Enviro VENTED GAS FIREPLACE HEATER Cm at top, 11⁄2 3.8 cm at sides, 11⁄2 3.8 cm at bottom

Page 19

Initial Installation

QUALIFIED INSTALLERS ONLY

HORIZONTAL INSTALLATION:

STEP 1. Set the appliance in the desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the appliance.

STEP 2. Direct vent pipe and fittings are designed with special twist-lock connections. Assemble the desired combination of black pipe and elbows to the appliance adapter with pipe seams oriented towards the wall or floor, as much out of view as possible.

 

Place a

bead of

Mil-Pac on

the

10"

 

outer edge of the inner exhaust

(254mm)

 

 

 

pipe (non-flared end). Place a bead

 

Female

of high

temperature silicone

on

10"

the male edge of the outer pipe.

Locking

(254mm)

Lugs

Push the pipe sections completely

 

Sealant

together,

then

twist-lock

one

 

section clockwise approximately 1⁄4

 

Male

 

turn, until the two sections are fully

 

Locking

 

Lugs

locked. The female locking lugs will

 

 

not be visible from the outside, on

 

 

black pipe. They may be located by

 

Figure 21: Twist-Lock Connection

examining the inside of the female

 

ends as shown in Figure 21.

 

Figure 22: Wall Framing Hole for

 

 

Notes:

 

 

 

 

Horizontal Installation.

 

 

 

 

 

(1)Twist-lock procedure: four (4) indentations, located on the female end of the pipes and fittings, are designed to slide straight onto the male ends of adjacent pipes and fittings, by orienting the four pipe indentations so they match and slide into the four entry slots on the male end.

(2)Horizontal runs of vent pipe must be supported every three (3) feet. Wall straps are available for this purpose, also when running horizontal pipe minimum clearances to combustibles must be maintained;

2” (5.1 cm) at top, 11⁄2” (3.8 cm) at sides, 11⁄2” (3.8 cm) at bottom.

11/4"

 

(3.2cm)

 

Fold strap

Woodscrews

 

here

 

Sheet metal

 

screws

 

 

Wall Thimble

 

Strap

Figure 23: Installing Decorative Wall Thimble.

19

Image 19
Contents Consumer InstallerGeneral Safety PrecautionsTable of Contents Vented GAS Fireplace Heater Ascot DV NG/LPG Codes And ApprovalsThis Enviro Ascot Fireplace Dimensions of the Ascot SpecificationsOperating Instructions For Your Safety Read Completely Before OperatingPilot flame Component Sound & ReasonSIT Valve on Ascot Maintenance And ServiceRemoving inner glass door FireboxConversion Kit Installation Kit Parts ListRemoving valve screw Qualified Installers only Initial InstallationRound Support Vent Termination Restrictions KIT Components Installation InstructionsManufacturer Trade Name Nominal Sizes Installation of Fireplace Horizontal Vent Kit4DSC Vent Restrictor Setting Twist-Lock Connection Cm at top, 11⁄2 3.8 cm at sides, 11⁄2 3.8 cm at bottomInstalling Vent Cap with Vinyl Siding Stand-Off Straight Through Wall Installation Support straps outwards, and push Sections until the height Multi-Story Vent Pipe Installation A. Installations InstallationWiring Diagram Canadian InstallationsSpillage Test Venting of a Fireplace Fitted with the Drafthood AdaptorSpill Switch Replacement Automatic Safety Shut DownOptional Finishing Seal Plate To Test Valve Pressures GAS Line ConnectionRecommended Thermostat Wire Size Ascot Burner Tray Secondary InstallationEmber Placement Installation of Optional Blower Problem Possible Cause Solution Trouble ShootingReference Description Part Number Parts ListCast Description Reference Cast Description Part Number DiagramParts To the Dealer WarrantyWarranty Warranty Installation Data Sheet