Vermont Casting DVRT41 manual Vertical Sidewall Installation Twist Lock Pipe

Page 17

Vertical Sidewall Installation

Twist Lock Pipe

Step 1

Locate vent opening on the wall. It may be necessary to first position the fireplace and measure to obtain hole location. Depending on whether the wall is com- bustible or noncombustible, cut opening to size. (Fig. 31) (For combustible walls first frame in opening.)

NOTE: When using flex vent, the opening will have to be measured according to the 1/2” (13mm) rise in 12” (305mm) vent run.

Combustible Walls: Cut a 9³⁄₈”H x 9³⁄₈”W (240mm x 240mm) hole through the exterior wall and frame as shown. (Fig. 31)

Noncombustible Walls: Hole opening must be 7¹⁄₂” (191mm) in diameter.

 

Vent Opening for Combustible Wall

 

 

9³⁄₈"

 

 

(240mm)

 

9³⁄₈"

 

 

(240mm)

 

 

Framing Detail

 

Fireplace Hearth

 

 

Vent Opening Noncombustible Wall

 

 

7¹⁄₂" Dia.

 

 

(190mm)

 

 

Fireplace Hearth

VO584-100

Fig. 31

Locate vent opening on wall.

 

Step 2

Measure wall thickness and cut zero clearance sleeve parts to proper length (MAXIMUM 12” / 305mm). Assemble sleeve and attach to firestop with #8 sheet metal screws (supplied). Install firestop assembly. (Fig. 32)

Zero clearance sleeve is only required for combustible walls.

Step 3

Place fireplace into position. Measure the vertical height (X) required from the base of the flue collars to the center of the wall opening. (Fig. 33)

DVRT41Direct Vent Gas Fireplace

Adjustable Zero

Max. Length 12"

(305mm)

Clearance Sleeve

 

 

#8 Screws (2)

#8 Screws (2)

 

 

#8 Screws

 

(2)

Firestop

 

Adjustable Zero Clearance Sleeve

ZCS101

 

Fig. 32 Adjustable zero clearance sleeve.

 

Step 4

Apply a band of silicone to the inner and outer flue collars of the fireplace and using appropriate length of pipe section(s) attach to fireplace with three (3) screws. Follow with the installation of the inner and outer elbow, again secure joints with three (3) sheet metal screws. Wipe off any excess high temperature sealant.

X

X

 

FP1181

Fig. 33

Vertical height requirements.

Step 5

Measure the horizontal length requirement including a 2” (51mm) overlap, i.e. from the elbow to the outside wall face plus 2” (51mm) (or the distance required if installing a second 90° elbow). (Fig. 34)

Always install horizontal venting on a level plane.

Step 6

Use appropriate length of pipe sections - telescopic or fixed - and install. The sections which go through the wall are packaged with the starter kit, and can be cut to suit if necessary.

10006740

17

Image 17
Contents Direct Vent Model DVRT41 Table of Contents Locating Your Fireplace Installation & Operating InstructionsFraming Dimensions Fireplace Dimensions Installed as Top VentFireplace Dimensions Installed as Rear Vent Clearance to Combustibles Mantel ChartMantels HearthGas Line Installation Gas SpecificationsFraming And Finishing Gas Inlet and Manifold PressuresEB-1 Electrical Box Alternate Switch LocationRemote ON/OFF Switch Installation EB-1 receptacle Optional Top Vent ApplicationLocation of Vent Termination General VentingGeneral Venting Information Termination Location Canadian Installations1 US Installations2USA Installations Canadian InstallationsGeneral Information Assembling Vent Pipes Flex Vent PipesRear Wall Vent Application How to Use the Vent GraphTwist Lock Pipes Step Rear Wall Vent InstallationVertical Sidewall Application Rear Wall Vent Installations Flex Vent PipeMaximum vent run with elbows Total angular variation 270Always install horizontal venting on a level plane Vertical Sidewall Installation Twist Lock PipeStep Vertical Sidewall Installation Flex Vent PipeVertical Through-the-Roof Application Below Grade InstallationPlace firestop spacers and secure Vertical Through-the-Roof InstallationTypical Roof SupportTypical Ceiling ApplicationSupport Venting Components Operating Instructions Log Identification Chart Installation of LogsBurner Lava Rock Placement Flame & Temperature AdjustmentSIT 820 Valve Flame CharacteristicsInspecting the Venting System To Turn Off Gas To Heater Lighting and Operating InstructionsTurning Off the Gas to the Appliance Lighting & Operating InstructionsLighting Instructions Transmitter Operation Off Mode Shut Off ProcedureOn Manual Mode Instructions for RF Comfort Control ValveAuto Mode Delay Timer ModeFan Override During Auto Mode Change Between F/C Temperature UnitsAuto Path LED Count Service ActionOn Path Local PathWindow Frame Assembly to be Removed Before Service Work Troubleshooting Honeywell VS8421SIT Nova 820 Millivolt Valve Trouble Shooting the Gas Control SystemSIT 822 Valve with a Honeywell Electronic Igniter Troubleshooting the Gas Control SystemNova SIT820 Valve Burner and Pilot Orifice ConversionLogs may be hot Installation PrecautionsConversion Procedure Depressd and turn center plunger Cleaning the Standing Pilot Control System MaintenanceLogs May Be HOT Burner and Burner CompartmentDVRT41 Description DVRT41DVRT41 LP to Natural Gas Fuel Conversion Kits Natural Gas to LPFK12 Fan Assembly Optional Accessories AvailableFK24 Fan Assembly Hard Direct Wire Hook UpCeramic Refractory Panels Remote ControlsDecorative Bay Windows Decorative Frame TrimConversion Instructions For Use in Mobile Homes Model DVRT41RMH9b.Units with Honeywell valve Limited Lifetime Warranty State % Fireplace Efficiency % Fan-OFF Fan-ON Efficiency RatingsModel EnerGuide Ratings

DVRT41 specifications

The Vermont Casting DVRT41 is a remarkable gas fireplace that harmoniously combines contemporary aesthetics with advanced heating technology. Designed to enhance any living space, the DVRT41 stands out with its impressive features and functionality, making it a popular choice for those looking to elevate their home environment.

One of the most notable features of the DVRT41 is its efficient heat output. With an impressive BTU range, this fireplace can warm spaces effectively while maintaining low emissions. This efficiency is complemented by Vermont Castings' commitment to sustainability, ensuring that the DVRT41 aligns with environmental considerations.

Aesthetically, the DVRT41 offers a customizable experience. Consumers can choose from various faceplate designs, glass door styles, and finishes to match any décor. The fireplace’s large viewing area provides an unobstructed view of the flames, creating a cozy atmosphere that’s perfect for gatherings or quiet evenings.

The DVRT41 incorporates advanced technologies aimed at maximizing user experience. The fireplace features an intuitive remote control for convenience, allowing users to adjust flame height and heat output easily. This adaptability ensures that homeowners can create the perfect ambiance at any time. The ignition system is designed for reliability and ease, ensuring that starting the fireplace is hassle-free, even in challenging conditions.

Safety is a top priority with the DVRT41. The unit includes features such as a safety shut-off system and a tempered glass front to prevent accidental burns. Additionally, the design allows for efficient venting, minimizing the risk of backdraft or buildup of harmful gases.

Maintenance is straightforward, thanks to the unit's design. The DVRT41 is constructed with durable materials that resist corrosion and wear, ensuring longevity and reduced upkeep costs. Regular cleaning is simple, ensuring that the fireplace remains functional and beautiful for years to come.

Overall, the Vermont Casting DVRT41 gas fireplace is not only a source of warmth but also a stunning focal point within any home. Its blend of efficiency, safety, and design flexibility make it a top choice for homeowners seeking an effective heating solution that doesn’t compromise on style or substance. The DVRT41 exemplifies Vermont Castings' commitment to quality, ensuring that every unit delivers exceptional performance and aesthetic appeal.