Empire Comfort Systems DVP42FP3(0,1,2,3)(N,P)-1, DVP48FP3(0,1,2,3)(N,P)-1 ARC Length Action

Page 39

Important

1.The following service procedures are provided as a general guide.

2.Meter readings between gas control and ignition module must be taken within the trial for ignition period. Once the igni- tion module locks out, the system must be reset by setting the thermostat down for at least one minute before continuing.

3.If any component does not function properly, make sure it is correctly installed and wired before replacing it.

4.The ignition module cannot be repaired. If it malfunctions, it must be replaced.

5.Only trained, experienced service technicians should service intermittent pilot systems.

Perform the CHECKOUT steps on page 37 as the first step in troubleshooting. Then check TROUBLESHOOTING GUIDE to pinpoint the cause of the problem. If troubleshooting indicates an ignition problem, see Ignition System Checks below to isolate and correct the problem.

Following troubleshooting, perform the CHECKOUT procedure (page 37 ) again to be sure system is operating normally.

Ignition System Checks Step 1: Check ignition cable. Make sure:

A.Ignition cable does not touch any metal surfaces.

B.Ignition cable is no more than 36 inches long.

C.Connections to the ignition module and to the igniter-sensor are clean and tight.

D.Ignition cable provides good electrical continuity.

Step 2: Check ignition system grounding.

Nuisance shutdowns are often caused by a poor or erratic ground.

A.Acommon ground, usually supplied by the pilot burner bracket, is required for the module and the pilot burner/igniter sen- sor.

Check for good metal-to-metal contact between the pilot burner bracket and the main burner.

Check the ground lead from GND (BURNER) terminal on the module to the pilot burner. Make sure connections are clean and tight. If the wire is damaged or deteriorated, replace it with No. 14-18 gauge, moisture-resistant, thermoplastic insulated wire with 105 C (221 F) minimum rating.

If flame rod or bracket are bent out of position, restore to correct position.

Replace pilot burner/igniter sensor if insulator is cracked.

Step 3: Check spark ignition circuit. You will need a short jumper wire made from ignition cable or other heavily insulated wire.

A.Close the manual gas valve.

B.Disconnect the ignition cable at the SPARK terminal on the module.

WARNING

When performing the following steps, do not touch stripped end of jumper or SPARK terminal. The ignition circuit generates 13,000 volts at 25 pf load and electrical shock can result.

C.Energize the module and immediately touch one end of the jumper firmly to the GND terminal on the module. Move the free end of the jumper slowly toward the SPARK terminal until a spark is established.

D.Pull the jumper slowly away from the terminal and note the length of the gap when sparking stops. Check table below.

ARC LENGTH

ACTION

No arc or arc less

Check external fuse, if

than 1/8 inch.

provided.

 

Verify power and module

 

input terminal.

 

Replace module if fuse and

 

power okay.

Arc 1/8 inch or longer

Voltage output is okay.

Step 4: Check pilot flame current.

A.Turn off furnace at thermostat.

B.Disconnect main valve wire from the TH or MV terminal on the gas control.

C.Disconnect ground wire from GND (BURNER) terminal at module.

D.Connect a meter (dc microamp scale) in series with the ground lead.

Disconnect ground lead from GND terminal on ignition module.

Connect the black (negative) meter lead to the ignition module GND (BURNER) terminal.

Connect the red (positive) meter lead to the free end of the ground lead.

E.Set thermostat to call for heat. The spark will light the pilot but the main burner will not light because the main valve actuator is disconnected.

F.Read the meter. The flame sensor current must be steady and at least 1.0 uA.

G.If the reading is less than the minimum or unsteady,

Make sure pilot flame envelopes 3/8 to 1/2 inch of the flame rod.

If necessary, adjust pilot flame by turning the pilot adjustment screw on the gas control clockwise to decrease or counter- clockwise to increase pilot flame. Following adjustment, always replace pilot adjustment cover screw and tighten firmly to assure proper gas control operation.

Check for cracked ceramic insulator, which can cause short to ground, and replace igniter-sensor if necessary.

Make sure electrical connections are clean and tight. Replace damaged wire with moisture-resistant No. 18 wire rated for continuous duty up to 105 C (221 F).

H.Remove meter and reconnect all wires. Return system to normal operation before leaving job.

17375-10-0706

Page 39

Image 39
Contents Effective Date Millivolt Standing PilotIntermittent Pilot Remote RF ModelsMain Title Important Safety Information LP-GAS Warning Odor No Odor Detected Odor FadeSome Points to Remember Vent Directly BELOW. Keep Clear of ALL Obstructions Requirements for MassachusettsIntroduction Fireplace Dimensions SpecificationsLocating Fireplace ClearancesInstalling a New Main Gas Cock GAS SupplyChecking Manifold Pressures Converting flue take-off to rear venting Rear Vent ConversionInstallation Framing and FinishingVent Pipe Clearance Flush Mount Mantel Installation Figure Framing FigureFinishing Figures 12 VERTICAL, 90 Elbow with Horizontal Termination Flush Wall InstallationCombustible Surround Installation Vent Runs Figures 14, 15, 16, 17Model VERTICAL, 90 Elbow to Horizontal OUT the WallExample B Venting Fireplace TOPTo Use the Vent Graph Figure Example aTypical Basement Installation Below Grade InstallationCutting the Hole Figures Positioning the FireplaceExamples TOP Vent RUN Venting Fireplace Rear Dimensions in FeetExamples Rear Vent RUN Vertical Sidewall Installations Termination ClearancesInformation on Various Venting Routes and Components Vent Clearances Vent System Identification Installing Vent Components FigureFraming and Finishing Installing Support Brackets FigureSee Horizontal Termination Page 25 and Vertical Termination Horizontal TerminationDVVK-5F Flex Vent Instructions InstallationDetermining Minimum Vent Height Above the Roof General MaintenanceInstalling the Vent System in a Chase Vertical TerminationVertical Termination Reassembly and Resealing Vent Pipe SystemLOG Placement 3 LOG SET Pilot Flame Figure Operating InstructionsMillivolt System Initial LightingTRW Standing Pilot Wiring Diagram Standing Pilot Lighting Instructions For Your SAFETY, Read Before LightingGlass soots Standing Pilot TroubleshootingFrequent pilot outage problem Pilot and main burner extinguish while in operationIntermittent Pilot Wiring Diagram Intermittent Pilot Operating InstructionsElectrical Connection Figure Damage, personal injury or loss of life Intermittent Pilot Lighting InsturctionsOperation Intermittent Pilot TroubleshootingS8600H Intermittent Ignition Module Specifications CheckoutMain Burner Operation Safety LockoutIgnition System Checks Check ignition cable. Make sure ARC Length ActionIntermittent Pilot Troubleshooting RF Standing Pilot Operating Instructions Status Action RF Transmitter FunctionsRF Wiring Diagram Wiring Diagram with BlowerWhat to do if YOU Smell GAS RF Standing Pilot Lighting InstructionsMaintenance and Service Parts View Index Part Number Description DVP42 DVP48 Parts ListParts List FBB4 Optional Variable Speed Blower Installation Blower MotorBlower Wheels Volt AC Optional Brick Liner Installation Instructions Junction BOX Wiring Installation InstructionsFBB4 AccessoriesService Notes HOW to Order Repair Parts Service Notes Service Notes 17375-10-0706

DVP42FP3(0,1,2,3)(N,P)-1, DVP42FP9(1,3)(N,P)-1, DVP48FP7(0,1,2,3)(N,P)-1, DVP48FP3(0,1,2,3)(N,P)-1, DVP48FP9(1,3)(N,P)-1 specifications

Empire Comfort Systems is a well-established name in the heating and comfort industry, and their line of direct vent gas fireplaces is a testament to their commitment to quality, efficiency, and innovative design. Among their offerings, models such as the DVP42FP9(1,3)(N,P)-1, DVP42FP7(0,1,2,3)(N,P)-1, DVP48FP9(1,3)(N,P)-1, DVP48FP7(0,1,2,3)(N,P)-1, and DVP42FP3(0,1,2,3)(N,P)-1 stand out for their remarkable features and technologies.

One of the key characteristics of these models is their direct vent technology, which allows them to draw in air from outside for combustion while venting exhaust safely outside. This feature enhances safety and efficiency, making them suitable for a variety of home environments. The models are equipped with adjustable flame control, allowing users to customize the ambiance according to their preferences, whether they seek a cozy, intimate setting or a more vibrant and warm atmosphere.

The DVP series is designed for easy installation and flexibility in placement, offering venting options that can accommodate different room layouts. The fireplaces feature easy-to-use electronic ignitions, alongside manual controls, ensuring reliability and ease of operation. Furthermore, the units are compatible with both natural gas and propane, providing versatility depending on the homeowner's fuel preferences.

Another crucial aspect of these models is their focus on energy efficiency. With advanced combustion systems, they maximize heat output while minimizing gas consumption, making them an environmentally friendly option. The fireplaces produce a significant amount of BTUs, providing adequate heating for various room sizes, while also featuring efficient heat distribution systems that ensure warmth reaches every corner.

Aesthetic appeal is not compromised with the DVP series. These fireplaces come with a variety of attractive front designs, media options such as logs or crystals, and customizable trim finishes. This versatility allows homeowners to select a unit that complements their interior décor seamlessly.

In summary, Empire Comfort Systems' DVP42FP9, DVP42FP7, DVP48FP9, DVP48FP7, and DVP42FP3 models boast advanced technologies, energy efficiency, and aesthetic versatility. Each unit embodies comfort and modernity, making them an excellent addition to any home looking to enhance its heating solution while maintaining an elegant and welcoming atmosphere. With a focus on safety, user-friendliness, and design, these direct vent gas fireplaces continue to set a standard in the heating industry.