INSTALLATION

COMBUSTION AIR SUPPLY

For a mobile home installation the stove must be connected to an outside source of combustion air. A 2” inside diameter metallic pipe, either flexible or rigid, may be attached to the inlet at the stove’s rear (refer to figures 5a, 5b, and 6). A rodent guard (minimum ¼” wire mesh)/wind hood must be used at the terminus (refer to figure 7). All connections must be secured and airtight by either using the appropriately sized hose clamp and/or UL-181-AP foil tape.

For mobile home installations only: 2” inside diameter pipe may be used for the first 5 feet of combustion air supply run. From 5 to 10 feet use 2 ¾” inside diameter pipe. No combustion air supply may exceed 10 feet.

Sources of Outside Combustion Air

a.In fireplaces

Chimney top.

Ash clean out door.

b.For freestanding installations

A hole in floor near stove rear terminating only in a ventilated crawl space.

A hole in the wall behind the stove.

WHEN OUTSIDE AIR IS NOT USED

If outside air is not used, it is important that combustion air is easily available to the air inlet. A closeable outside air register can be used in tightly insulated homes. In insert installations, flashing vents should not be restricted. The flashing should not necessarily seal the fireplace face.

VENTING

The Breckwell P22 Freestanding is certified for use with listed TYPE L-Vent, 3” or 4” diameter in size. The stove was tested with Simpson Duravent brand. Class “A” chimney is not required. Refer to the instructions provided by the vent manufacturer, especially when passing through a wall, ceiling or roof.

This is a pressurized exhaust system. All vent connector joints must be sealed with 500°F (260°C) RTV silicone sealant to ensure consistent performance and avoid smoke spillage. All horizontal connector joints must be sealed with UL-181-AP foil tape. We recommend that all vertical vent connector joints be secured with a minimum of 3 screws.

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.

INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER.

FIGURE 5a

FIGURE 5b

FIGURE 6

FIGURE 7

Image 6
Contents Economy Series P22 Introduction Important Information Safety Precautions Table of Contents Preparation InstallationSpecifications ClearancesWhen Outside AIR is not Used Combustion AIR SupplyVenting Assembling Pedestal or LEG SET Freestanding InstallationsEquivalent Vent Length EVL Horizontally Through Wall refer to FigureVertically with NEW Chimney System Refer to Figure Vertically Into Existing Chimney SystemInstallation Through Side of Masonry Chimney Vertically Into Existing Masonry FireplaceInsert Installations Assembling the Flashing SETWhen Vent Pipe Extends to Chimney TOP Refer to Figures 16 Chase dimensions shown are minimums and must be maintained AS a BUILT-IN FireplaceElectrical Installation Special Mobile Home RequirementsCombustion AIR Supply Operation Building a Fire Proper FuelPRE-START-UP Check Hotrod Automatic FirestarterSafety Features Breckwell Maintenance ToolShutdown Procedure RE-STARTING a Warm StoveOptional Thermostat Thermostat InstallationThermostat Installation ∙ a Millivolt Thermostat is RequiredPlease Read this ASH Removal MaintenanceCleaning ASH DisposalBlowers Chimney Cleaning Daily Weekly Annually or per TonTroubleshooting Guide Stove Shuts OFF and the # 2 Light FlashesPossible Causes Stove Shuts OFF and the # 3 Light Flashes Smoke Smell Coming Back Into the Home Stove Feeds PELLETS, but will not IgnitePossible Causes Possible Remedies Convection Blower Shuts OFF and Comes Back onTroubleshooting Guide Troubleshooting Guide Smoke Smell or Soot BUILD-UP High Limit Switch Keeps TrippingHeat Level Setting P22 Digital Circuit Board Timing RatesElectrical Diagram Replacement Parts BurnpotLifetime Limited Warranty