Empire Comfort Systems DVP42FP3(0,1,2,3)(N,P)-1 GAS Supply, Installing a New Main Gas Cock

Page 9

GAS SUPPLY

The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Tubing, Type L

 

Inside Diameter

Outside Diameter

 

 

 

 

 

 

Nat.

L.P.

Nat.

L.P.

 

 

 

 

 

0-10ft

1/2"

3/8"

1/2"

3/8"

0-3m

12.7mm

9.5mm

12.7mm

9.5mm

 

 

 

 

 

11-40ft

1/2"

1/2"

5/8"

1/2"

4-12m

12.7mm

12.7mm

15.9mm

12.7mm

 

 

 

 

 

41-100ft

1/2"

1/2"

3/4"

1/2"

13-30m

12.7mm

12.7mm

19mm

12.7mm

 

 

 

 

 

101-150ft

3/4"

1/2"

7/8"

3/4"

31-46m

19mm

12.7mm

22.2mm

1.9 mm

 

 

 

 

 

Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:

ANS Z21.24Appliance Connectors of Corrugated MetalTubing and Fittings.

ANS Z21.45 Assembled Flexible Appliance Connectors of Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority having jurisdiction.The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.

 

 

Figure 6

 

 

 

 

 

 

Gas Supply Pressure (inches w.c.)

 

 

 

 

 

 

Minimum

Normal

 

Maximum

 

 

 

 

 

Natural Gas

4.5"

7.0"

 

*14.0"

 

 

 

 

 

LP (Propane)

10.8"

11.0"

 

*14.0"

 

 

 

 

 

Manifold Pressure (inches w.c.)

 

 

 

 

 

 

Normal (HI)

 

 

 

 

 

 

Natural Gas

 

3.5"

 

 

 

 

 

 

 

LP (Propane)

 

10.0"

 

 

*NOTE: Remote "RF" Models - 10.5" w.c. maximum

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not ad- equate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

NOTE: The millivolt gas controls are equipped with a captured screw type pressure test point, therefore it is not necessary to provide a 1/8" test point up stream of the control.

Ondirectignitionvalves,hexplugsmaybereplacedwithhosefittings for pressure checks, then reinstalled before operating fireplace.

When using copper or flex connector use only approved fittings.

The appliance and it’s individual shut off valve must be disconnected from supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa).

The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa).

Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result in a hazardous condition.

Checking Manifold Pressures

Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 14.0" w.c. (3.484kPa). Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet

with the inlet pressure to the valve from a minimum of 10.8" w.c. (2.68kPa) for the purpose of input adjustment to a maximum

of 14.0" w.c. (3.484kPa).

Figure 7

17375-10-0706

Page 9

Image 9
Contents Intermittent Pilot Millivolt Standing PilotRemote RF Models Effective DateMain Title Important Safety Information LP-GAS Warning Odor No Odor Detected Odor FadeSome Points to Remember Vent Directly BELOW. Keep Clear of ALL Obstructions Requirements for MassachusettsIntroduction Fireplace Dimensions SpecificationsLocating Fireplace ClearancesInstalling a New Main Gas Cock GAS SupplyChecking Manifold Pressures Converting flue take-off to rear venting Rear Vent ConversionInstallation Framing and FinishingVent Pipe Clearance Flush Mount Mantel Installation Figure Framing FigureFinishing Figures 12 Combustible Surround Installation Flush Wall InstallationVent Runs Figures 14, 15, 16, 17 VERTICAL, 90 Elbow with Horizontal TerminationModel VERTICAL, 90 Elbow to Horizontal OUT the WallTo Use the Vent Graph Figure Venting Fireplace TOPExample a Example BTypical Basement Installation Below Grade InstallationCutting the Hole Figures Positioning the FireplaceExamples TOP Vent RUN Venting Fireplace Rear Dimensions in FeetExamples Rear Vent RUN Vertical Sidewall Installations Termination ClearancesInformation on Various Venting Routes and Components Vent Clearances Vent System Identification Installing Vent Components FigureFraming and Finishing Installing Support Brackets FigureSee Horizontal Termination Page 25 and Vertical Termination Horizontal TerminationDVVK-5F Flex Vent Instructions InstallationInstalling the Vent System in a Chase General MaintenanceVertical Termination Determining Minimum Vent Height Above the RoofVertical Termination Reassembly and Resealing Vent Pipe SystemLOG Placement 3 LOG SET Millivolt System Operating InstructionsInitial Lighting Pilot Flame FigureTRW Standing Pilot Wiring Diagram Standing Pilot Lighting Instructions For Your SAFETY, Read Before LightingFrequent pilot outage problem Standing Pilot TroubleshootingPilot and main burner extinguish while in operation Glass sootsIntermittent Pilot Wiring Diagram Intermittent Pilot Operating InstructionsElectrical Connection Figure Damage, personal injury or loss of life Intermittent Pilot Lighting InsturctionsS8600H Intermittent Ignition Module Specifications Intermittent Pilot TroubleshootingCheckout OperationMain Burner Operation Safety LockoutIgnition System Checks Check ignition cable. Make sure ARC Length ActionIntermittent Pilot Troubleshooting RF Standing Pilot Operating Instructions Status Action RF Transmitter FunctionsRF Wiring Diagram Wiring Diagram with BlowerWhat to do if YOU Smell GAS RF Standing Pilot Lighting InstructionsMaintenance and Service Parts View Index Part Number Description DVP42 DVP48 Parts ListParts List FBB4 Optional Variable Speed Blower Installation Blower MotorBlower Wheels Volt AC Optional Brick Liner Installation Instructions Junction BOX Wiring Installation InstructionsFBB4 AccessoriesService Notes HOW to Order Repair Parts Service Notes Service Notes 17375-10-0706

DVP42FP3(0,1,2,3)(N,P)-1, DVP42FP9(1,3)(N,P)-1, DVP48FP7(0,1,2,3)(N,P)-1, DVP48FP3(0,1,2,3)(N,P)-1, DVP48FP9(1,3)(N,P)-1 specifications

Empire Comfort Systems is a well-established name in the heating and comfort industry, and their line of direct vent gas fireplaces is a testament to their commitment to quality, efficiency, and innovative design. Among their offerings, models such as the DVP42FP9(1,3)(N,P)-1, DVP42FP7(0,1,2,3)(N,P)-1, DVP48FP9(1,3)(N,P)-1, DVP48FP7(0,1,2,3)(N,P)-1, and DVP42FP3(0,1,2,3)(N,P)-1 stand out for their remarkable features and technologies.

One of the key characteristics of these models is their direct vent technology, which allows them to draw in air from outside for combustion while venting exhaust safely outside. This feature enhances safety and efficiency, making them suitable for a variety of home environments. The models are equipped with adjustable flame control, allowing users to customize the ambiance according to their preferences, whether they seek a cozy, intimate setting or a more vibrant and warm atmosphere.

The DVP series is designed for easy installation and flexibility in placement, offering venting options that can accommodate different room layouts. The fireplaces feature easy-to-use electronic ignitions, alongside manual controls, ensuring reliability and ease of operation. Furthermore, the units are compatible with both natural gas and propane, providing versatility depending on the homeowner's fuel preferences.

Another crucial aspect of these models is their focus on energy efficiency. With advanced combustion systems, they maximize heat output while minimizing gas consumption, making them an environmentally friendly option. The fireplaces produce a significant amount of BTUs, providing adequate heating for various room sizes, while also featuring efficient heat distribution systems that ensure warmth reaches every corner.

Aesthetic appeal is not compromised with the DVP series. These fireplaces come with a variety of attractive front designs, media options such as logs or crystals, and customizable trim finishes. This versatility allows homeowners to select a unit that complements their interior décor seamlessly.

In summary, Empire Comfort Systems' DVP42FP9, DVP42FP7, DVP48FP9, DVP48FP7, and DVP42FP3 models boast advanced technologies, energy efficiency, and aesthetic versatility. Each unit embodies comfort and modernity, making them an excellent addition to any home looking to enhance its heating solution while maintaining an elegant and welcoming atmosphere. With a focus on safety, user-friendliness, and design, these direct vent gas fireplaces continue to set a standard in the heating industry.