Page 13

Twist Lock Pipes

When using twist lock pipe it is not necessary to use sealant on the joints. The only areas of the venting system that need to be sealed with high temperature silicone sealant are the collars on the fireplace and termination, and the sliding joint of any telescopic vent section used in the system.

To join twist lock pipes together, simply align the beads of the male end with the grooves of the female end, twisting the pipe until the flange on the female end contacts external flange on the male end. It is recom- mended that you secure the joints with three (3) sheet metal screws, however, this is not mandatory with twist lock pipe. (Fig. 17)

To make it easier to assembly the joints, we suggest putting a lubricant (Vaseline or similar) on the male end of the twist lock pipe prior to assembly.

Male End

 

Female

 

 

End

 

 

 

 

 

 

Screw Holes

TWL100

Fig. 17 Twist-Lock pipe joints.

How to Use the Vent Graph

The Vent Graph should be read in conjunction with the following vent installation instructions to determine the relationship between the vertical and horizontal dimen- sions fo the vent system.

1.Determine the height of the center of the horizontal vent pipe exiting through the outer wall. Using this dimension on the Sidewall Vent Graph (Fig. 17), locate the point intersecting with the slanted graph line.

2.From the point of this intersection, draw a vertical line to the bottom of the graph.

3.Select the indicated dimension, and position the fireplace in accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 11’ (3.4m) the horizontal run to the face of the outer wall must not exceed 14’ (4.3m).

EXAMPLE B:

If the vertical dimension from the floor of the unit is 7’ (2.1m), the horizontal run to the face of the outer wall must not exceed 8¹⁄₂’ (2.6m).

DVRT41Direct Vent Gas Fireplace

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

theto

Vertical

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

centerofhorizontalthe ventpipe

dimensionfrom floorunitthetheof

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

eg: A

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

eg: B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

4

5

6

7

8

9

10 11

12

13

14

15

16

17

18

19

20

 

Horizontal dimension from the outside face of the wall to the

center of the fireplace vent flange

Fig. 18 Sidewall venting graph. (Dimensions in feet.)

Refer to Page 19 for venting requirements for snorkels.

Rear Wall Vent Application

When installed as a rear vent unit this appliance may be vented directly to a termination located on the rear wall behind the appliance.

Only CFM Corporation venting components are approved to be used in these applications (See ‘Venting Components’ listed for different installation requirements).

The maximum horizontal distance between the rear of the appliance (or end of the transition elbow in a corner application) and the outside face of the rear wall is 20” (508mm). (Fig. 19, 20)

Only one 45° elbow is allowed in these installations.

Minimum clearances between vent pipe and com- bustible materials are as follows:

Top - 2" (51 mm)

Sides - 1" (25 mm)

Bottom - 1" (25 mm)

10006740

13

Image 13
Contents Direct Vent Model DVRT41 Table of Contents Locating Your Fireplace Installation & Operating InstructionsFraming Dimensions Fireplace Dimensions Installed as Top VentFireplace Dimensions Installed as Rear Vent Clearance to Combustibles Mantel ChartMantels HearthGas Line Installation Gas SpecificationsFraming And Finishing Gas Inlet and Manifold PressuresRemote ON/OFF Switch Installation Alternate Switch LocationEB-1 Electrical Box EB-1 receptacle Optional Top Vent ApplicationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2USA Installations Canadian InstallationsGeneral Information Assembling Vent Pipes Flex Vent PipesTwist Lock Pipes How to Use the Vent GraphRear Wall Vent Application Step Rear Wall Vent InstallationVertical Sidewall Application Rear Wall Vent Installations Flex Vent PipeMaximum vent run with elbows Total angular variation 270Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeStep Vertical Sidewall Installation Flex Vent PipeVertical Through-the-Roof Application Below Grade InstallationPlace firestop spacers and secure Vertical Through-the-Roof InstallationTypical Roof SupportTypical Ceiling ApplicationSupport Venting Components Operating Instructions Log Identification Chart Installation of LogsBurner Lava Rock Placement Flame & Temperature AdjustmentInspecting the Venting System Flame CharacteristicsSIT 820 Valve To Turn Off Gas To Heater Lighting and Operating InstructionsLighting Instructions Lighting & Operating InstructionsTurning Off the Gas to the Appliance Transmitter Operation Off Mode Shut Off ProcedureOn Manual Mode Instructions for RF Comfort Control ValveAuto Mode Delay Timer ModeFan Override During Auto Mode Change Between F/C Temperature UnitsAuto Path LED Count Service ActionOn Path Local PathWindow Frame Assembly to be Removed Before Service Work Troubleshooting Honeywell VS8421SIT Nova 820 Millivolt Valve Trouble Shooting the Gas Control SystemSIT 822 Valve with a Honeywell Electronic Igniter Troubleshooting the Gas Control SystemNova SIT820 Valve Burner and Pilot Orifice ConversionConversion Procedure Installation PrecautionsLogs may be hot Depressd and turn center plunger Cleaning the Standing Pilot Control System MaintenanceLogs May Be HOT Burner and Burner CompartmentDVRT41 Description DVRT41DVRT41 LP to Natural Gas Fuel Conversion Kits Natural Gas to LPFK12 Fan Assembly Optional Accessories AvailableFK24 Fan Assembly Hard Direct Wire Hook UpCeramic Refractory Panels Remote ControlsDecorative Bay Windows Decorative Frame TrimConversion Instructions For Use in Mobile Homes Model DVRT41RMH9b.Units with Honeywell valve Limited Lifetime Warranty Model EnerGuide Ratings Efficiency RatingsState % Fireplace Efficiency % Fan-OFF Fan-ON

DVRT41 specifications

The Vermont Casting DVRT41 is a remarkable gas fireplace that harmoniously combines contemporary aesthetics with advanced heating technology. Designed to enhance any living space, the DVRT41 stands out with its impressive features and functionality, making it a popular choice for those looking to elevate their home environment.

One of the most notable features of the DVRT41 is its efficient heat output. With an impressive BTU range, this fireplace can warm spaces effectively while maintaining low emissions. This efficiency is complemented by Vermont Castings' commitment to sustainability, ensuring that the DVRT41 aligns with environmental considerations.

Aesthetically, the DVRT41 offers a customizable experience. Consumers can choose from various faceplate designs, glass door styles, and finishes to match any décor. The fireplace’s large viewing area provides an unobstructed view of the flames, creating a cozy atmosphere that’s perfect for gatherings or quiet evenings.

The DVRT41 incorporates advanced technologies aimed at maximizing user experience. The fireplace features an intuitive remote control for convenience, allowing users to adjust flame height and heat output easily. This adaptability ensures that homeowners can create the perfect ambiance at any time. The ignition system is designed for reliability and ease, ensuring that starting the fireplace is hassle-free, even in challenging conditions.

Safety is a top priority with the DVRT41. The unit includes features such as a safety shut-off system and a tempered glass front to prevent accidental burns. Additionally, the design allows for efficient venting, minimizing the risk of backdraft or buildup of harmful gases.

Maintenance is straightforward, thanks to the unit's design. The DVRT41 is constructed with durable materials that resist corrosion and wear, ensuring longevity and reduced upkeep costs. Regular cleaning is simple, ensuring that the fireplace remains functional and beautiful for years to come.

Overall, the Vermont Casting DVRT41 gas fireplace is not only a source of warmth but also a stunning focal point within any home. Its blend of efficiency, safety, and design flexibility make it a top choice for homeowners seeking an effective heating solution that doesn’t compromise on style or substance. The DVRT41 exemplifies Vermont Castings' commitment to quality, ensuring that every unit delivers exceptional performance and aesthetic appeal.