14
TROUBLE SHOOTING GUIDE
BEFORE ATTEMPTING TO TROUBLESHOOT, PURGE YOUR UNIT AND INITIALLY LIGHT THE PILOT AND THE MAIN BURNER WITH THE GLASS DOOR REMOVED.
SYMPTOM |
| PROBLEM |
| TEST SOLUTION |
|
|
|
|
|
|
|
| |
|
|
|
|
|
| |
Pilot will not light. | No spark at pilot burner | - | check if pilot can be lit by a match |
|
| |
|
|
| - | check that the wire is connected to the push button ignitor. |
|
|
|
|
| - | check if the push button ignitor needs tightening. |
|
|
|
|
| - | replace the push button ignitor. |
|
|
|
|
|
|
|
| |
| Spark gap is incorrect | - spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.) |
|
| ||
| from the electrode tip and the pilot burner. |
|
| |||
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| No gas at the pilot burner | - | check that the manual valve is turned on. |
|
|
|
|
| - | check the pilot orifice for blockage. |
|
|
|
|
| - | replace the valve. |
|
|
|
|
| - | call the gas distributor. |
|
|
|
|
|
|
|
| |
| Out of propane gas. | - | fill the tank. |
|
|
Pilot goes out when the gas knob is re- leased.
System is not correctly purged. - purge the gas line with the glass door open.
| Out of propane gas | - | fill the tank. | |
|
|
|
| |
Pilot flame is not large enough | - | turn up the pilot flame. | ||
Pilot flame is not engulfing the | - | turn up pilot flame. | ||
thermocouple. | - | replace pilot assembly. | ||
|
|
|
|
|
| Thermocouple shorting. | - | loosen and tighten thermocouple. | |
|
| - | clean thermocouple and valve connection. | |
|
| - | replace thermocouple. | |
|
| - | replace valve. |
Pilot burning; no gas to main burner; gas knob is on 'HI'; wall switch / thermostat is on.
| Faultly thermocouple. | - | replace. |
| |
Faulty valve. | - | replace. | |||
|
| Main burner orifice is plugged. | - | remove stoppage in orifice. | |
|
|
|
|
|
|
|
| Faulty thermopile. | - | replace. | |
|
| Faulty themostat or switch. | - | connect a jumper wire across the wall switch terminals; if | |
|
|
| main burner lights, replace thermostat. | ||
|
|
| - | disconnect the switch wires & connect a jumper wire across | |
|
|
| terminals 1 & 3; if the main burner lights, check the wires for | ||
|
|
| defects and / or replace wires. |
Faulty valve. | - | replace. |
|
|
|
Pilot goes out while Gas piping is undersized. | - | turn on all gas appliances and see if pilot flame flutters, |
standing; Main burner | diminishes or extinguishes, especially when main burner ig- | |
is in 'OFF' position. | nites. Monitor supply pressure. | |
| - | check if supply piping size is to code. Correct all undersized |
piping.
Main burner goes out; pilot stays on.
Pilot flame is not large enough - | turn up pilot flame. | |
or not engulfing the thermopile. - replace pilot assembly. | ||
|
|
|
Thermopile shorting | - | clean thermopile and thermopile connection to valve. |
Remote wall switch wire is too - shorten wire to correct length or wire gauge. long, too much resistance in
the system
Faulty thermostat or switch | - replace |