REQUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1.INSTALLATIONOFCARBONMONOXIDEDETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a.In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b.In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/

UL 2034 listed and IAS certified.

3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS”.

4.INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

(b)EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(d)MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies

“special venting systems”, the following requirements shall be satisfied by the manufacturer:

1.The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2.The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instruction.

(e)A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

24820-1-0409

Page 5

Image 5
Contents Empire Table of Contents This is a Heating Appliance Important Safety InformationLP-GAS Warning Odor Safety Information for Users of LP-GASVent Directly BELOW. Keep Clear of ALL Obstructions Requirements for MassachusettsPressure Testing of the Gas Supply System Installing a New Main Gas CockGAS Supply Recommended Gas Pipe DiameterIntroduction Installation Instructions General Safety Information SpecificationsInstallation on Rugs and Tile Heater Installation for Direct VentClearances for Direct Vent Locating Wall OpeningClearances for Single Flue Heater Installation for Single FlueHeater with Pedestal and Single Flue Adaptor Heater without pedestal SpecificationsFireplace Insert with Mantel Surround with Slim Top Panel Fireplace Insert with Mantel Surround with Short Top Panel Freestanding Units Clearance to CombustiblesInsert Into Masonry Fireplace Rough Framing DimensionsWall Clearances Log Installation All Logs LOG SET Installation InstructionsVent Examples for Single Flue Single Flue Vertical Vent Run Shroud Kit Model# Pvsh Venting for Existing Fireplace InstallationSingle Flue Venting with Shroud Installed Single Flue Vertical Vent Run With 45 degree elbows Determining Minimum Vent Height AboveRoof Determining Minimum Vent Height Above the Roof PVVK-CFA Flex Vent KITAvailable from Empire Comfort Systems, Inc PVVK-SH Horizontal Vent Adaptor KIT Horizontal Examples for Colinear Direct Vent Vertical Examples for Colinear Direct Vent Colinear Direct Vent Pitched Roof Installation Colinear adaptor Pvca Horizontal Colinear Direct Vent AdaptorTermination Cap Pvvtc Termination CAP Vent KITHorizontal Application Pvct Colinear Transition Vent KITFlat Roof or Chimney Application Direct Vent System Building Exterior View Direct Vent Installation InstructionsHorizontal Venting Minimum Exterior Grade Dimension Unit With Pedestal Minimum Exterior Grade Dimension Unit Without PedestalStep PVVK-24H and PVVK-48H Vent KITPVVK-24H and PVVK-48H Vent KIT GAS Connection Line Supply GAS Connection Installation InstructionsOperating Instructions Checklist Lighting Instructions For Your Safety Read Before Lighting FAN Operation Conversion Instructions from LP Propane GAS to Natural GAS GAS Conversion InstructionsConversion Instructions from Natural GAS to LP Propane GAS Automatic Humidifier Operation Optional Controllers Installation Instruction for TMV2 Two Stage Thermostat ModelEconomy Display Mode Wiring Diagram WiringOver Temperature Cut Out MaintenanceGeneral Information Paint Curing First FiringGlass Assembly Replacement Front door removal drawing Glass CleaningMain Burner Drawing Cleaning Main Burner General Glass InformationLOG Placement Unit Operating FaultsResetting the Heater Heat Exchanger Surround Installation InstructionsMain Convection FAN Optional Pedestal Assembly Installation Pedestal Installation InstructionsIndex Part Number Description Parts ListGAS Line Rear Parts View Parts View Purchase Date Dealer Name/Phone Warranty TermsParts Not Under Warranty HOW to Order Repair PartsWarranty Parts Master Parts Distributor ListComfort Systems