety Device Piezo Ignition SystemAIR FOR COMBUSTION AND VENTILATION PROVIDING ADEQUATE VENTILATIONCOMBUSTION AIR FORVENTILATION ContinuedVENTILATION AIR AIR FOR COMBUSTION AND VENTILATIONContinued Ventilation Air from Inside BuildingINSTALLING NOTICEContinued INSTALLING ContinuedASSEMBLING AND ATTACHING BRASS TRIM Continued INSTALLINGINSTALLATION CLEARANCES CONVENTIONAL FIREPLACE INSTALLATIONINSTALLING Continuedheads and putty over Continued INSTALLINGBUILT-INFIREPLACE INSTALLATION ContinuedContinued INSTALLINGFigure 13 - Attaching Nailing Flange Accessory 39 3/8 27 7/8 35 1/2 55 5/8Continued INSTALLINGMantel Clearances for Built-InInstallation ContinuedInstallation Items Needed INSTALLINGINSTALLING GAS PIPING TO FIREPLACE LOCATION NOTICEInstallation Items Needed INSTALLINGCONNECTING FIREPLACE TO GAS SUPPLY ContinuedNOTICE G 001WARNINGINSTALLING ContinuedContinued INSTALLINGPressure Testing Fireplace Gas Connections ContinuedFigure 21 - Installing Rear Log INSTALLINGINSTALLING LOGS Figure 22 - Installing Front LogContinued INSTALLINGFigure 23 - Installing Crossover Log ContinuedINSTALLING FOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING FIREPLACE ContinuedNOTICE OPERATINGFIREPLACE LIGHTING INSTRUCTIONSVARIABLE OUTPUT CONTROL OPERATION MANUAL LIGHTING PROCEDURETO TURN OFF GAS TO APPLIANCE OPERATING FIREPLACENOTICE INSPECTINGBURNERS PILOT FLAME PATTERNCLEANING AND MAINTENANCE TROUBLE SHOOTING ODS/PILOT AND BURNERSLOGS Continued TROUBLE- SHOOTINGCleaning and Mainte ContinuedCleaning and Mainte TROUBLE SHOOTINGCleaning and Mainte Cleaning and MainteContinued TROUBLESHOOTING leaks see Checking GasWhen gas pressure is too low TECHNICAL SERVICE SERVICE HINTSREPLACEMENT PARTS SPECIFICATIONS When gas quality is badGMC12U - Unfinished ACCESSORIESCABINET MANTEL GMC11F - Walnut Finished HEARTH BASE GC3333F- Walnut FinishedPARTS Log Base AssemblyILLUSTRATED BREAKDOWNPART NUMBER PARTS LISTLog Base Assembly DESCRIPTIONPARTS FireplaceILLUSTRATED BREAKDOWNPART NUMBER PARTS LISTFireplace DESCRIPTIONWARRANTY INFORMATION LIMITED WARRANTY VENT-FREENATURAL GAS FIREPLACEKEEP THIS WARRANTY