Enviro VENTED GAS FIREPLACE HEATER owner manual Vent Termination Restrictions

Page 14

Initial Installation

QUALIFIED INSTALLERS ONLY

VENT TERMINATION RESTRICTIONS:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

O

D

E

 

 

 

 

 

H

 

 

B

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

L

B

Fixed

 

 

B

 

 

 

G

F

Closed

Openable

Fixed

 

 

G

 

 

Openable

Closed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

B

 

A

 

J

 

 

K

 

 

 

 

 

 

 

 

 

 

 

 

I

A

 

Termination Cap

 

Air Supply Inlet

 

 

 

 

G

Gas Meter

Restriction Zone

 

 

 

 

 

 

 

 

 

(Termination not allowed)

 

Figure 15. Vent Termination Restrictions, refer to Table 2.

Table 2: Vent termination clearances, refer to Figure 15.

Letter

Canadian Installation 1

US Installation2

Description

A

12 in (30 cm)

Clearance above grade, verandah, porch, deck, or balcony.

 

 

 

 

B

12 in (30 cm)

9 in (23 cm)

Clearance from window or door that may be opened.

 

 

 

 

C

12 in (30 cm)*

Clearance from permanently closed window (to prevent

 

 

 

condensation).

 

 

 

D

24 in (60 cm)*

Vertical clearance to ventilated soffit located above the

 

 

 

terminal, within a horizontal distance of 2 ft (60 cm) from

 

 

 

center line of terminal.

 

 

 

E

18 in (45 cm)*

Clearance to unventilated soffit.

 

 

 

F

12 in (30 cm)*

Clearance to outside corner.

 

 

 

G

12 in (30 cm)*

Clearance to inside corner.

 

 

 

 

H

3 ft (91 cm) within a height of

3 ft (91 cm) within a height of

Clearance to each side of center line extended above

 

15 ft (4.5 m) above the meter/

15 ft (4.5 m) above the meter/

meter/regulator assembly.

 

regulator assembly

regulator assembly*

 

 

 

 

 

I

3 ft (91 cm)

3 ft (91 cm)*

Radial clearance around service regulator vent outlet.

 

 

 

 

J

12 in (30 cm)

9 in (23 cm)

Clearance to non-mechanical air supply inlet to building, or

 

 

 

the combustion air inlet to any other appliance.

 

 

 

 

K

6 ft (1.83 m)

3 ft (91 cm) above if within 10

Clearance to mechanical air supply inlet.

 

 

ft (3 m) horizontally

 

 

 

 

 

L

7 ft (2.13 m)t

7 ft (2.13 m)*t

Clearance above paved sidewalk or paved driveway located

 

 

 

on public property.

 

 

 

 

M

12 in / 30 cm+

12 in / 30 cm*+

Clearance under verandah, porch, deck, or balcony.

N

12 in (30 cm)*

Clearance horizontally to any surface (such as an exterior

 

 

 

wall) for vertical terminations.

 

 

 

O

12 in (30 cm)

Clearance above roof line for vertical terminations.

 

 

 

 

1In accordance with the current CSA B149, Natural Gas and Propane Installation Code.

2 In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.

* These numbers are only estimates. Clearance in accordance with installation codes and the requirements of the gas supplier.

t A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and it serves both dwellings. + Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

NOTE: Venting terminals shall not be recessed into walls or siding.

14

Image 14
Contents Installer ConsumerSafety Precautions GeneralTable of Contents This Enviro Ascot Fireplace Codes And ApprovalsVented GAS Fireplace Heater Ascot DV NG/LPG Specifications Dimensions of the AscotFor Your Safety Read Completely Before Operating Operating InstructionsComponent Sound & Reason Pilot flameMaintenance And Service SIT Valve on AscotFirebox Removing inner glass doorKit Parts List Conversion Kit InstallationRemoving valve screw Initial Installation Qualified Installers onlyRound Support Vent Termination Restrictions Installation Instructions KIT ComponentsInstallation of Fireplace Horizontal Vent Kit Manufacturer Trade Name Nominal Sizes4DSC Vent Restrictor Setting Cm at top, 11⁄2 3.8 cm at sides, 11⁄2 3.8 cm at bottom Twist-Lock ConnectionInstalling Vent Cap with Vinyl Siding Stand-Off Straight Through Wall Installation Support straps outwards, and push Sections until the height Multi-Story Vent Pipe Installation Canadian Installations InstallationWiring Diagram A. InstallationsVenting of a Fireplace Fitted with the Drafthood Adaptor Spillage TestOptional Finishing Automatic Safety Shut DownSpill Switch Replacement Seal Plate GAS Line Connection To Test Valve PressuresRecommended Thermostat Wire Size Secondary Installation Ascot Burner TrayEmber Placement Installation of Optional Blower Trouble Shooting Problem Possible Cause SolutionParts List Reference Description Part NumberCast Description Reference Cast Description Part Number DiagramParts Warranty To the DealerWarranty Warranty Installation Data Sheet