Breckwell P22I, P22FSL owner manual Vertically Into Existing Masonry Fireplace

Page 9

INSTALLATION

9

E.VERTICALLY INTO EXISTING MASONRY FIREPLACE

NOTE: Follow L-Vent chimney manufacturer’s instructions.

1.Have the masonry chimney inspected by a qualified chimney sweep or installer to determine its structural condition.

2.You will need a pipe length equal to the chimney height from the hearth. If outside combustion air is to be used, you will need a pipe length equal to the chimney height plus 18 inches.

3.Install a blanking plate and the chimney pipe, and if used the outside air pipe, as shown in Figure 12.

4.Attach the L-Vent adapter, a section of pipe and clean out tee, making sure the clean out tee is centered in the chimney flue area. Use RTV, metallic tape, and a minimum of three self-taping screws at all joint connections to ensure a tight seal.

5.Position the stove, adhering to the clearances in Figures 1 & 2.

6.Measure and build chimney top plate. Cut out holes for chimney pipe, and if used the outside air pipe. Install and seal with non-hardening mastic to prevent water leakage. Install vent cap.

F. INSTALLATION THROUGH SIDE OF MASONRY CHIMNEY

NOTE: Follow L-Vent chimney manufacturer’s instructions.

1.Position the stove, adhering to the clearances in Figures 1 & 2. Mark the center of the hole where the pipe is to pierce the masonry chimney.

2.It will be necessary to break out the masonry around the location of the pipe center mark. Use a 4-inch diameter hole for 3-inch pipe and 5-inch diameter hole for 4-inch pipe.

3.Measure and build chimney top plate. Cut out holes for chimney pipe, and if used the outside air pipe.

4.Install the tee on the bottom of the vertical pipe system and lower it down the chimney until the center branch of the tee is level with the center of the hole in the masonry, as shown in Figure 13.

5.Install and seal the top plate from step 3 with non- hardening mastic. Slip the storm collar over the pipe, and while holding the pipe at the proper elevation, affix the collar with a minimum of three ¼” stainless steel sheet metal screws. Seal all joints and seams around the collar.

6.Connect the horizontal pipe by pushing it through the hole in the masonry and lining it up with the branch in the tee. Push the pipe into the tee while twisting it to lock it into the tee.

7.If desired, once the horizontal pipe is in place, the space between the pipe and masonry may be filled with high-temperature grout.

8.Install the trim collar. An adjustable pipe length and adapter may be needed to finish the connection to the stove.

FIGURE 12

FIGURE 13

Image 9
Contents Economy Series P22 Important Information IntroductionSafety Precautions Table of Contents Specifications InstallationPreparation Clearances When Outside AIR is not Used Combustion AIR Supply Venting Equivalent Vent Length EVL Freestanding InstallationsAssembling Pedestal or LEG SET Horizontally Through Wall refer to FigureVertically Into Existing Chimney System Vertically with NEW Chimney System Refer to FigureVertically Into Existing Masonry Fireplace Installation Through Side of Masonry ChimneyAssembling the Flashing SET Insert InstallationsWhen Vent Pipe Extends to Chimney TOP Refer to Figures 16 AS a BUILT-IN Fireplace Chase dimensions shown are minimums and must be maintainedElectrical Installation Special Mobile Home RequirementsCombustion AIR Supply Operation PRE-START-UP Check Proper FuelBuilding a Fire Hotrod Automatic FirestarterShutdown Procedure Breckwell Maintenance ToolSafety Features RE-STARTING a Warm StoveThermostat Installation Thermostat InstallationOptional Thermostat ∙ a Millivolt Thermostat is RequiredPlease Read this Cleaning MaintenanceASH Removal ASH DisposalBlowers Daily Weekly Annually or per Ton Chimney CleaningTroubleshooting Guide Stove Shuts OFF and the # 2 Light FlashesPossible Causes Stove Shuts OFF and the # 3 Light Flashes Possible Causes Possible Remedies Stove Feeds PELLETS, but will not IgniteSmoke Smell Coming Back Into the Home Convection Blower Shuts OFF and Comes Back onTroubleshooting Guide Troubleshooting Guide Heat Level Setting P22 High Limit Switch Keeps TrippingSmoke Smell or Soot BUILD-UP Digital Circuit Board Timing RatesElectrical Diagram Burnpot Replacement PartsLifetime Limited Warranty