Regency U38-LP GAS Connection, GAS Pipe Pressure Testing, High Elevation U38-NG

Page 8

INSTALLATION

GAS CONNECTION

The gas line can be rigid pipe, or to make installation easier, use a listed flexible connec- tor if allowed by local codes. Copper may also be used if approved by local codes.

The gas connection at the valve is 3/8" NPT. For minimum and maximum supply pressure see the System Data Table.

System Data

U38 with 40,000 BTU

U38-NG: For 0 to 2000 feet altitude

U38-LP: For 0 to 4500 feet alttitude

 

Burner Inlet Orifice Sizes:

 

 

 

 

Natural Gas

Propane

 

Burner

#31

#50

 

 

 

 

 

 

 

Max. Input

 

 

 

 

Natural Gas

40,000 Btu/h

 

Propane

38,000 Btu/h

 

 

 

 

 

 

Min. Input

 

 

 

 

Natural Gas

22,000 Btu/h

 

Propane

20,000 Btu/h

 

 

 

 

 

Supply Pressure

 

 

 

Natural Gas

min. 5" w.c.

 

Propane

min. 12" w.c.

 

 

 

 

 

Manifold Pressure

 

 

 

Natural Gas

3.8"

+/- 0.2" w.c.

 

Propane

11"

+/- 0.2" w.c.

Electrical: 120 V. 1.13A 60Hz.

Circulation:Variablespeedfan,125/75CFM.

Log Set: Ceramic fiber, 7 per set.

System Data:

HIGH ELEVATION - U38-NG

For 2,000 - 4,500 feet altitude

Burner Inlet Orifice Sizes:

Natural Gas Burner #33

Max. Input Rating 36,000 Btu/h

Min. Input Rating 19,000 Btu/h

System Data

U38 Converted to 30,000 Btu

For 0 to 4500 feet altitude

 

Burner Inlet Orifice Sizes:

 

 

 

 

Natural Gas

Propane

 

 

 

Burner

#37

#52

 

 

 

 

 

 

 

 

 

Max. Input

 

 

 

 

 

Natural Gas

30,000 Btu/h

 

 

 

Propane

30,000 Btu/h

 

 

 

 

 

 

 

 

 

Min. Input

 

 

 

 

 

Natural Gas

15,000 Btu/h

 

 

 

Propane

15,000 Btu/h

 

 

 

 

 

 

 

 

 

Supply Pressure

 

 

 

 

 

Natural Gas

min. 5" w.c.

 

 

 

Propane

min. 12" w.c.

 

 

 

 

 

 

 

 

Manifold Pressure

 

 

 

 

Natural Gas

3.8"

+/- 0.2" w.c.

 

 

 

Propane

11"

+/- 0.2" w.c.

 

 

 

 

 

 

 

 

Electrical: 120 V. 1.13A 60Hz.

Circulation: Variable speed fan, 125/75 CFM.

Log Set: Ceramic fiber, 7 per set.

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pres- sures over 1/2 psig (14" w.c.).

The manifold pressure is controlled by a regu- lator built into the gas control, and should be checked at the pressure test point.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" position.

2)Loosen the "IN" (# 7) and/or "OUT" (# 6) pressure tap(s), turning counterclockwise with a 1/8" wide flat screwdriver.

3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.

4)Light the pilot and turn the valve to "ON" position.

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specified on the safety label.

6)When finished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" flat screwdriver. Screw should be snug, but do not over tighten.

S.I.T. Valve Description

1)Gas cock knob

2)Manual high/low adjustment

3)Pilot Adjustment

4)Thermocouple Connection

5)Main Operator

6)Outlet Pressure Tap

7)Inlet Pressure Tap

8)Pilot Outlet

9)Main Gas Outlet

10)Flange Securing Screw Holes

11)Alternative TC Connection Point

12)Thermoelectric Unit

13)Additional Valve Mounting Hole

8

Regency U38 ULTIMATE Freestanding Gas Stove

Image 8
Contents Ultimate U38 Freestanding Gas Stove Regency U38 Ultimate Freestanding Gas Stove To the New OwnerU38-NG & U38-LP Table of Contents Safety Label Copy of the Safety Label for the U38 Freestanding Gas StoveInstallation General Safety InformationInstallation Checklist Before YOU StartClearances to Combustibles U38-NG & U38-LP Reference DimensionsOptional Outside AIR Draft Hood High ElevationHigh Elevation U38-NG GAS Pipe Pressure TestingGAS Connection Burner Orifice Pilot assembly is now accessible for Steps 4 toConversion from Natual GAS to Propane LOG SET Installation Conversion to Lower BTU Rating for U38Natural Gas Conversion Kit 730-920 Contains Propane Conversion Kit 730-922 ContainsPins on Rear Log Support PinCutoutNotch Lava rockFront Door Installation Louver InstallationTest for Flue Spillage Optional Wall ThermostatOptional Remote Control WiringThermostat Wire Table Final CheckOperating Instructions Copy of the Lighting Plate Instructions Normal Operating Sounds GAS Appliances Pilot AdjustmentAeration Adjustment Maintenance Panel Door FAN MaintenanceInstalling Glass Removing Valve Magnetic type screwdriverDescription Parts ListU38 Main Assembly U38 Burner & LOG Assembly U38 Door Assemblies Warranty ConditionsInstaller Please complete the following information

U38-NG, U38-LP specifications

The Regency U38-LP and U38-NG are innovative gas fireplaces designed to deliver both warmth and elegance to any living space. These units exemplify modern craftsmanship while ensuring high efficiency, making them popular choices among homeowners looking to enhance their indoor ambiance.

One of the key features of the Regency U38 series is its versatile design. Both models can be easily installed in a variety of settings, including new constructions and retrofits. Their clean, contemporary lines and large viewing area provide a stunning focal point for any room, allowing for maximum enjoyment of the flames. The U38-LP operates on liquid propane, while the U38-NG uses natural gas, catering to different fuel preferences and availability.

Efficiency is a hallmark of the Regency U38 series. With an impressive thermal efficiency rating, both models ensure minimal heat loss while maximizing warmth output. This efficiency not only translates into cost savings on energy bills but also contributes to a more environmentally friendly home. The switchable electronic ignition system enhances their user-friendliness, providing instant warmth with the push of a button.

The construction of the U38 fireplaces is another standout feature. They are built using high-quality materials, including a robust steel body and premium glass, ensuring durability and performance over time. Among the optional features available are customizable media options, such as glass crystals or decorative logs, allowing homeowners to personalize their fireplace to suit their tastes.

Advanced technology sets the Regency U38 series apart from traditional fireplaces. The units come equipped with an integrated, thermostatic remote control that allows users to adjust the temperature effortlessly. Additionally, the advanced airflow system ensures even heat distribution throughout the room, while the fan assist option can further enhance heat circulation.

Safety features are paramount in the design of the U38 fireplaces. They include a built-in safety shutdown system that activates if any anomalies are detected, providing peace of mind for users.

In summary, the Regency U38-LP and U38-NG fireplaces offer an ideal combination of style, efficiency, and advanced technology. Their attractive design, customizable options, energy-saving performance, and comprehensive safety features make them an excellent choice for modern homes looking for effective heating solutions without compromising on aesthetics.