Desa UNVENTED (VENT-FREE) NATURAL GAS FIREPLACE G 001WARNING, Installing, Notice, Continued

Page 18
CHECKING GAS CONNECTIONS

INSTALLING

Continued

18

4.Route flexible gas line from manual shutoff valve into fireplace through side or rear access panel. Route flexible gas supply line through fireplace access door.

NOTICE

Most building codes do not permit concealed gas connections. A flexible gas line is provided to allow accessibility from the fireplace. The flexible gas supply line connection to the manual shutoff valve should be accessible.

5.Apply pipe joint sealant lightly to male threads of gas connector attached to flexible gas line (see Figure 18). Connect flexible gas line to flexible gas line attached to gas regulator of fireplace (see Figure 18).

6.Check all gas connections for leaks. See Checking Gas Connections, below.

7.Replace log base assembly back into fireplace. Feed flexible gas line into fireplace base area while replacing log base assembly. Make sure the entire flexible gas line is in fireplace base area. Reattach log base assembly to fire- place with screws removed in step 3.

To Fireplace

 

 

 

 

Gas Regulator

Gas Connector

Manual Shutoff Valve

 

Flexible Gas Line

 

 

 

 

from Fireplace Gas

 

 

 

To Gas

Regulator

 

Flexible Gas Line from

Meter

 

 

Manual Shutoff Valve

 

 

 

 

 

Figure 18 - Attaching Flexible Gas Lines Together

CHECKING GAS CONNECTIONS

 

 

 

WARNING ICON

G 001WARNING

 

 

Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.

WARNING

WARNING ICON

G 001

Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG

1.Disconnect fireplace and its individual manual shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage fireplace gas regula- tor.

2.Cap off open end of gas pipe where manual shutoff valve was connected.

3.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Re-connect fireplace and manual shutoff valve to gas supply. Check re-con-

nected fittings for leaks.

101742

Image 18
Contents OWNER’S OPERATION AND INSTALLATION MANUAL Save this manual for future referenceUNVENTED VENT-FREENATURAL GAS FIREPLACE DANGER CONTENTS SAFETY INFORMATIONWARNINGS Safety Information continues on next pageSAFETY INFORMATIONContinued PRODUCT IDENTIFICATION Figure 1 - Log Base AssemblyFigure 2 - Fireplace Operation LOCAL CODES UNPACKING PRODUCT FEATURESSafety Device Piezo Ignition SystemAIR FOR COMBUSTION AND VENTILATION PROVIDING ADEQUATE VENTILATIONCOMBUSTION AIR FORVENTILATION ContinuedVENTILATION AIR AIR FOR COMBUSTION AND VENTILATIONContinued Ventilation Air from Inside BuildingINSTALLING NOTICEContinued INSTALLING ContinuedASSEMBLING AND ATTACHING BRASS TRIM Continued INSTALLINGINSTALLATION CLEARANCES CONVENTIONAL FIREPLACE INSTALLATIONINSTALLING Continuedheads and putty over Continued INSTALLINGBUILT-INFIREPLACE INSTALLATION ContinuedContinued INSTALLINGFigure 13 - Attaching Nailing Flange Accessory 39 3/8 27 7/8 35 1/2 55 5/8Continued INSTALLINGMantel Clearances for Built-InInstallation ContinuedInstallation Items Needed INSTALLINGINSTALLING GAS PIPING TO FIREPLACE LOCATION NOTICEInstallation Items Needed INSTALLINGCONNECTING FIREPLACE TO GAS SUPPLY ContinuedNOTICE G 001WARNINGINSTALLING ContinuedContinued INSTALLINGPressure Testing Fireplace Gas Connections ContinuedFigure 21 - Installing Rear Log INSTALLINGINSTALLING LOGS Figure 22 - Installing Front LogContinued INSTALLINGFigure 23 - Installing Crossover Log ContinuedINSTALLING FOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING FIREPLACE ContinuedNOTICE OPERATINGFIREPLACE LIGHTING INSTRUCTIONSVARIABLE OUTPUT CONTROL OPERATION MANUAL LIGHTING PROCEDURETO TURN OFF GAS TO APPLIANCE OPERATING FIREPLACENOTICE INSPECTINGBURNERS PILOT FLAME PATTERNCLEANING AND MAINTENANCE TROUBLE SHOOTING ODS/PILOT AND BURNERSLOGS Continued TROUBLE- SHOOTINGCleaning and Mainte ContinuedCleaning and Mainte TROUBLE SHOOTINGCleaning and Mainte Cleaning and MainteContinued TROUBLESHOOTING leaks see Checking GasWhen gas pressure is too low TECHNICAL SERVICE SERVICE HINTSREPLACEMENT PARTS SPECIFICATIONS When gas quality is badGMC12U - Unfinished ACCESSORIESCABINET MANTEL GMC11F - Walnut Finished HEARTH BASE GC3333F- Walnut FinishedPARTS Log Base AssemblyILLUSTRATED BREAKDOWNPART NUMBER PARTS LISTLog Base Assembly DESCRIPTIONPARTS FireplaceILLUSTRATED BREAKDOWNPART NUMBER PARTS LISTFireplace DESCRIPTIONWARRANTY INFORMATION LIMITED WARRANTY VENT-FREENATURAL GAS FIREPLACEKEEP THIS WARRANTY